4.2. PRODUCT DEFINITION.
4.2.1. Nomenclature.
SLC-8000-TWIN/3 PRO2 B1 WCO 0/AB147 208/208V EE521925
MOD BAT TWIN PRO2 2x3AB147 3x40A WCO EE521925
EE521925
Particular specifications of the client.
208V
Output voltage if it is not 220/230/240V AC.
208V
Input voltage if it is not 220/230/240V AC.
147
Last three characters of the battery code.
AB
Family of the battery according to Salicru's code.
0/
Equipment with no batteries but with the needed
accessories to fit them in.
CO
“Made in Spain” marking in the UPS and packaging
(custom issues).
W
Neutral equipment brand.
B0
No batteries and no space to install them.
B1
External batteries to the UPS enclosure and extra charger.
TWIN PRO2
Single phase input - output configuration.
TWIN/3 PRO2 Three phase input / single phase output equipment.
8000
Power in VA.
SLC
Brand acronym.
CF
Frequency converter (equipment with no batteries).
EE*
Particular specifications of the client.
CO
“Made in Spain” marking in the UPS and packaging
(custom issue).
W
Neutral equipment brand.
40A
Protection size.
3x
Quantity of fuses in parallel. Omitted for only one.
147
Last three characters of the battery code.
AB
Family of the battery according to Salicru's code..
3
Quantity of batteries in one string.
2x
Quantity of strings in parallel. Omitted for only one.
0/
Battery module with no batteries, but with the needed
accessories to fit them in.
TWIN PRO2
Battery module series.
MOD BAT
Battery module.
Note concerning batteries:
B0 and B1 acronyms, stated in the nomenclature are re-
lated with the batteries:
B0 The equipment is supplied with no batteries and no
accessories (screws and electrical cables). Batteries
belong to the client and they will be installed externally
to the UPS enclosure. Under request, it is possible to
supply these accessories, which are needed to inter-
connect them with the own the equipment.
B1 Equipment with extra battery charger. The UPS
is supplied with no batteries and no accessories
(screws and electrical cables).Under request, it is pos-
sible to supply these accessories, which are needed to
interconnect them with the own the equipment.
Those equipments requested with no batteries, their pur-
chasing, installation and connection will be borne by the
client and
under his responsibility
.
Data concerning batteries in respect of quantity, capacity
and voltage are stated in the battery label sticked beside
the nameplate of the equipment,
respect this data and
their polarity strictly
when connecting them.
SLC TWIN PRO2