EN |
45
SMARTY XV v2020.2
SMARTY
4
XV
V
1.
1
Climate zone
Control typology
Control factor
Specific energy
consumption
(SEC)
SEC Class
AEC
AHS
[ kWh/m²/a ]
[ kWh/a ]
[ kWh/a ]
Average
Central demand control
0,85
-34,6
A
407
4413
Local demand control (opt. with 1 sensor)
0,65
-39,5
A
257
4528
Cold
Central demand control
0,85
-71,5
A+
944
8633
Local demand control (opt. with 1 sensor)
0,65
-77,5
A+
794
8857
W
arm
Central demand control
0,85
-10,9
E
362
1996
Local demand control (opt. with 1 sensor)
0,65
-15,2
E
212
2047
Declared typology
Bidirectional
Type of drive installed (fan)
Variable
Type of heat recovery system
Recuperative
Thermal efficiency of heat recovery
[ % ]
82
Maximum flow rate
[ m
3
/h ]
583
Electric
power
input
of
the
fan
drive
at
maximum
flow
rate
[ W ]
421
Sound power level (Lwa)
[ dB(A) ]
54
Reference flow
[ m
3
/s ]
0,1
13
Reference pressure difference
[ Pa ]
50
SPI
[ W/(m
3
/h) ]
0,4
Control factor and control typology
0,95
Declared maximum internal leakage rates
[ % ]
1,2
Declared maximum external leakage rates
[ % ]
1,2
Possition
and
description
of
visual
filter
warning
for
RV
U
’s
Timer
ErP
Compliance
2018
Internet address for disassembly instructions
www
.salda.lt
Summary of Contents for SMARTY XV Series
Page 1: ...SMARTY XV EN MOUNTING AND INSTALLATION INSTRUCTION...
Page 23: ...EN 23 SMARTY XV v2020 2 EKA NIS connection...
Page 30: ...30 EN SMARTY XV v2020 2 Figure 8 1 9 2 Smarty 2XV 1 1 Smarty 2XV 3XV 4XV 1 2 219 1017 0 1 2 PS...
Page 49: ...49 SMARTY XV v2020 2...
Page 50: ...50 SMARTY XV v2020 2...