45
Inverter
indicator
Fixed green
Load supplied by inverter
Blinking
green
Inverter on, start, synchronisation or standby
(ECO mode) for one or more modules
Fixed red
System output not supplied by the inverter,
inverter failure for one or more modules
Blinking red
System output supplied by the inverter,
inverter failure for one or more modules
Off
Inverter not operational for all modules
Load
indicator
Fixed green
UPS output on and normal
Fixed red
UPS overload time exceeded, short circuit in
output or output without power supply
Blinking red
UPS output with overload
Off
No UPS output
Status
indicator
Fixed green
Normal operation
Fixed red
Failure
Tab. 22.
Description of indicator status.
There are two types of audible alarm during UPS operation.
Alarm
Description
Two short alarms
and one long
General system alarm
(for example: AC failure)
Continuous alarm
Serious system failure
(for example: blown fuse or hardware failure)
Tab. 23.
Description of the audible alarms.
7.2.2. Control and operation buttons.
There are four control and operation buttons (2, 10, 11 and 12
in Fig. 69) and they are used next to the LCD touch screen. The
following table describes the functions of each of them.
Button
Description
EPO
Long press, cuts load power (disconnects the rectifier, inverter,
static bypass and battery)
BYP
Long press, transfer to bypass (press the ‘up’ button on the back
of the door to activate it)
INV
Long press, transfer to inverter
MUTE
Long press to activate or deactivate the audible alarm
Tab. 24.
Functions of the control and operation buttons.
When the frequency of the Bypass is out of sync, it will
take a short time (less than 10 ms) to transfer from
Bypass to Inverter.
7.2.3. LCD touch screen.
Users can search for information, control the UPS and adjust
the parameters using the LCD touch screen in a simple way.
After the control system starts the auto-test, the system enters
the start page and then the welcome window.
Status bar
Information display
Warning
information
Main menu
Fig. 70.
Start page.
The start page consists of four parts: status bar, information
display, warning information and main menu.
•
Status bar
The status bar contains information about the product
model, its capacity, operating mode, number of power mod-
ules and system time.
•
Information display
Users can check the cabinet information in this area.
Bypass, mains input, battery and output voltages are dis-
played in the form of analogue meters.
Loads are shown as a bar chart with percentages. The
green area represents a load less than 60%; the yellow
one, a load of 60-100%; and the red one, a load greater
than 100%.
The energy flow mimics the power flow.
•
Warning information
Display of the cabinet’s warning information.
•
Main menu
The main menu includes: Cabinet, Module, Settings, Log,
Operation and Charts. Users can control and operate the
UPS to search for all parameters measured through the
main menu.
SLC ADAPT
UNINTERRUPTIBLE POWER SUPPLY (UPS)
USER'S MANUAL
Summary of Contents for SLC ADAPT Series
Page 1: ...SLC serie ADAPT 180 300 y 500 kVA UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...
Page 12: ...12 SALICRU Fig 8 Front view of 10 slot cabinet 500 kVA 300 kVA at 3x208 V with closed doors...
Page 64: ...64 SALICRU...
Page 65: ...65 SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...