background image

19

SALICRU

• 

The DC Power-L can be supplied from the factory with con-

nection of positive to earth, negative to earth or float. On the 

nameplate and terminal labelling, the type of connection is 

identified by means of symbols ‘+’ or ‘–’ placed before the 

value of the output voltage and the symbol for live pole is 

indicated.
It is 

very important

 to ensure that the loads to be connected 

to the device have the same type of connection as this one, 

otherwise it would pose a risk to personnel and destroy the 

system and associated devices.
By default and if not indicated otherwise, all devices have 

floating output voltage.

• 

It is recommended to use shielded cables for com-

munications, as well as the earth connection of the 

screen through the terminal or strip.

7.4.  Connection of the system to the 

cabinet or battery bank. 

• 

This operation is only intended for the connection between 

the battery terminals of a system and the respective ones 

of the cabinet or cabinets, or battery bank, regardless of 

whether the batteries are owned by the customer or supplied 

with the device.
All of the instructions concerning the physical installation of 

each of the elements inside the system or battery cabinet are 

described in Section 7.1.

• 

All of the protections or disconnectors of the system must be 

in the ‘Off’ position and, in particular, that of the the batteries 

of the device 

(Q3)

 and its counterpart 

(Q8)

 in the accumulator 

cabinet, when it has an external battery bank.

Since the fuses of the disconnectors are supplied al-

ready installed to prevent them from being lost or mis-

laid, it is important to check that the disconnectors are open 

(Off).

• 

Connect the cable hose, usually supplied, between termi-

nals of the system and those of the battery cabinet or bank, 

respecting the colour of the cables (red for (+), black for (–) 

and green-yellow for the earth bonding 

( )

) as well as the 

polarity indicated on the label of the device (see Fig. 7).

• 

 

In systems with more than one battery cabinet/bank, 

the connection in parallel between them and the 

system will be taken into account according to each particular 

case. The battery connection diagram supplied with the doc-

umentation will always take precedence.

Battery terminals in 

accumulator cabinet.

Battery terminals in 

rectifier cabinet.

Fig. 7. 

Connection of the system to a battery cabinet.

• 

Do not start the system without having previously con-

nected the batteries to the device.

7.5.  Connection to the main single-

phase or three-phase AC power 

supply network.

• 

All of the protections or disconnectors of the system must be 

in the ‘Off’ position and, in particular, that of the the batteries 

of the device 

(Q3)

 and its counterpart 

(Q8)

 in the accumulator 

cabinet, when it has an external battery bank.

Since the fuses of the disconnectors are supplied al-

ready installed to prevent them from being lost or mis-

laid, it is important to check that the disconnectors are open 

(Off).

• 

The earth connection

 ( )

 of the device must be con-

nected to the terminal or strip, making sure that this is 

done before connecting the voltage to the input of the device.

• 

Connect the power supply cables to the terminals indicated

 

 

for single-phase devices 

F, N

 or for three-phase systems 

R, 

S, T, N,

 respecting the order of the phase or phases and the 

neutral indicated on the labelling of the DC Power-L.

 

ˆ

If the phase order is not respected, the three-

phase device will not work.

7.6.  Connection of the loads to DC 

output terminals.

• 

The earth connection 

( )

 of the device must be connected 

to the terminal or strip intended for that purpose, making sure 

that this is done before connecting the voltage to the input of 

the device.

• 

The DC Power-L can be supplied from the factory with posi-

tive or negative connection referenced to earth, or float. On 

the nameplate and terminal labelling, the type of connection 

is identified by means of symbols ‘+’ or ‘–’ placed before the 

value of the output voltage and the symbol for live pole is 

indicated.

By default and if not indicated otherwise, all de-

vices are dispatched from the factory with floating 

output voltage.

It is 

very important

 to ensure that the loads to be con-

nected to the device have the same type of connec-

tion as this one, otherwise it would pose a risk to personnel 

and destroy the system and associated devices.

• 

The type of output protection is predetermined and estab-

lished as follows:

 

ˆ

For floating output, two-pole protection.

 

ˆ

For output with positive referenced to earth, single-pole 

protection in negative pole.

 

ˆ

For output with negative referenced to earth, single-pole 
protection in positive pole.

The type of output protection is also applicable to the battery 

switch or protection and to any DC distribution protection.

• 

All of the protections or disconnectors of the system must be 

in the ‘Off’ position and, in particular, that of the batteries of 

the device 

(Q3)

 and its counterpart 

(Q8)

 in the accumulator 

cabinet, when it has an external battery bank.

Since the fuses of the disconnectors are supplied al-

ready installed to prevent them from being lost or mis-

laid, it is important to check that the disconnectors are open 

(Off).

Summary of Contents for DC POWER-L Series

Page 1: ...P DOWN LIGHT DIMMERS ILUEST POWER SOURCES STATIC INVERTERS PHOTOVOLTAIC INVERTERS LINE VOLTAGE STABILISERS MANUAL EE671774 1 DC POWER SUPPLY DEVICE THYRISTOR CONTROLLED CHARGER RECTIFIER 12 PULSE DC P...

Page 2: ...2 USER MANUAL...

Page 3: ...eception and unpacking 6 2 Packing list and contents 6 3 Storage 7 Installation 7 1 Look after your safety 7 2 Considerations to take into account 7 3 Earth connection terminal or strip 7 4 Connection...

Page 4: ...fied per sonnel Although no effort has been spared to ensure that the information in this user manual is complete and accurate we accept no liability for any errors or omissions that may exist The ima...

Page 5: ...e device is installed and operating it is recom mended to keep the documentation pendrive in a safe and easy to access location for future reference If a system differs from that shown in the figures...

Page 6: ...plies d c output Part 7 Safety requirements Reference standard IEC EN 60950 1 Information technology equipment Safety Part 1 General requirements IEC EN 61204 3 Low voltage power supply devices d c ou...

Page 7: ...o earth the protection will always be single pole so as not to disconnect the pole from earth The entry of connection cables is through the base of the cab inet Optionally and on request cable entry c...

Page 8: ...ker Q2 Battery circuit breaker Q3 Input terminals R S T Battery terminals Output terminals Cable input gland Earth Terminal Alarm interface X32 see Table 2 Interface Aux Contacts X34 refer to Table 3...

Page 9: ...ck format with a 623 x 803 mm base The dimensions of the rectifier and battery cabinets are the same and the only external difference is the control panel on the device The device can operate with PbC...

Page 10: ...ltage 110 Rated output voltage with positive to earth 110 Rated output voltage with negative to earth L Device series standard version only single phase devices with 5 ripple and no Schuko socket LP D...

Page 11: ...n the event of input mains failure or output overloads 5 2 2 AC input For greater versatility the system can be either single phase or three phase Regardless of the topology of the mains protection el...

Page 12: ...erride con trol the control is transferred to another current PID when one of the current limits is exceeded batteries or rectifier A selective control enables automatic switching between the two curr...

Page 13: ...event of input wave voltage and frequency variations The output current of each charger is equal to the current de manded by 100 of the loads plus the maximum charging cur rent of the battery accordi...

Page 14: ...tions Each automatic deactivation automatically recalculates the next periodic trip Table 5 Activation and deactivation of fast charging Exceptional charging Automatic Manual Periodic Activation No Vi...

Page 15: ...if re quested in the order cardboard box expanded polystyrene EPS corners polyethylene cover and polyester strapping All of these materials are recyclable so any disposal must be carried out in accord...

Page 16: ...6 3 Storage The device should be stored in a dry ventilated room and pro tected from rain dust and water or chemical splashes It is advisable to keep devices and batteries in their original pack agin...

Page 17: ...up operations The surface on which the system is to be installed must be properly prepared to support its weight and level to prevent the metal structure from having to withstand unnecessary and harmf...

Page 18: ...e accumulator bank with the resultant risk It should never be forgotten that the DC Power L with batteries is a generator of electrical power regardless of whether the batteries are installed in the s...

Page 19: ...phase or three phase AC power supply network All of the protections or disconnectors of the system must be in the Off position and in particular that of the the batteries of the device Q3 and its cou...

Page 20: ...bles red for positive and black for negative and the polarity indicated on the labelling of the device Connect the load or loads to the earth terminal or strip It is recommended to distribute the outp...

Page 21: ...tically or manually Exceptional charging Exceptional charging is forced manually at the will of the operator via the control panel 8 1 Startup procedure Set battery circuit breaker Q3 to On In systems...

Page 22: ...main screen of the system which appears when the device starts up It is also the screen that appears when is pressed to exit any of the other menus or sub menus of the control panel with LCD The first...

Page 23: ...Screen 2 1 This is the gateway to the device s switching menu Screen 2 2 Manual and forced activation of fast charging 9 3 4 User Parameters menu To access this menu from the home screen press the fo...

Page 24: ...MP C MIN T COMP C QUICK CHARGING MAX T min PERIODIC CHARGING INTERVAL Days BATT FLOAT CHARGE TIME h LOW BATTERY VOLTAGE x x x x V OUTPUT VOLTAGE LOW V INSULATION ALARM Kohm INSULATION MEASUREMENT S N...

Page 25: ...auxiliary contact closed Urgent 5 Current leakage alarm Isol res approx 5 K Isol res approx 5 K Not urgent 5 Electrolyte level low alarm Electrolyte low level Electrolyte normal level Not urgent 1 Ch...

Page 26: ...C input failure Phase rotation error RELE 2 EMERGENCY fault Output overvoltage Output undervoltage High battery voltage Low battery voltage Battery fuse blown Rectifier fuse blown Input switch open Ou...

Page 27: ...lower than the nominal setting of the device Screen 6 6 Use this screen to set the rectifier s overload alarm threshold Screen 6 7 Use this screen to activate or deactivate the rectifier output isola...

Page 28: ...itors The service life of the capacitors in the DC bus and those used for input and output filtering depends on use and environmental conditions Preventative replacement by authorised technical person...

Page 29: ...Batteries in system cabinet Fuses Batteries in external cabinet Fuses General output switch Disconnector Soft start Yes COMMUNICATION AND ALARMS Slot Yes one pre connected as standard SNMP Remote mai...

Page 30: ...y depending on their temperature they can function as insulators or conductors It is a one way device because it only transmits the current in a single direction It is generally used to control electr...

Page 31: ...31 SALICRU...

Page 32: ...R EGYPT PHILIPPINES NETHERLANDS INDONESIA IRELAND JORDAN KUWAIT MALAYSIA PERU POLAND CZECH REPUBLIC RUSSIA SWEDEN SWITZERLAND THAILAND TUNISIA UAE URUGUAY VENEZUELA VIETNAM REST OF THE WORLD Product r...

Reviews: