background image

10

SALICRU

 

The cross-section of the cables must always be considered 

in relation to the size of the switch terminals, so that their 

entire cross-section is correctly embraced for optimal contact 

between the two elements.

 

Only the nominal currents are printed on the unit’s name plate, 

as indicated in the EN-IEC 62040-1 safety standard. Overload 

conditions are considered a temporary and exceptional oper-

ating mode.

 

If peripheral input, output or bypass elements such as trans-

formers or autotransformers are added to the UPS or parallel 

system, the currents indicated on the name plates of these 

elements must be considered in order to use the appropriate 

cross-sections, observing the local and/or national Low 

Voltage Electrotechnical Regulations.

 

It is important to never forget that once the installation is 

complete, the bypass panel will be connected to a UPS or 

group of UPSs. Based on the concept that a UPS is a gener-

ator of electrical energy, the user must take the necessary 

precautions to prevent direct or indirect contact.

5.2.  UNIT RECEPTION

5.2.1.  Unpacking, checking the contents and inspection.

 

For the unpacking, see section 5.2.3.

 

When receiving the unit, check that it has not been dam-

aged in any way during transport (impact, fall, etc.) and that 

the characteristics of the unit match those specified in the 

order. It is therefore recommended to unpack the stabiliser 

to carry out an initial visual inspection.

 

If any damage is detected, make the relevant claims to your 

supplier, or, failing that, our company.

Never start a unit when external damage is detected.

 

Also check that the information on the name plate on the 

packaging and on the unit match those specified in the order. 

Unpack it in order to do so (see section 5.2.3). Otherwise, 

deal with the non-conformity as soon as possible, citing the 

unit’s manufacturing number and the references on the de-

livery note.

 

Check the contents of the package:

 

ˆ

The bypass panel itself.

 

ˆ

The user manual in electronic format (CD-ROM).

 

ˆ

For panels supplied in wall-type boxes, the accessories 

required for its attachment (screws and supports) and 

the mechanical diagram.

 

Once the reception process is complete, the panel should be 

repacked until it is started up in order to protect it against 

mechanical shock, dust, dirt, etc.

5.2.2.  Storage

 

The unit must be stored in a dry, well-ventilated area, protected 

from rain, dust, splashes of water or chemical agents. It is rec-

ommended to keep the unit in its original packaging, as it has 

been specifically designed to ensure maximum protection during 

transport and storage.

5.2.3.  Unpacking 

 

The unit’s packaging may consist of a wooden pallet, 

cardboard or wooden packaging as applicable, expanded 

polystyrene (EPS) corner protectors, polyethylene cover and 

strips, all recyclable materials, so if you do dispose of them, 

you should do so in accordance with current laws. We rec-

ommend that you keep the packaging in case you need to 

use it in the future.

 

Proceed to unpack the unit

To do so, cut the strips around the cardboard packaging and/or 

the sealing tape. For panels with seaworthy packaging, open the 

packaging using the most appropriate means available to you.

Remove the unit from the cardboard or wooden box.

5.2.4.  Transfer to the installation site

 

If the reception area is far from the installation site, it is 

recommended to move the unit using a pallet truck or the 

most suitable means of transport, assessing the distance 

between the two points.

If the distance is considerable, it is recommended to move 

the unit in its packaging to the vicinity of the installation 

site and then unpack it.

5.2.5.  Siting

 

Locate the unit taking the indications and recommenda-

tions from the EK266*08 safety instructions into account.

 

The unit will be located in the vicinity of the UPS or system 

of parallel units made up of “n” units.

 

Manual bypass panels are provided in wall-type boxes, except 

for exceptional cases where they are mounted in cabinets.

For the former, carry out the machining tasks on the wall 

using the paper plane provided with the attachment acces-

sories and proceed to fix it in place.

5.3.  CONNECTIONS

 

Wall-type boxes are delivered with mounted cable glands, 

of the right size to correctly block the intended cables.

 

Depending on the type of input, bypass and/or output 

(single-phase or three-phase), the number of terminals 

on each block may vary. Connect the cables to the corre-

sponding terminals according to each case, respecting the 

order of the phase (R) or phases (R-S-T) and neutral (N).

Summary of Contents for SLC ADAPT

Page 1: ...SLC ADAPT SLC ADAPT X SLC ADAPT 2 SLC CUBE 3 SLC CUBE 4 7 5 80 kVA SLC X PERT SLC X TRA SLC TWIN PRO2 MAKE BEFORE BREAK MANUAL BYPASS PANEL FOR UPS BM USER S MANUAL...

Page 2: ...2 SALICRU...

Page 3: ...Systemswith n equipmentsinparallelorredundant 5 3 7 1 Powerconnections 5 3 7 2 Connection of the auxiliary contact of the manual bypass switch of each UPS with the one in the bypass panel not availab...

Page 4: ...onnel exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The image...

Page 5: ...SING THIS MANUAL The generic documentation for the unit is provided in digital format on a pen drive and includes among other documents the system user manual itself and document EK266 08 relating to...

Page 6: ...d in accordance with the EN ISO 9001 standard on Quality Assurance and is certified by SGS The mark indi cates conformity with the EEC Directives 2014 35 EU Low voltage directive 2014 30 EU Electromag...

Page 7: ...lbypasspanelto theUPS With a separate static bypass line Fig 2 These panels have separate terminal blocks for the input and static bypass networks which allows both networks to be supplied from differ...

Page 8: ...e from a source other than the UPS input line B Unit with separate bypass line L Single phase input single phase output configuration L Single phase input three phase output configuration N Three phas...

Page 9: ...a circuit breakers Depending on the panel model the enclosure may vary plastic ormetalbox ormetalcabinet sotheadjacencybetweenthem could be affected although the order would be maintained Depending on...

Page 10: ...n process is complete the panel should be repacked until it is started up in order to protect it against mechanical shock dust dirt etc 5 2 2 Storage The unit must be stored in a dry well ventilated a...

Page 11: ...identified with the label ensuring that this is done before supplying input voltage to the bypass panel Connect the loads to the set of terminals identified as LOADS OUTPUT on the bypass panel respect...

Page 12: ...nt Aux cont available on manual bypass panels for these UPSs SLC ADAPT SLC ADAPT X SLC ADAPT2 SLC CUBE 3 SLC CUBE 4 SLC X PERT SLC X TRA 1 YES YES YES YES YES YES YES 2 YES YES YES 1 YES YES 1 The IDI...

Page 13: ...ese UPSs SLC CUBE 3 SLC CUBE 4 SLC TWIN PRO 2 1 YES YES 2 YES YES Fig 5 Manualbypasspanelfor n standardparallelorredundantUPSs forUPSseriesCUBE3 CUBE4andTWINPRO2 5 3 7 3 Connection between the auxilia...

Page 14: ...t circuit breaker Fig 6 Manual bypass panel for n standard parallel or redundant UPSs for the ADAPT ADAPT X ADAPT2 TWIN PRO2 X PERT and X TRA series INPUT LINE LOADS OUTPUT MANUAL BYPASS Aux cont Manu...

Page 15: ...programmed as an auxiliary contact for the NC output circuit breaker Fig 8 Manual bypass panel for n standard parallel or redundant UPSs with a separate bypass line for the ADAPT ADAPT X ADAPT2 TWIN...

Page 16: ...ut Auxiliary Contact Input Battery Circuit Breaker Auxiliary Contact Input External Digital Input External Digital Input External Digital Input External Digital Input SREG_LOGIC_POS_NEG__DIG_ALMS_BOOL...

Page 17: ...PSNSTATICBYPASS Off UPS NOUTPUT Off Fig 10 Position of the manual bypass switches Out of service with several UPS s Make sure that all the loads are shutdown start up switches turned Off Proceed in th...

Page 18: ...er Off according to the procedure stated in the User s installation and start up manual of the UPS It is essential to shutdown the inverter of the UPS before proceeding otherwise a short circuit at it...

Page 19: ...to the factory for its fixing This option is valid when the power of the equipments which are still installed is enough to supply the loads Evenitisunlikelybutnotimpossible anynewfaultinany of the rem...

Page 20: ...according to the procedure stated in the User s installation and start up manual of the equipment Turn the UPS INPUT and UPS OUTPUT switches of the bypass panel to Off In case of including the separat...

Page 21: ...21 USER S MANUAL...

Page 22: ...any salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Reviews: