DC POWER SUPPLY DEVICE.
THYRISTOR-CONTROLLED CHARGER RECTIFIER 12 PULSE.

DC POWER-L Series 12 pulse

DC-75-L 12P 110V EE671774-1

Summary of Contents for DC POWER-L DC-75-L 12P 110V EE671774-1

Page 1: ...P DOWN LIGHT DIMMERS ILUEST POWER SOURCES STATIC INVERTERS PHOTOVOLTAIC INVERTERS LINE VOLTAGE STABILISERS MANUAL EE671774 1 DC POWER SUPPLY DEVICE THYRISTOR CONTROLLED CHARGER RECTIFIER 12 PULSE DC P...

Page 2: ...2 USER MANUAL...

Page 3: ...eception and unpacking 6 2 Packing list and contents 6 3 Storage 7 Installation 7 1 Look after your safety 7 2 Considerations to take into account 7 3 Earth connection terminal or strip 7 4 Connection...

Page 4: ...fied per sonnel Although no effort has been spared to ensure that the information in this user manual is complete and accurate we accept no liability for any errors or omissions that may exist The ima...

Page 5: ...e device is installed and operating it is recom mended to keep the documentation pendrive in a safe and easy to access location for future reference If a system differs from that shown in the figures...

Page 6: ...Part 7 Safety requirements IEC 60146 1 1 Semiconductor converters General re quirements and line commutated converters Part 1 1 Speci fication of basic requirements IEC EN 61204 3 Low voltage power su...

Page 7: ...th the protection will always be single pole so as not to disconnect the pole from earth The entry of connection cables is through the base of the cab inet Optionally and on request cable entry can be...

Page 8: ...ker Q2 Battery circuit breaker Q3 Input terminals R S T Battery terminals Output terminals Cable input gland Earth Terminal Alarm interface X32 see Table 2 Interface Aux Contacts X34 refer to Table 3...

Page 9: ...ck format with a 623 x 803 mm base The dimensions of the rectifier and battery cabinets are the same and the only external difference is the control panel on the device The device can operate with PbC...

Page 10: ...tage 110 Rated output voltage with positive to earth 110 Rated output voltage with negative to earth L Device series standard version only single phase devices with 5 ripple and no Schuko socket LP De...

Page 11: ...n the event of input mains failure or output overloads 5 2 2 AC input For greater versatility the system can be either single phase or three phase Regardless of the topology of the mains protection el...

Page 12: ...erride con trol the control is transferred to another current PID when one of the current limits is exceeded batteries or rectifier A selective control enables automatic switching between the two curr...

Page 13: ...event of input wave voltage and frequency variations The output current of each charger is equal to the current de manded by 100 of the loads plus the maximum charging cur rent of the battery accordi...

Page 14: ...tions Each automatic deactivation automatically recalculates the next periodic trip Table 5 Activation and deactivation of fast charging Exceptional charging Automatic Manual Periodic Activation No Vi...

Page 15: ...if re quested in the order cardboard box expanded polystyrene EPS corners polyethylene cover and polyester strapping All of these materials are recyclable so any disposal must be carried out in accord...

Page 16: ...6 3 Storage The device should be stored in a dry ventilated room and pro tected from rain dust and water or chemical splashes It is advisable to keep devices and batteries in their original pack agin...

Page 17: ...artup operations The surface on which the system is to be installed must be properly prepared to support its weight and level to prevent the metal structure from having to withstand unnecessary and ha...

Page 18: ...the accumulator bank with the resultant risk It should never be forgotten that the DC Power L with batteries is a generator of electrical power regardless of whether the batteries are installed in the...

Page 19: ...ase or three phase AC power supply network All of the protections or disconnectors of the system must be in the Off position and in particular that of the the batteries of the device Q3 and its counte...

Page 20: ...cables red for positive and black for negative and the polarity indicated on the labelling of the device Connect the load or loads to the earth terminal or strip It is recommended to distribute the o...

Page 21: ...tically or manually Exceptional charging Exceptional charging is forced manually at the will of the operator via the control panel 8 1 Startup procedure Set battery circuit breaker Q3 to On In systems...

Page 22: ...appears when the device starts up It is also the screen that appears when is pressed to exit any of the other menus or sub menus of the control panel with LCD The first line shows the voltage and outp...

Page 23: ...eway to the device s switching menu Screen 2 2 Manual and forced activation of fast charging 9 3 4 User Parameters menu To access this menu from the home screen press the forward key three times Use k...

Page 24: ...MP C MIN T COMP C QUICK CHARGING MAX T min PERIODIC CHARGING INTERVAL Days BATT FLOAT CHARGE TIME h LOW BATTERY VOLTAGE x x x x V OUTPUT VOLTAGE LOW V INSULATION ALARM Kohm INSULATION MEASUREMENT S N...

Page 25: ...auxiliary contact closed Urgent 5 Current leakage alarm Isol res approx 5 K Isol res approx 5 K Not urgent 5 Electrolyte level low alarm Electrolyte low level Electrolyte normal level Not urgent 1 Ch...

Page 26: ...C input failure Phase rotation error RELE 2 EMERGENCY fault Output overvoltage Output undervoltage High battery voltage Low battery voltage Battery fuse blown Rectifier fuse blown Input switch open Ou...

Page 27: ...lower than the nominal setting of the device Screen 6 6 Use this screen to set the rectifier s overload alarm threshold Screen 6 7 Use this screen to activate or deactivate the rectifier output isola...

Page 28: ...itors The service life of the capacitors in the DC bus and those used for input and output filtering depends on use and environmental conditions Preventative replacement by authorised technical person...

Page 29: ...r Batteries in system cabinet Fuses Batteries in external cabinet Fuses General output switch Disconnector Soft start Yes COMMUNICATION AND ALARMS Slot Yes one pre connected as standard SNMP Remote ma...

Page 30: ...y depending on their temperature they can function as insulators or conductors It is a one way device because it only transmits the current in a single direction It is generally used to control electr...

Page 31: ...31 SALICRU...