37
EN
8. TROUBLESHOOTING GUIDE.
8.1. MAINTENANCE.
Danger
Risk of causing damage to the battery or personal injury due to
improper use.
Before using the inverter, observe the following procedure:
- Lower the AC thermal-magnetic circuit breaker and the inverter
DC switch.
- Wait at least 5 minutes for the internal capacitors to be fully
discharged.
- Check that there is no voltage or current before removing
a connector.
Warning
Keep all unqualified staff far from these areas!
A temporary warning sign or barrier should be posted to keep
unqualified persons away while performing electrical connection
and service work.
Attention
Only restart the battery after eliminating the safety-related fault.
Never replace internal components at random.
Please contact SALICRU for support regarding the maintenance
tasks. Otherwise, SALICRU shall not be held liable for any
damage caused.
Note
Perform the maintenance tasks on the unit as described in
the manual and always using the corresponding tools, test
equipment, or the latest version of the manual.
Tab. 6. Basic warnings for maintenance.
8.1.1. Maintenance of electrical components.
Items
Test
Test point Methods
Repair
condition
Solution
1
Electric
Make sure
that the
output
voltage is
normal.
Multimeter.
The battery
voltage is
exceeding the
preset range.
Contact the
distributor or
manufacturer.
2
Verification
failure.
Make sure
that the light
is normal.
Visual
inspection.
Warning
3
Cable
Insulation,
terminal
Insulation
defect, ageing,
terminal
stripped or
corroded.
Replace the
cable, replace
the terminal
board.
Tab. 7. Points to check.
8.1.2. Battery maintenance.
Item Frequency
Test
Solution
1
Every month
Work
environment.
Keep the battery away from heat sources
and direct sunlight.
Visual
inspection.
If there is any damage, leakage or
deformation, remove the defective battery
pack, take photos and replace it.
Item Frequency
Test
Solution
2
Every three
months
Visual
inspection.
Carefully clean the battery with a cotton
cloth.
Condition
of the
connections.
Check the tightness of each terminal and
the temperature of the cable.
3
Every six
months
Measure and
record the
voltage.
Collect discharge data at least once every
six months during the first year.
During the second year, discharge data must
be recorded every three months. Check the
historical logs via the RS232 port. If the
alarm information shows that the battery
is frequently being overcharged, this may
indicate that the battery has reached the
point of protection against charging and
discharging, which may result in insufficient
time for power preparation. We recommend
replacing the battery immediately.
Tab. 8. Points to check and frequency.
8.2. TROUBLESHOOTING.
If a battery failure occurs, record the information about the failure,
shut down the battery as per the shutdown procedure and contact
the distributor or SALICRU. Do not try to fix the problem yourself.
EQX2
SOLAR INVERTERS CONNECTED TO THE GRID
USER MANUAL
Summary of Contents for EQUINOX BATT EQX2 BATT
Page 1: ...EQX2 BATT ES EN MANUAL DE USUARIO BATER AS MODULARES PARA INVERSORES SOLARES...
Page 2: ...2 SALICRU...
Page 19: ...19 ES EQX2 INVERSORES SOLARES DE CONEXI N A RED MANUAL DE USUARIO...
Page 21: ...EQX2BATT EN USER MANUAL MODULAR BATTERIES FOR SOLAR INVERTERS...
Page 22: ...22 SALICRU...
Page 39: ...39 EN EQX2 SOLAR INVERTERS CONNECTED TO THE GRID USER MANUAL...