61
9. ANNEXES.
9.1. GENERAL TECHNICAL SPECIFICATIONS.
MODEL
SLC ADAPT
TECHNOLOGY
On-line double conversion, three-level PWM, DSP control
INPUT
3 x 380 / 400 / 415 V AC
3 x 208 / 220 V AC
MODULES AVAILABLE (kVA / kW)
30 / 27
50 / 45
20 / 18
30 / 27
Rated AC voltage
3 x 380 / 400 / 415 V (3P + N)
3 x 208 / 220 V (3P + N)
Voltage range
- 43% + 20%
(1)
Frequency
50 / 60 Hz
Frequency range
40 - 70 Hz
Total harmonic distortion (THDi)
≤ 3%
Power factor
> 0.99
OUTPUT
Rated voltage
3 x 380 / 400 / 415 V (3P + N)
3 x 208 / 220 V (3P + N)
Accuracy
± 1% (static mode) / ± 1.5% (dynamic mode)
Frequency
50 / 60 Hz
Total harmonic distortion (THDv)
≤ 1%
Power factor
0.9
Crest factor
3:1
Total efficiency in On-line mode
> 95%
> 96%
> 95%
> 96%
Total efficiency in Battery mode
> 95%
> 96%
> 95%
> 96%
Total efficiency in Eco mode
99%
Permissible overload
125% for 10 min / 150% for 1 min
STATIC BYPASS
Type
Static thyristor
Voltage
3 x 380 / 400 / 415 V (3P + N)
3 x 208 / 220 V (3P + N)
MANUAL BYPASS
Type
Uninterrupted
BATTERIES
Type
Lead-acid, lithium iron phosphate. Maintenance-free SLA, NiCd
Number
2 x 16 ... 2 x 22
2 x 11
MODEL
SLC ADAPT
TECHNOLOGY
On-line double conversion, three-level PWM, DSP control
INPUT
3 x 380 / 400 / 415 V AC
3 x 208 / 220 V AC
MODULES AVAILABLE (kVA / kW)
30 / 27
50 / 45
20 / 18
30 / 27
Charging voltage regulation
Batt-watch
Charger maximum power
20% of total system power
COMMUNICATION
Display
10.4”
Ports
RS-232, RS-485, relays and USB
Free slots
1 x SNMP / 1 x extended relays
GENERAL
Operating temperature
0°C ÷ + 40°C
Relative humidity
Up to 95%, non-condensing
Operating altitude
2,400 masl
(2)
Acoustic noise at 1 metre
< 65 dB (A)
< 72 dB (A)
< 65 dB (A)
< 72 dB (A)
Dimensions (D x W x H) (mm)
790 x 460 x 134 (3 u)
700 x 510 x 178 (4 u)
790 x 460 x 134 (3 u)
700 x 510 x 178 (4 u)
Weight (kg)
34
45
34
45
SYSTEMS
Maximum no. modules per system
6 or 10
10
6 or 10
10
Maximum power per system (kVA)
300
500
200
300
Maximum no. systems in parallel
3
STANDARDS
Safety.
EN 60950-1; EN IEC 62040-1
Electromagnetic compatibility (EMC).
EN IEC 62040-2
Operation
VFI-SS-111 as per EN-IEC 62040-3
Quality and Environmental Management
ISO 9001 and ISO 14001
(1)
Depending on charge percentage
(2)
Power degradation for higher altitudes up to a maximum of 5,000 masl.
SLC ADAPT
UNINTERRUPTIBLE POWER SUPPLY (UPS)
USER'S MANUAL
Summary of Contents for SLC ADAPT Series
Page 1: ...SLC serie ADAPT 180 300 y 500 kVA UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...
Page 12: ...12 SALICRU Fig 8 Front view of 10 slot cabinet 500 kVA 300 kVA at 3x208 V with closed doors...
Page 64: ...64 SALICRU...
Page 65: ...65 SLC ADAPT UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...