background image

18

When the protection consists of fuses, these are supplied 

already inserted into the fuse holder base, as the batteries 

themselves are not delivered already installed in the cabinet. 

This way, any loss or mislaying is avoided.

• 

The batteries are always supplied in packaging separate to 

the device cabinet or accumulator cabinet or cabinets. Con-

sequently, it will be necessary to install and connect them 

according to the connection diagram supplied with the docu-

mentation, using the accessories provided, such as strips, 

cables and screws.
Start the process by placing the batteries in the lower tray to 

secure the cabinet, ensuring that the centre of gravity is as 

low as possible, and work your way up as the trays are filled.

• 

In systems with removable trays, it is advisable to insert 

them as they fill up, thus avoiding unnecessary mechanical 

stresses on the frame itself, which can lead to structural tor-

sion.

 

ˆ

To remove each battery tray, it is necessary to remove 

the two screws

 

 that fix it like a mechanical lock located 

on either side of the front.

 

ˆ

Wait until the end to connect the end cables be-

tween levels, otherwise there is a risk of electric 

shock.

 

ˆ

Fill up the trays with the accumulators one by one, inter-

connect the batteries between them and insert each tray 

as individual tasks are completed on each of them.
Fit the two screws

 

which act as a lock and tighten them.

 

ˆ

Then connect the batteries between levels, observing 

the safety instructions indicated in this document and in 

EK266*08.

• 

Dangerous voltages stored in batteries

: Precau-

tions must be taken with the batteries once intercon-

nected, as there may be dangerous voltage between the 

terminals of different batteries or between one of them and 

the earth, depending on the total voltage of the bank, in-

cluding when the device is disconnected.

• 

In systems with 0/ or 0A/ backup, the acquisition, installation 

and connection of batteries will always be carried out 

under 

the responsibility

 of the customer. Information concerning 

the batteries in terms of number, capacity and voltage is indi-

cated on the battery label affixed next to the device’s name-

plate. 

Strictly observe

 this information, the connection 

polarity of the batteries and the connection diagram supplied 

with the documentation and the DC Power-L.

• 

Any handling and connection of the batteries should 

only be carried out or supervised by 

suitably quali-

fied personnel

.

Before carrying out any action, disconnect the batteries. 

Check that no current is present and that there is no dan-

gerous voltage at the ends of the terminals of the battery 

bank.
The battery circuit is isolated from the input voltage of devices 

with floating output voltage, but not from devices with output 

voltage referenced to earth. Dangerous voltages can occur 

between the terminals of the battery bank and the earth.
Check that the system does not have input voltage before 

working on the batteries, otherwise the rectifier will supply 

DC voltage to the cables connected to the accumulator bank, 

with the resultant risk.

• 

It should never be forgotten that the DC Power-L with 

batteries is a generator of electrical power, regardless 

of whether the batteries are installed in the same cabinet or in 

the device itself, so the user must take all necessary precau-

tions against direct or indirect contact.

If the batteries are connected to the device and its protec-

tions are set to ‘On,’ it is irrelevant whether or not the DC 

Power-L is connected to the power supply, as is the state or 

position (On or Off) of its protection.
The output terminals will supply voltage while the battery 

bank has power, unless the output disconnector switch 

(Q2)

 

is ‘Off’ or, if there is output distribution, the general protection 

of the output distribution or each of the individual output dis-

tribution protections is set to ‘Off.’

• 

Dangerous voltages stored in capacitors

:

 

Precau-

tions must be taken as charged capacitors with dan-

gerous voltages may be installed between the connection 

terminals or between one of them and earth, even when the 

device is switched off. Wait 30 seconds or more to allow 

these to discharge.

7.2.  Considerations to take into 

account.

• 

The location should be spacious, airy and easily accessible. 

The slots of the ventilation should never be obstructed, nor 

should the device be installed outdoors.

• 

The cross sections of the input, output and earth cables must 

be in accordance with the rated current indicated on the 

nameplate, and compliance with the country’s regulations 

and legislation is an essential requirement.

• 

A bad connection or operation can cause faults in the device 

and/or the loads connected to it. Read the instructions in this 

manual carefully and follow the steps indicated in the order 

established.

• 

The base of the cabinet features a number of wall bushings 

(cable glands, Fig. 2), to isolate the routing of the connection 

cables through the metal sheet of the cabinet.
Cut them to the appropriate section to enable the respec-

tive input, output and battery cables to pass through them in 

models with the accumulators in a separate cabinet.
Upon request, some cabinets can have a slot to serve as a 

conduit for cable entry, instead of the wall bushings.

• 

All of the cables will be fixed to the bar by clips in order to im-

mobilise them and prevent possible pulling that could lead to 

false contacts, cable disconnection, etc., and consequently, 

to failures of the device and/or possible accidents due to 

electric shock.

7.3.  Earth connection, terminal or 

strip  .

• 

It is advisable, 

and so required by

 the regulations or legisla-

tion of the country, to 

connect the device to earth

.

Make sure that all of the device’s loads are only connected 

to earth in the form of a terminal or strip. Failure to limit the 

earthing of the loads to this 

single point

 would create earth 

return loops and degrade the quality of the power supplied.
All terminals identified as an earth connection 

( )

 are linked 

together and to the earth of the cabinet.

• 

For models with batteries in a separate cabinet, connect 

the terminal or strip 

 

of the earth of the rectifier, to the earth 

bonding terminal

( )

 of the accumulator cabinet, using the 

cable provided in the battery connections hose.

USER MANUAL

Summary of Contents for DC POWER-L Series

Page 1: ...P DOWN LIGHT DIMMERS ILUEST POWER SOURCES STATIC INVERTERS PHOTOVOLTAIC INVERTERS LINE VOLTAGE STABILISERS MANUAL EE671774 1 DC POWER SUPPLY DEVICE THYRISTOR CONTROLLED CHARGER RECTIFIER 12 PULSE DC P...

Page 2: ...2 USER MANUAL...

Page 3: ...eception and unpacking 6 2 Packing list and contents 6 3 Storage 7 Installation 7 1 Look after your safety 7 2 Considerations to take into account 7 3 Earth connection terminal or strip 7 4 Connection...

Page 4: ...fied per sonnel Although no effort has been spared to ensure that the information in this user manual is complete and accurate we accept no liability for any errors or omissions that may exist The ima...

Page 5: ...e device is installed and operating it is recom mended to keep the documentation pendrive in a safe and easy to access location for future reference If a system differs from that shown in the figures...

Page 6: ...plies d c output Part 7 Safety requirements Reference standard IEC EN 60950 1 Information technology equipment Safety Part 1 General requirements IEC EN 61204 3 Low voltage power supply devices d c ou...

Page 7: ...o earth the protection will always be single pole so as not to disconnect the pole from earth The entry of connection cables is through the base of the cab inet Optionally and on request cable entry c...

Page 8: ...ker Q2 Battery circuit breaker Q3 Input terminals R S T Battery terminals Output terminals Cable input gland Earth Terminal Alarm interface X32 see Table 2 Interface Aux Contacts X34 refer to Table 3...

Page 9: ...ck format with a 623 x 803 mm base The dimensions of the rectifier and battery cabinets are the same and the only external difference is the control panel on the device The device can operate with PbC...

Page 10: ...ltage 110 Rated output voltage with positive to earth 110 Rated output voltage with negative to earth L Device series standard version only single phase devices with 5 ripple and no Schuko socket LP D...

Page 11: ...n the event of input mains failure or output overloads 5 2 2 AC input For greater versatility the system can be either single phase or three phase Regardless of the topology of the mains protection el...

Page 12: ...erride con trol the control is transferred to another current PID when one of the current limits is exceeded batteries or rectifier A selective control enables automatic switching between the two curr...

Page 13: ...event of input wave voltage and frequency variations The output current of each charger is equal to the current de manded by 100 of the loads plus the maximum charging cur rent of the battery accordi...

Page 14: ...tions Each automatic deactivation automatically recalculates the next periodic trip Table 5 Activation and deactivation of fast charging Exceptional charging Automatic Manual Periodic Activation No Vi...

Page 15: ...if re quested in the order cardboard box expanded polystyrene EPS corners polyethylene cover and polyester strapping All of these materials are recyclable so any disposal must be carried out in accord...

Page 16: ...6 3 Storage The device should be stored in a dry ventilated room and pro tected from rain dust and water or chemical splashes It is advisable to keep devices and batteries in their original pack agin...

Page 17: ...up operations The surface on which the system is to be installed must be properly prepared to support its weight and level to prevent the metal structure from having to withstand unnecessary and harmf...

Page 18: ...e accumulator bank with the resultant risk It should never be forgotten that the DC Power L with batteries is a generator of electrical power regardless of whether the batteries are installed in the s...

Page 19: ...phase or three phase AC power supply network All of the protections or disconnectors of the system must be in the Off position and in particular that of the the batteries of the device Q3 and its cou...

Page 20: ...bles red for positive and black for negative and the polarity indicated on the labelling of the device Connect the load or loads to the earth terminal or strip It is recommended to distribute the outp...

Page 21: ...tically or manually Exceptional charging Exceptional charging is forced manually at the will of the operator via the control panel 8 1 Startup procedure Set battery circuit breaker Q3 to On In systems...

Page 22: ...main screen of the system which appears when the device starts up It is also the screen that appears when is pressed to exit any of the other menus or sub menus of the control panel with LCD The first...

Page 23: ...Screen 2 1 This is the gateway to the device s switching menu Screen 2 2 Manual and forced activation of fast charging 9 3 4 User Parameters menu To access this menu from the home screen press the fo...

Page 24: ...MP C MIN T COMP C QUICK CHARGING MAX T min PERIODIC CHARGING INTERVAL Days BATT FLOAT CHARGE TIME h LOW BATTERY VOLTAGE x x x x V OUTPUT VOLTAGE LOW V INSULATION ALARM Kohm INSULATION MEASUREMENT S N...

Page 25: ...auxiliary contact closed Urgent 5 Current leakage alarm Isol res approx 5 K Isol res approx 5 K Not urgent 5 Electrolyte level low alarm Electrolyte low level Electrolyte normal level Not urgent 1 Ch...

Page 26: ...C input failure Phase rotation error RELE 2 EMERGENCY fault Output overvoltage Output undervoltage High battery voltage Low battery voltage Battery fuse blown Rectifier fuse blown Input switch open Ou...

Page 27: ...lower than the nominal setting of the device Screen 6 6 Use this screen to set the rectifier s overload alarm threshold Screen 6 7 Use this screen to activate or deactivate the rectifier output isola...

Page 28: ...itors The service life of the capacitors in the DC bus and those used for input and output filtering depends on use and environmental conditions Preventative replacement by authorised technical person...

Page 29: ...Batteries in system cabinet Fuses Batteries in external cabinet Fuses General output switch Disconnector Soft start Yes COMMUNICATION AND ALARMS Slot Yes one pre connected as standard SNMP Remote mai...

Page 30: ...y depending on their temperature they can function as insulators or conductors It is a one way device because it only transmits the current in a single direction It is generally used to control electr...

Page 31: ...31 SALICRU...

Page 32: ...R EGYPT PHILIPPINES NETHERLANDS INDONESIA IRELAND JORDAN KUWAIT MALAYSIA PERU POLAND CZECH REPUBLIC RUSSIA SWEDEN SWITZERLAND THAILAND TUNISIA UAE URUGUAY VENEZUELA VIETNAM REST OF THE WORLD Product r...

Reviews: