6.6.1. Location of parallel cards.
The parallel interfaces of the 180 and 300 kVA devices are
located at the rear of the cabinet, as shown in Fig. 57.
Parallel interface card
Zoom area A
Fig. 57.
Location of the parallel card in 180 and 300 kVA
devices.
In 500 kVA devices, they are inside the cabinet at the front, as
shown in Fig. 58.
UPS input
Q1
Q2
Q4
Bypass input
Manual bypass
Cold Start
Parallel interface
cover
Fig. 58.
Location of the parallel card in 500 kVA devices.
6.6.2. Jumper settings for parallel operation.
The settings of the jumpers of the parallel cards will be dif-
ferent depending on whether it is a 2 UPS or 3 UPS system.
6.6.2.1. Case of 2 UPSs in parallel.
jumpers in short circuit
J13, J14, J15 and J16
J4
J6
J8
J10
J12
J3
J5
J7
J9
J11
jumpers in open circuit
Fig. 59.
Jumper setting for the case of two UPSs in
parallel.
Jumpers J3, J5, J7, J9, J11 and J4 in short circuit.
Jumpers J6, J8, J10, J12, J13, J14, J15 and J16 in open
circuit.
6.6.2.2. Case of 3 UPSs in parallel.
J4
J3
Fig. 60.
Jumper setting for the case of three UPSs in
parallel.
Only jumpers J3 and J4 are in short circuit. The rest are
in open circuit.