35
Pin
Reference
Function
J6.1
BCB_DRV
It provides a pulse signal of +24 V / 20 mA for
the remote control of the battery circuit breaker
through its shunt trip. This signal turns the
switch «Off».
J6.2
BCB_CONT
Status of the BCB switch. Its normally closed
auxiliary contact -NC- can be connected
between this pin and the GND.
J7.1
GND
+ 24V ground reference
J7.2
BCB_ONL
Not useful. Not implemented.
Tabla 6.
Pinout terminal block for connection to external
BCB.
5.5.7.6. Dry contacts.
Switched contacts of three relays, corresponding to three sig-
nals of the dry contacts, are supplied through terminal blocks
J8, J9 and J10. Tab. 7 shows the pinout of all of them. The
voltage and maximum current applicable to these contacts is
250 V AC 3A.
J8
J9
J10
***_NC
***_NO
GND
Fig. 39.
Terminal block J8, J9, and J10 dry contacts.
Pin
Reference
Function
J8-1
BYP_ALM_NC
Normally closed contact -NC-, dry contacts
signal STATIC BYPASS.
J8-2
BYP_ALM_NO
Normally open contact -NO-, dry contacts signal
STATIC BYPASS.
J8-3
GND
Common for dry contacts signal STATIC
BYPASS.
J9-1
ALARM_NC
Normally closed contact -NC-, dry contacts
signal GENERAL ALARM.
J9-2
ALARM_NO
Normally open contact -NO-, dry contacts signal
GENERAL ALARM.
J9-3
GND
Common for dry contacts signal GENERAL
ALARM.
J10-1
UTI_FAIL_NC
Normally closed contact -NC-, dry contacts
signal, AC MAINS FAULT.
J10-2
UTI_FAIL_NO
Normally open contact -NO-, dry contacts signal
AC MAINS FAULT.
J10-3
GND
Common for dry contacts signal AC MAINS
FAULT.
Tabla 7.
Pinout terminal block for dry contacts.