background image

12

5.2.6.  Battery.

The device will function as a stand-alone power source even 
when the AC input mains fail, supplying voltage to the load con-
nected to the output of the device by means of its backup battery.
To keep the battery in an optimum state and ensure a maximum 
life, the system monitors the current and voltage of the battery at 
all times, as well as the temperature of the battery room in order 
to enable the appropriate compensations to be made.
The system can charge all kinds of PbCa or NiCd batteries, ei-
ther sealed or with maintenance. Batteries with maintenance can 
optionally include in their cells an electrolyte level detector to pro-
vide low level alarms.
The rectifier cabinet has battery fuses at both poles, which, in ad-
dition to providing the respective protection, facilitate connection 
in systems with battery banks external to the device.

5.2.7.  Output filter.

For output ripple reduction, an LC filter is incorporated to keep 
the ripple voltage and current levels within the established limits 
and ensure correct operation of the output loads and the ex-
pected life of the battery.
The system also includes all necessary filters to ensure compli-
ance with the electromagnetic compatibility standards required 
for CE marking.

5.2.8.  DC output.

The isolation offered by the transformer allows a floating output 
with respect to the input, which enables earthing of either of the 
two output terminals (poles).

5.2.9.  Control/Display.

The vital constants of the source are controlled digitally through a 
microprocessor which is also responsible for managing the set-
tings and measurements shown on the LCD display.
All rectifiers are identical in operation regardless of the format, 
power and input/output voltage.

5.2.9.1.  Control.

In normal operating mode, a PID is responsible for regulating the 
desired output voltage.
By means of an automatic priority change system (override con-
trol), the control is transferred to another current PID when one of 
the current limits is exceeded: batteries or rectifier.
A selective control enables automatic switching between the two 
currents to ensure that neither of the two limits is ever exceeded.

5.2.10.  Relay interface (X32).

All systems incorporate as standard a relay interface with four 
relays (*), a battery temperature sensor for measuring and com-
pensating the float voltage in relation to it and an Ethernet/SNMP 
adapter slot, plus three additional relays, an electrolyte level de-
tection input for NiCd batteries and ports RS-232 and RS-485 in 
their extended COM version.

(*) The relay table corresponds to the extended COM ver-
sion (relays from 1 to 9). 

The standard relays included on the control board are 10, 11, 12 
and 13.

Relay nº.

Description of relay programming

1

Reserved

2 and 10

Groups the following alarms:

- Input failure

- RS and/or ST and/or TR input undervoltage

3 and 11

Groups the following alarms:

- Rectifier overload

- Battery overtemperature

- Battery current high

- Heat sink overtemperature

- Battery voltage low

- Battery overvoltage

- RS and/or ST and/or TR input overvoltage

- Output voltage low

- Output voltage high

- Electrolyte level low

4 and 12

Groups the following alarms:

- Isolation f 

(2)

- Isolation failure – 

(2)

5 and 13

Reserved

Table 2. 

Description of standard relay programming (X32).

Other configurations are available on request, but always in the 
factory or later by 

TSS

, and associating any of the system alarms 

with one of the relays interchangeably and even associating 
more than one alarm with the same relay.

5.2.11.  Interface auxiliary contacts (X34).

The system incorporates an interface of auxiliary contacts in 
the Input 

(Q1)

, Output 

(Q2)

 and Batteries 

(Q3)

 protections, all of 

them wired to terminals.

Terminal

Alarm

Contact

A

Input circuit breaker 

(Q1)

 (position)

NA

B

Input circuit breaker 

(Q1)

 (trip)

NA

C

Battery circuit breaker 

(Q3)

 (position)

NA

D

Battery circuit breaker 

(Q3)

 (trip)

NA

E

Output circuit breaker 

(Q2)

 (position)

NA

F

Output circuit breaker 

(Q2)

 (trip)

NA

Table 3. 

Description auxiliary contacts (X34).

USER MANUAL

Summary of Contents for DC POWER-L Series

Page 1: ...P DOWN LIGHT DIMMERS ILUEST POWER SOURCES STATIC INVERTERS PHOTOVOLTAIC INVERTERS LINE VOLTAGE STABILISERS MANUAL EE671774 1 DC POWER SUPPLY DEVICE THYRISTOR CONTROLLED CHARGER RECTIFIER 12 PULSE DC P...

Page 2: ...2 USER MANUAL...

Page 3: ...eception and unpacking 6 2 Packing list and contents 6 3 Storage 7 Installation 7 1 Look after your safety 7 2 Considerations to take into account 7 3 Earth connection terminal or strip 7 4 Connection...

Page 4: ...fied per sonnel Although no effort has been spared to ensure that the information in this user manual is complete and accurate we accept no liability for any errors or omissions that may exist The ima...

Page 5: ...e device is installed and operating it is recom mended to keep the documentation pendrive in a safe and easy to access location for future reference If a system differs from that shown in the figures...

Page 6: ...plies d c output Part 7 Safety requirements Reference standard IEC EN 60950 1 Information technology equipment Safety Part 1 General requirements IEC EN 61204 3 Low voltage power supply devices d c ou...

Page 7: ...o earth the protection will always be single pole so as not to disconnect the pole from earth The entry of connection cables is through the base of the cab inet Optionally and on request cable entry c...

Page 8: ...ker Q2 Battery circuit breaker Q3 Input terminals R S T Battery terminals Output terminals Cable input gland Earth Terminal Alarm interface X32 see Table 2 Interface Aux Contacts X34 refer to Table 3...

Page 9: ...ck format with a 623 x 803 mm base The dimensions of the rectifier and battery cabinets are the same and the only external difference is the control panel on the device The device can operate with PbC...

Page 10: ...ltage 110 Rated output voltage with positive to earth 110 Rated output voltage with negative to earth L Device series standard version only single phase devices with 5 ripple and no Schuko socket LP D...

Page 11: ...n the event of input mains failure or output overloads 5 2 2 AC input For greater versatility the system can be either single phase or three phase Regardless of the topology of the mains protection el...

Page 12: ...erride con trol the control is transferred to another current PID when one of the current limits is exceeded batteries or rectifier A selective control enables automatic switching between the two curr...

Page 13: ...event of input wave voltage and frequency variations The output current of each charger is equal to the current de manded by 100 of the loads plus the maximum charging cur rent of the battery accordi...

Page 14: ...tions Each automatic deactivation automatically recalculates the next periodic trip Table 5 Activation and deactivation of fast charging Exceptional charging Automatic Manual Periodic Activation No Vi...

Page 15: ...if re quested in the order cardboard box expanded polystyrene EPS corners polyethylene cover and polyester strapping All of these materials are recyclable so any disposal must be carried out in accord...

Page 16: ...6 3 Storage The device should be stored in a dry ventilated room and pro tected from rain dust and water or chemical splashes It is advisable to keep devices and batteries in their original pack agin...

Page 17: ...up operations The surface on which the system is to be installed must be properly prepared to support its weight and level to prevent the metal structure from having to withstand unnecessary and harmf...

Page 18: ...e accumulator bank with the resultant risk It should never be forgotten that the DC Power L with batteries is a generator of electrical power regardless of whether the batteries are installed in the s...

Page 19: ...phase or three phase AC power supply network All of the protections or disconnectors of the system must be in the Off position and in particular that of the the batteries of the device Q3 and its cou...

Page 20: ...bles red for positive and black for negative and the polarity indicated on the labelling of the device Connect the load or loads to the earth terminal or strip It is recommended to distribute the outp...

Page 21: ...tically or manually Exceptional charging Exceptional charging is forced manually at the will of the operator via the control panel 8 1 Startup procedure Set battery circuit breaker Q3 to On In systems...

Page 22: ...main screen of the system which appears when the device starts up It is also the screen that appears when is pressed to exit any of the other menus or sub menus of the control panel with LCD The first...

Page 23: ...Screen 2 1 This is the gateway to the device s switching menu Screen 2 2 Manual and forced activation of fast charging 9 3 4 User Parameters menu To access this menu from the home screen press the fo...

Page 24: ...MP C MIN T COMP C QUICK CHARGING MAX T min PERIODIC CHARGING INTERVAL Days BATT FLOAT CHARGE TIME h LOW BATTERY VOLTAGE x x x x V OUTPUT VOLTAGE LOW V INSULATION ALARM Kohm INSULATION MEASUREMENT S N...

Page 25: ...auxiliary contact closed Urgent 5 Current leakage alarm Isol res approx 5 K Isol res approx 5 K Not urgent 5 Electrolyte level low alarm Electrolyte low level Electrolyte normal level Not urgent 1 Ch...

Page 26: ...C input failure Phase rotation error RELE 2 EMERGENCY fault Output overvoltage Output undervoltage High battery voltage Low battery voltage Battery fuse blown Rectifier fuse blown Input switch open Ou...

Page 27: ...lower than the nominal setting of the device Screen 6 6 Use this screen to set the rectifier s overload alarm threshold Screen 6 7 Use this screen to activate or deactivate the rectifier output isola...

Page 28: ...itors The service life of the capacitors in the DC bus and those used for input and output filtering depends on use and environmental conditions Preventative replacement by authorised technical person...

Page 29: ...Batteries in system cabinet Fuses Batteries in external cabinet Fuses General output switch Disconnector Soft start Yes COMMUNICATION AND ALARMS Slot Yes one pre connected as standard SNMP Remote mai...

Page 30: ...y depending on their temperature they can function as insulators or conductors It is a one way device because it only transmits the current in a single direction It is generally used to control electr...

Page 31: ...31 SALICRU...

Page 32: ...R EGYPT PHILIPPINES NETHERLANDS INDONESIA IRELAND JORDAN KUWAIT MALAYSIA PERU POLAND CZECH REPUBLIC RUSSIA SWEDEN SWITZERLAND THAILAND TUNISIA UAE URUGUAY VENEZUELA VIETNAM REST OF THE WORLD Product r...

Reviews: