background image

5

SALICRU

• 

If 

the instructions are not in total or partial and in 

special referred to the safety, do not carry on with 

the installation or commissioning tasks

, because there 

could be a 

risk on your safety or on the other/s persons,

 

being able to make 

serious injuries even the death

, also it 

can 

cause damages to the equipment and/or to the loads 

and installation

.

• 

The local electrical regulations and the different re-

strictions of the client's site, they can invalidate some 

recommendations included in the manuals. When discrepan-

cies exist, the user has to comply the local regulations.

• 

The equipments provided with power cord with plug 

and outlets, can be connected and used by personnel 

without any kind of experience.

• 

A person is defined as 

qualified

, if it has experience of as-

sembling, commissioning and perfect control operating of 

the equipment, if he has the requirements to do the job and 

if has read and understand all the things described in this 

manual, in particular the safety indications. Such preparation 

is considered only valid if it is certified by our 

S.T.S.

.

• 

Place the equipment the closest to the power supply and 

loads to be supplied, leaving an easy access if it were needed 

an urgent disconnection.

• 

Warning labels should be placed on all primary power 

switches installed in places away from the equipment to alert 

the electrical maintenance personnel of the presence of a 

UPS in the circuit 
The label will bear the following text or an equivalent one:

Before working in this circuit.

• 

Isolate the Uninterruptible Power System (UPS).

• 

Check the voltage between all terminals including the 

protective earth.

Risk of voltage feedback from UPS.

1.2.3.1.  General safety warnings.

• 

All connections and disconnections of the cables from the 

equipment, including the control ones, will be done with no 

power supply and the switches on rest, position «O» or «Off».

• 

Shutdown the equipment completely by switching «Off» the 

button of the control panel first. Next disconnect the cable or 

by switching «Off» the input circuit breaker of the installation.

 The indiscriminate manoeuvring of the switches may 

involve production losses and/or equipment dam-

ages. Consult the documentation before doing any action 

• 

Pay special attention to the labelling of the equipment 

that warns about the «Electrical shock hazard». Inside 

the equipment there are dangerous voltages, never open the 

enclosure, the access has to be done by qualified staff. In 

case of maintenance or fault, consult to the closest (

S.T.S.

).

• 

Cross cable sections used to supply the equipment and loads, 

will be according to the nominal current stated in the nameplate 

label of the equipment, and respecting the Low Voltage Electro-

technical Regulations or standards of the country.
Use approved cables only

• 

Protection Earth cable of the UPS drives the leakage 

current of the load devices. An isolated earth cable has 

to be installed as part of the circuit that supplies the equip-

ment. Cross cable section and its features will be same as 

the power supply cables, but with green colour with or without 

the yellow strip.
All outlets of the UPS has an earth bonding, duly connected 

and those equipments with power blocks there is an exclusive 

terminal for the load earth connection. When an outgoing dis-

tribution is done, i.e power strips, it is essential that they have 

an earth terminal connected to each one of them.
It is essential that the cables that supplies the loads have the 

earth connection cable. 

The protection earth must be connected to the frame 

or metallic chassis of any electrical equipment (in our 

case to the UPS, battery cabinet or case and loads), assuring 

that it is done before connecting the input voltage.
Check the quality and availability of the earth, it has to be 

between the defined parameters by the local or national 

regulations.

• 

For the smallest devices (the ones connected with the fore-

seen power cord with plug), the user has to check the wall 

outlet corresponds with the type of supplied plug, with earth 

duly installed and connected to the local protection earth.

• 

During the normal UPS operation, the power cord 

cable can't be disconnected from wall outlet, because 

the protection earth of the own UPS would be disconnected 

and also the earth from the loads connected to the output.
For this reason, the general protection earth cable of the 

building or switchgear panel that supplies the UPS will not 

be disconnected.

• 

Check that the sum of the leakage currents of the UPS and 

connected load/s do not exceed over 3,5mA.

• 

The installation will have input protections sized to the cur-

rents of the equipment and stated in the nameplate label 

(RCD devices type B and circuit breakers with C character-

istic or any other equivalent one).
Overload conditions are considered as a nonpermanent an 

exceptional operating mode, so these currents will not be 

kept in mind when sizing the protections.

• 

Do not overload the UPS by connecting loads with inrush 
consumptions at its output, like laser printers.

• 

Output protection will be done with a circuit breaker of C char-

acteristic or an equivalent one.
It is recommended to distribute the output power, into four 

lines as minimum. Each one of them will have a protection 

circuit breaker sized to the quarter of the nominal power. 

This kind of outgoing distributions will allow that any fault in 

any device connected to the equipment, that makes a short-

circuit, will affect to the line with the faulty device only. An 

uninterruptible power supply will be guaranteed to the rest of 

connected loads, due to the protection tripping of the affected 

line by the short-circuit only.

• 

When replacing a fuse, do it for another of the same type, char-

acteristics format and size.

• 

Under any concept the input power cord will be connected to the 

output of the equipment, either directly or through other ways.

• 

All the equipments have an auxiliary terminal strip to install 

an external emergency power off button (EPO), and it will be-

long to the user property.
Type of circuit is selectable through the LCD panel of the equip-

ment. The contact is preset from factory as normally open, so 

the button must be switched to close the circuit and the voltage 

to the loads is broken. To establish the power supply to the 

loads again, the EPO button must be deactivated.
EPO doesn't affect to the power supply of the equipment, it 

only breaks the power supply to the loads as a safety measure.

• 

When supplying input voltage to a UPS with fitted in or 

separate static bypass, although the inverter is still 

turned «Off» (deactivated) it doesn't mean that at the output 

there will not be voltage.

Summary of Contents for PS.2000.ADV RT (B1)

Page 1: ...PLY UPS LIGHTING FLOW DIMMER STABILIZERS ILUEST SWITCH MODE POWER SUPPLY STATIC INVERTERS PHOTOVOLTAIC INVERTERS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS SPS ADVANCE RT series UNINTERRUPTIBLE P...

Page 2: ......

Page 3: ...IEC outlets 4 3 3 Connection of the external batteries extended back up time 4 3 4 Connection of main input earth terminal and the earth bonding terminal 4 3 5 EPO terminals in UPSs 1kVA Emergency Pow...

Page 4: ...s for safety of the things To not respect such instructions can damage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic in structions an...

Page 5: ...ive terminal for the load earth connection When an outgoing dis tribution is done i e power strips it is essential that they have an earth terminal connected to each one of them It is essential that t...

Page 6: ...ven pack aged the equipment will be left for a minimum time of two hours in the new location before making any action with the purpose of adapting it to the new environmental conditions and avoid the...

Page 7: ...battery cabinet to the equipment respect the cable s polarity and colour red positive black negative indicated in the manual and in the cor responding labelling Wear rubber gloves and shoes Use tools...

Page 8: ...tive EMC In accordance with the specifications of the harmonized stand ards Standards as reference EN IEC 62040 1 Uninterruptible power supply UPS Part 1 1 General and safety requirements for UPS s us...

Page 9: ...ment can be checked Act in accordance with the installation Front virew ADVANCE RT Fixing screws Plastic beauty front Fixing screws Plastic beauty front Control panel with LCD Plastic beauty front Fro...

Page 10: ...AC power supply Earth connection for battery module Output connector with M dem ADSL Fax protection Connector for external EPO Smart slot protection cover Fan IEC outlets LS2 Input connector for modem...

Page 11: ...of strings in parallel Omitted for one 0 Battery module without them but the needed accessories to install them ADV RT Series of the battery module MOD BAT Battery module i Note relative to the batter...

Page 12: ...from the batteries through the inverter for a determined time depending on the model battery charge level and the own load connected at the output For models higher than 1000 VA it is possible to inc...

Page 13: ...olling and management at the manager system dis posal This facility is got through the SNMP adaptor which is well known by the main software and hardware manufacturers The available SNMP option for SP...

Page 14: ...c isolation transformer as standard as an option or either in stalled by yourself either at the UPS input or output or at all of them protections against indirect contact has to be fitted in residual...

Page 15: ...als therefore they should be disposed according to current regulations We recom mend to keep the packaging in case its use is necessary in the future Proceed as follows Cut the strips of cardboard enc...

Page 16: ...wise B and insert it again into the beautiful front cover till click it C Check the correct closing of the fixing nails Put the beautiful front cover back in the reverse way as its removing see sectio...

Page 17: ...ing with ex tended back up time battery module In the side of each front cover there are the K trims as a notch to go the cables through it with the battery modules Break the needed trims to pass the...

Page 18: ...igure 9 For higher quantity of modules reproduce the connection procedure among them All models can be installed in a 19 rack cabinet attending the height of each one of them is 2 units Proceed as fol...

Page 19: ...utlets As this is a device with class I protection against elec tric shocks it is essential to install a protective earth conductor connect earth Connect the conductor to the terminal before connectin...

Page 20: ...rmally closed NC Less punctual cases it is not recommended to use this type of connection due to the function of the EPO button because it would not work in case of any of the two cables that goes fro...

Page 21: ...the equipment labelled as Input Connect the own modem ADSL Fax to RJ45 connector of the equipment labelled as Output 4 3 7 Software Free software download WinPower WinPower is a UPS monitoring softwa...

Page 22: ...part from sensi tive ones are required to be connected like laser printers or CRT monitors keep in mind the start inrush currents of these peripherals in order to avoid that the equipment becomes bloc...

Page 23: ...from the nominal and takes as a default value the wrong one Check the frequency in the control panel and repeat the procedure if this circumstance would occur 5 2 2 UPS start up with mains present For...

Page 24: ...on stabilizer mode Blue BATT Warning UPS working on battery mode Blue BTOP Warning Battery disconnected Red TEST Warning UPS working on battery in life function test Blue OPVH Fault Battery mode with...

Page 25: ...the possible se lectable variables or values Code Description Values OPV Output voltage selection 220 220V 230 230V 240 240V AV Input voltage type 000 Normal range 001 Wide range 002 Gen set EBM Exte...

Page 26: ...ments stated in table 10 and go forward or backward till reaching EBM 3 Validate the configuration element When the LCD panel displays EBM press the key for more than one second to enter into the elem...

Page 27: ...the battery and earth termi nals Even with the input circuit breaker switch from protection panel is turned off the internal parts of the UPS are still con nected to the batteries so there are hazardo...

Page 28: ...company is not forced by the warranty if it appreciates that the defect in the product doesn t exist or it was caused by a wrong use negligence installation and or inadequate testing tentative of repa...

Page 29: ...reventive and corrective maintenance contracts is pos sible to determine the intervention timetable and response times as well as exclusion or inclusion parts in partial or total way with the purpose...

Page 30: ...r kVA 0 750 1 1 5 2 3 Power kVW 0 675 0 900 1 350 1 8 2 7 Wave shape Pure sinewave Nominal voltage 220 230 240 V AC selectable Voltage accuracy battery mode 5 Voltage THD linear load 10 3 Voltage THD...

Page 31: ...l loads always flow in the same direction from the highest potential point to the lowest one Although usually the direct current is identified with the constant cur rent for example the one supplied b...

Page 32: ...agni tude and frequency by the user or the designer Rectifier In electronic a rectifier is the element or circuit that allows to convert the alternating current into direct cur rent This is done by re...

Page 33: ...33 SALICRU...

Page 34: ...34 USER MANUAL...

Page 35: ...35 SALICRU...

Page 36: ...NCIA VALLADOLID ZARAGOZA BRANCHES AND SERVICES AND TECHNICAL SUPPORT S T S CHINA FRANCIA HUNGR A MARRUECOS M XICO PORTUGAL REINO UNIDO SINGAPUR SUBSIDIARIES ALEMANIA ARABIA SAUD ARGELIA ARGENTINA B LG...

Reviews: