57
89
Inverter IGBT driver lock
Inverter IGBTs are turned off. Check:
1. If power modules are installed correctly in cabinet.
2. If fuses between rectifier and inverter are damaged.
90
Battery dead
Battery service life expired. Replacement of batteries for new ones recommended. New ones must be activated with
software.
91
Bypass CAN bus failure
CAN bus between bypass module and cabinet abnormal.
92
Dust filter expired
Clean or replace dust filter.
102
Wave activation
Waveform saved during UPS failure.
103
Bypass CAN bus failure
Bypass and cabinet communicate with each other through CAN bus. Check:
1. State of connector and signal cable.
2. If control card is abnormal.
105
Firmware error
For manufacturer’s use only.
106
System setting error
For manufacturer’s use only.
107
Bypass overtemperature
Bypass module overtemperature. Check:
1. If there is bypass overload.
2. If ambient temperature exceeds 40°C.
3. If bypass SCRs are correctly installed.
4. If bypass fans are normal.
108
Duplicate module ID
There are at least two modules set with the same ID card as the power connector. Set the ID in the correct sequence.
Tab. 29.
UPS event list.
The text colours indicate the event levels:
Green: there is an event;
Grey: there is an event and it has been deleted;
Yellow: there is a warning;
Red: there is a failure.
7.3.5. Operate menu.
Press icon
at the bottom of the screen to access the
Operate menu.
Fig. 88.
Operation menu.
The FUNCTION BUTTONS and TEST COMMANDS can be
accessed from the Operate menu. The available options are
described below:
FUNCTION BUTTONS
•
Mute/Reset audible alarm
Press
or
to mute or reset audible alarm.
•
Clear failures
Press
to clear failures.
•
Transfer to Bypass mode and exit Bypass mode
Press
or
to transfer to Bypass mode or
cancel this command, respectively.
•
Transfer to inverter
Press
to switch from Bypass mode to Inverter mode.
•
Activate power module ‘OFF’ button
Press
to activate power module off switch.
•
Reset battery history
Press
to restore battery history data. Battery
history data includes discharge times, days in operation
and discharge hours.
•
Reset dust filter usage time
Press
to clear dust filter usage time. Includes usage
days and maintenance period.
TEST COMMANDS
•
Battery test
Press
, the system transfers to Battery mode to
check its condition. Make sure that the bypass is operating
normally and the battery has more than 25% of load.
•
Battery maintenance
Press
, the system transfers to Battery mode. This
function is used for battery maintenance. Make sure that
the bypass is operating normally and the battery has more
than 25% of load.
SLC ADAPT
UNINTERRUPTIBLE POWER SUPPLY (UPS)
USER'S MANUAL
Summary of Contents for SLC ADAPT Series
Page 1: ...SLC serie ADAPT 180 300 y 500 kVA UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...
Page 12: ...12 SALICRU Fig 8 Front view of 10 slot cabinet 500 kVA 300 kVA at 3x208 V with closed doors...
Page 64: ...64 SALICRU...
Page 65: ...65 SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...