24
SALICRU
factors influence the reverse chemical process that occurs
in the discharge in the event of an energy demand and that
they have a significant effect on shortening the useful life
of the same.
The nominal operating temperature of a battery is 20°C.
Operating above this temperature will reduce its duration
or life and operating below it will reduce its storage ca-
pacity. If the average operating temperature of the battery
increases from 20°C to 30°C, the service life will be re-
duced by 50%. If the operating temperature exceeds 40°C,
the service life will be reduced exponentially.
In a normal installation, the battery temperature is main-
tained between 15 and 25°C. Keep batteries away from
heat sources or air intakes.
•
The protections (fuses or circuit breakers) should be fitted
as close as possible to the accumulators, and their con-
necting cables, between them and the UPS, should be as
short as possible.
5.2. CABINET POSITIONING.
5.2.1. 180 to 300 kVA devices.
The cabinet has two positioning systems, one by means of the
base with four wheels, which is suitable for adjusting the posi-
tion of the cabinet, and the other by means of anchor bolts for
its final permanent installation.
55 86.5
349
55
86.5
10
971
10
55
522
55
47
105
687
①
②
③
Front door
Back door
Front door
Rear door
Anchor bolt.
L-shaped plates.
Wheels.
Fig. 28.
Support structure for 180 kVA and 300 kVA
devices (bottom view).
5.2.2. 500kVA devices.
The UPS cabinet can be supported on six wheels and on anchor
bolts at the base. The wheels are used for temporary adjust-
ment of position, the anchor bolts are used to keep the cabinet
in its final position. The support structure and its dimensions
(expressed in mm) are shown in Fig. 29.
1230
570
570
32
48
696
195
100
Fig. 29.
Support structure for 500 kVA devices (bottom view).
The steps to position the cabinet are as follows:
1.
Make sure that the support structure is in good condition
and that the surface where the unit will be installed is flat
and strong.
2.
Loosen the anchor bolts with a spanner, turning them anti-
clockwise. The unit is only supported on the wheels.
3.
Place the device in its final position.
Be sure to leave a space of at least 0.8m at the front
of the cabinet to be able to fully open the power
module door and at least 0.5 m at the back for good
ventilation and cooling. The space that must be reserved for
the cabinet is shown in Fig. 30.
≥ 500
≥ 500
≥ 800
Fig. 30.
Space reserved for the cabinet (units: mm).