SALICRU
7.3.6. Operation menu.
Click on the menu screen
to access the different func-
tions and commands.
Fig. 57.
Setting Menu.
7.3.6.1. Function icons.
•
Detail of the functionality of each icon:
-
Mute/un-mute.
Direct access without password.
Manual fault clearing or alarm.
Access with PSW # 1 key.
-
Manual transfer to bypass or exit by-
pass mode.
Access with PSW # 1 key.
Manual transfer to inverter.
The difference between touching this icon or leaving
the bypass mode
is that if for some reason the
inverter cannot connect to the output automatically,
this icon forces the transfer with an interruption of
around 20 ms.
Access with PSW # 1 key.
Activates the “Off” push button on the front of
the power module “ ”, to enable the individual stop-
page of any of them.
Direct access without password.
Clears battery history data including download
dates and times and number of downloads. It is usu-
ally recommended to reset the battery data logger, after
changing them by new ones.
Access with PSW # 1 key.
Delete dust filter data including days and main-
tenance period. This is usually done after changing the
filter or cleaning it.
Direct access without password.
7.3.6.2. Command icons.
•
Detail of the functionality of each icon:
Battery test command. The UPS switches to bat-
tery mode, the mains indicator LED is off and the bat-
tery LED flashes green. If the battery is not correct or
fails, the UPS will trigger an alarm and return to normal
mode or transfer to bypass mode.
To perform this test, ensure that:
–
There is no alarm or warning.
–
The battery voltage is higher than 90% of the
floating voltage.
If the battery is correct, the UPS will transfer back to
normal mode after 20 seconds. If the battery test fails,
the UPS will include the alarm in the historical log .
Access with PSW # 2 key, restricted to the
T.S.S.
or the
distributor.
Battery maintenance command. The UPS
switches to battery mode, the mains indicator LED is
off and the battery LED flashes green.
To perform this test, ensure that:
–
There is no alarm or warning.
–
The battery voltage is higher than 90% of the
floating voltage.
If the battery is correct, the UPS will transfer back to
normal mode when the battery voltage is approximately
105% of the end of discharge voltage [EOD].
Access with PSW # 1 key.
.
Allows the charger to enter manual charging
mode quickly, to force the boost charge.
Direct access without password.
Allows the charger to enter floating load mode
manually.
Direct access without password.
Useful for stopping battery test or battery main-
tenance .
Direct access without password.