11.  Annexes.

11.1.  General technical specifications.

INPUT

AC voltage (V)

Single-phase 230 V AC

(3 wire: 1 phase + N + TT)

Three-phase 3x230 or 3x400 depending 

on model (4 wire: 3 TT)

Regulation range

± 15%. Outside this range, the 

corresponding alarm is activated.

With input voltage of -20%, the rectifier 

is blocked and the loads continue to be 

powered from the batteries while backup 

is available

Frequency (Hz)

50 / 60 ± 5% (47.5.. 52.5 / 57.. 63)

Power factor

0.9 (with rated input, 100% load and 

floating output voltage)

Performance 100% of load (%)

> 90

OUTPUT
Rated DC voltage (V)

24

48

110

120

125

220

Accuracy with batteries (%)

± 1

Floating voltage 

2.28 V/cell (PbCa) / 1.4.. 1.45 V/el. (NiCd)

Fast charging voltage

2.5 V/cell (PbCa) / 1.5 V/el. (NiCd)

Exceptional charging voltage

2.7 V/cell (PbCa) / 1.65 V/el. (NiCd)

Ripple voltage without batteries 

(%)

< 3

Ripple voltage with batteries 

(%)

< 1

Rectifier output current (A)

25 / 50 / 75 / 100 / 150 / 200

BATTERIES
Type

PbCa (sealed or open) or NiCd

No. PbCa cells

12

24

55

60

62

110

Number of elements (NiCd)

19 38..39 81..86 88..94 92..96 161.. 

173

Charge type

Constant I/U in accordance with DIN 

41773

Battery charging current

0.1.. 0.3 C adjustable

Recharge time

Up to 80% in 4 hours (0.2 C)

Protection

Against overvoltage and undervoltage

Fast charge

Automatic according to established 

conditions or forced manually via the 

control panel

Exceptional charging

Forced manually via the control panel 

and limited by conditions established for 

365 days 

Float voltage/ambient 

temperature compensation

Yes, customisable according to battery 

specifications (mV / °C)

PROTECTION AND OPERATION ELEMENTS
Rectifier input

Circuit breaker

Auxiliary input for TSS

Circuit breaker

Batteries (in system cabinet)

Fuses

Batteries (in external cabinet)

Fuses

General output switch

Disconnector

Soft start

Yes

COMMUNICATION AND ALARMS
Slot

Yes, one pre-connected as standard

SNMP / Remote maintenance

NIMBUS, optional

DB9 connector (COM1)

Optional

DB9 connector (COM3)

Optional

Relay interface (RELAYS), 

potential-free contacts

3 relays, expandable to 6. Optional.

Compensation of battery 

voltage according to 

temperature

By means of a sensor installed in the 

battery bank

Low electrolyte level (for open 

type batteries)

Optional. By means of a sensor installed 

in one of the batteries

GENERAL
Dielectric strength

2500 V AC for 1 minute

Protection rating

IP20

Ventilation

Natural convection

Rectifier operating 

temperature

-10ºC to +55ºC 

(11)

Rectifier storage temperature

-20ºC to +70ºC 

(12)

Relative humidity

Up to 95% non-condensing

Maximum operating altitude

Up to 3,000 masl 

(13)

Acoustic noise at 1 metre

< 49 dBA (average)

< 57 dBA (max. value)

Colour

Cabinet structure and covers painted in 

RAL-7035

Structure, supports and 

accessories

Pre-formed and galvanised sheet steel

Battery trays

Galvanised sheet steel

Weights (kg)

Depending on configuration, see Table 6

Dimensions (mm)

Depending on configuration, see Table 6

LCD

Screen map menus (Fig. 15)

- Main

- Measurements

- Switching

-  User Parameters

- Alarms

-  Battery Settings

-  Password (necessary to display 

‘Battery Settings’ menu)

LUMINESCENT INDICATIONS

LED optical on the control 

panel with LCD

a) Correct output indication

b) Input fault indication

c)  Urgent alarm indication

d) Non-urgent alarm indication

STANDARDS
Safety

IEC/EN 61204-7, IEC/EN 60950-1

Electromagnetic compatibility 

(EMC)

IEC/EN 61204-3

Marking

EC

Quality and environmental 

management

ISO 9001 and ISO 14001

Certification company

SGS

(11)

 

Power degradation from +40ºC.

(12)

 

No batteries. 

(13)

 

Power degradation from 1000 masl

.

Table 9. 

General specifications.

Summary of Contents for DC POWER-L Series

Page 1: ...P DOWN LIGHT DIMMERS ILUEST POWER SOURCES STATIC INVERTERS PHOTOVOLTAIC INVERTERS LINE VOLTAGE STABILISERS MANUAL EE671774 1 DC POWER SUPPLY DEVICE THYRISTOR CONTROLLED CHARGER RECTIFIER 12 PULSE DC P...

Page 2: ...2 USER MANUAL...

Page 3: ...eception and unpacking 6 2 Packing list and contents 6 3 Storage 7 Installation 7 1 Look after your safety 7 2 Considerations to take into account 7 3 Earth connection terminal or strip 7 4 Connection...

Page 4: ...fied per sonnel Although no effort has been spared to ensure that the information in this user manual is complete and accurate we accept no liability for any errors or omissions that may exist The ima...

Page 5: ...e device is installed and operating it is recom mended to keep the documentation pendrive in a safe and easy to access location for future reference If a system differs from that shown in the figures...

Page 6: ...plies d c output Part 7 Safety requirements Reference standard IEC EN 60950 1 Information technology equipment Safety Part 1 General requirements IEC EN 61204 3 Low voltage power supply devices d c ou...

Page 7: ...o earth the protection will always be single pole so as not to disconnect the pole from earth The entry of connection cables is through the base of the cab inet Optionally and on request cable entry c...

Page 8: ...ker Q2 Battery circuit breaker Q3 Input terminals R S T Battery terminals Output terminals Cable input gland Earth Terminal Alarm interface X32 see Table 2 Interface Aux Contacts X34 refer to Table 3...

Page 9: ...ck format with a 623 x 803 mm base The dimensions of the rectifier and battery cabinets are the same and the only external difference is the control panel on the device The device can operate with PbC...

Page 10: ...ltage 110 Rated output voltage with positive to earth 110 Rated output voltage with negative to earth L Device series standard version only single phase devices with 5 ripple and no Schuko socket LP D...

Page 11: ...n the event of input mains failure or output overloads 5 2 2 AC input For greater versatility the system can be either single phase or three phase Regardless of the topology of the mains protection el...

Page 12: ...erride con trol the control is transferred to another current PID when one of the current limits is exceeded batteries or rectifier A selective control enables automatic switching between the two curr...

Page 13: ...event of input wave voltage and frequency variations The output current of each charger is equal to the current de manded by 100 of the loads plus the maximum charging cur rent of the battery accordi...

Page 14: ...tions Each automatic deactivation automatically recalculates the next periodic trip Table 5 Activation and deactivation of fast charging Exceptional charging Automatic Manual Periodic Activation No Vi...

Page 15: ...if re quested in the order cardboard box expanded polystyrene EPS corners polyethylene cover and polyester strapping All of these materials are recyclable so any disposal must be carried out in accord...

Page 16: ...6 3 Storage The device should be stored in a dry ventilated room and pro tected from rain dust and water or chemical splashes It is advisable to keep devices and batteries in their original pack agin...

Page 17: ...up operations The surface on which the system is to be installed must be properly prepared to support its weight and level to prevent the metal structure from having to withstand unnecessary and harmf...

Page 18: ...e accumulator bank with the resultant risk It should never be forgotten that the DC Power L with batteries is a generator of electrical power regardless of whether the batteries are installed in the s...

Page 19: ...phase or three phase AC power supply network All of the protections or disconnectors of the system must be in the Off position and in particular that of the the batteries of the device Q3 and its cou...

Page 20: ...bles red for positive and black for negative and the polarity indicated on the labelling of the device Connect the load or loads to the earth terminal or strip It is recommended to distribute the outp...

Page 21: ...tically or manually Exceptional charging Exceptional charging is forced manually at the will of the operator via the control panel 8 1 Startup procedure Set battery circuit breaker Q3 to On In systems...

Page 22: ...main screen of the system which appears when the device starts up It is also the screen that appears when is pressed to exit any of the other menus or sub menus of the control panel with LCD The first...

Page 23: ...Screen 2 1 This is the gateway to the device s switching menu Screen 2 2 Manual and forced activation of fast charging 9 3 4 User Parameters menu To access this menu from the home screen press the fo...

Page 24: ...MP C MIN T COMP C QUICK CHARGING MAX T min PERIODIC CHARGING INTERVAL Days BATT FLOAT CHARGE TIME h LOW BATTERY VOLTAGE x x x x V OUTPUT VOLTAGE LOW V INSULATION ALARM Kohm INSULATION MEASUREMENT S N...

Page 25: ...auxiliary contact closed Urgent 5 Current leakage alarm Isol res approx 5 K Isol res approx 5 K Not urgent 5 Electrolyte level low alarm Electrolyte low level Electrolyte normal level Not urgent 1 Ch...

Page 26: ...C input failure Phase rotation error RELE 2 EMERGENCY fault Output overvoltage Output undervoltage High battery voltage Low battery voltage Battery fuse blown Rectifier fuse blown Input switch open Ou...

Page 27: ...lower than the nominal setting of the device Screen 6 6 Use this screen to set the rectifier s overload alarm threshold Screen 6 7 Use this screen to activate or deactivate the rectifier output isola...

Page 28: ...itors The service life of the capacitors in the DC bus and those used for input and output filtering depends on use and environmental conditions Preventative replacement by authorised technical person...

Page 29: ...Batteries in system cabinet Fuses Batteries in external cabinet Fuses General output switch Disconnector Soft start Yes COMMUNICATION AND ALARMS Slot Yes one pre connected as standard SNMP Remote mai...

Page 30: ...y depending on their temperature they can function as insulators or conductors It is a one way device because it only transmits the current in a single direction It is generally used to control electr...

Page 31: ...31 SALICRU...

Page 32: ...R EGYPT PHILIPPINES NETHERLANDS INDONESIA IRELAND JORDAN KUWAIT MALAYSIA PERU POLAND CZECH REPUBLIC RUSSIA SWEDEN SWITZERLAND THAILAND TUNISIA UAE URUGUAY VENEZUELA VIETNAM REST OF THE WORLD Product r...

Reviews: