background image

11

 

When there are discrepancies between the labels 

and the instructions in this manual, the labels on the 

unit will always take precedence.

 

References 

in bold in brackets

 that appear in the different 

sections of this chapter, correspond to elements of the UPSs 

identified in their respective user manual. For more informa-

tion, consult this document.

5.3.1.  Connection of the bypass panel power. UPS input line 

(rectifier)

 

The earth connection must be connected to the ter-

minal identified with the 

( )

 label, ensuring that this 

is done before supplying input voltage to the bypass panel.

 

Connect the bypass panel input line power cables to the ter-

minals indicated as “INPUT LINE”, respecting the order of the 

phase (R) or phases (R-S-T) and neutral (N), indicated on the 

unit’s labels and in this manual.

It is essential to have a neutral (N).

5.3.2.  Connection of the bypass panel power. Static bypass 

line (only on -B panels).

 

The earth connection must be connected to the ter-

minal identified with the 

( )

 label, ensuring that this 

is done before supplying input voltage to the bypass panel.

 

Connect the bypass panel’s static bypass line power ca-

bles to the terminals indicated as “STATIC BYPASS INPUT 

LINE”, respecting the order of the phase (R) or phases (R-

S-T) and neutral (N), indicated on the unit’s labels and in 

this manual.

It is essential to have a neutral (N).

5.3.3.  Connection of the UPS to the bypass panel

 

Connect a cable bundle between the set of terminals identi-

fied as “UPS INPUT” on the bypass panel and the UPS input 

terminals identified as “INPUT”, respecting the order of the 

phase (R) or phases (R-S-T) and neutral (N), indicated on the 

unit’s labels and in this manual. 

 

On units with a separate static bypass line, connect a cable 

bundle between the set of terminals identified as “STATIC BY-

PASS INPUT” on the bypass panel and the UPS input terminals 

identified as “STATIC BYPASS”, respecting the order of the 

phases (R-S-T) and neutral (N), indicated on the unit’s labels 

and in this manual.

 

Connect a cable bundle between the set of terminals iden-

tified as “UPS OUTPUT” on the bypass panel and the UPS 

output terminals identified as “OUTPUT”, respecting the 

order of the phase (R) or phases (R-S-T) and neutral (N), 

indicated on the unit’s labels and in this manual.

5.3.4.  Connection of the loads to the bypass panel

 

The earth connection must be connected to the ter-

minal identified with the 

( )

 label, ensuring that this 

is done before supplying input voltage to the bypass panel.

 

Connect the loads to the set of terminals identified as 

“LOADS OUTPUT” on the bypass panel, respecting the 

order of the phase (R) or phases (R-S-T) and neutral (N), 

indicated on the unit’s labels and in this manual.

5.3.5.  Connection of the auxiliary contact of the UPS 

manual bypass switch to the bypass panel

 

The terminals identified as “BYPASS AUXILIARY CON-

TACT” on the UPS must be connected to those on the 

bypass panel using control cables (minimum 1 mm

2

 and max-

imum 2.5 mm

2

). These signal terminals are the extension of the 

normally open auxiliary contact of the respective internal 

manual bypass switch.

The auxiliary terminals of the UPS are identified as follows, 

depending on the product series:

 

ˆ

ADAPT, ADAPT-X, pins

 1 

and

 2 

of

 (JP5)

.

 

ˆ

ADAPT2, pins 1 and 2 of 

(IDIG3)

.

 

ˆ

CUBE3+, 2-terminal strip 

(X51)

.

 

ˆ

CUBE4, 2-terminal strip 

(IDIG3)

.

 

ˆ

X-PERT, terminals 

(X10-1), (X10-2)

.

 

ˆ

X-TRA, terminals 

(MBY-1)

 and 

(MBY-2)

.

 

ˆ

TWIN PRO, 2-terminal strip 

(EMBS)

.

 

This connection is a safety lock against unwanted or erro-

neous operations, which, without it, would lead to faults on 

the UPS and/or in the loads supplied by it, as it transfers the 

inverter to “OFF” when switching any of the manual bypass 

switches to “ON”.

5.3.6.  Connection of the auxiliary contact of the UPS output 

switch to the bypass panel (only available on panels 

from the SLC CUBE3+ and SLC CUBE4 series).

The output switch on each UPS has a normally open auxiliary 

contact with a cable connected as a bridge 

(PT)

 that closes 

its circuit respectively on terminal strip 

(X45)

 on CUBE3+, 

on terminal strip 

(IDIG4)

 on CUBE4 30-80 kVA, between the 

terminals on strip

 (XAUX-1)

 and 

(XAUX-2)

 on X-TRA, or be-

tween terminals 

(X10-5)

 and 

(X10-6)

 on X-PERT. 

On CUBE4 7.5-20 kVA models, the output switch does not 

have an auxiliary contact, but it does have the auxiliary con-

tact signal of the external output switch between terminals 5 

and 11 or 9 on the INPUT SIGNAL terminal strip.

 

Remove it and, using control cables (minimum 1 mm

2

 and 

maximum 2.5 mm

2

), connect the terminals identified as 

“OUTPUT AUXILIARY CONTACT” on the UPS 

(X45)

(IDIG4) 

and (between terminals 

5 and 11 or 9 INPUT SIGNAL

) to 

those on the bypass panel. Both terminals are the extension 

of the normally open auxiliary contact of the respective 

output switch. 

The purpose of this connection is none other than to activate 

the alarm on the control panel due to accidental tripping or 

voluntary/involuntary switching to “OFF” of either of the two 

output switches (on the UPS or the panel).

USER'S MANUAL        

Summary of Contents for SLC ADAPT

Page 1: ...SLC ADAPT SLC ADAPT X SLC ADAPT 2 SLC CUBE 3 SLC CUBE 4 7 5 80 kVA SLC X PERT SLC X TRA SLC TWIN PRO2 MAKE BEFORE BREAK MANUAL BYPASS PANEL FOR UPS BM USER S MANUAL...

Page 2: ...2 SALICRU...

Page 3: ...Systemswith n equipmentsinparallelorredundant 5 3 7 1 Powerconnections 5 3 7 2 Connection of the auxiliary contact of the manual bypass switch of each UPS with the one in the bypass panel not availab...

Page 4: ...onnel exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The image...

Page 5: ...SING THIS MANUAL The generic documentation for the unit is provided in digital format on a pen drive and includes among other documents the system user manual itself and document EK266 08 relating to...

Page 6: ...d in accordance with the EN ISO 9001 standard on Quality Assurance and is certified by SGS The mark indi cates conformity with the EEC Directives 2014 35 EU Low voltage directive 2014 30 EU Electromag...

Page 7: ...lbypasspanelto theUPS With a separate static bypass line Fig 2 These panels have separate terminal blocks for the input and static bypass networks which allows both networks to be supplied from differ...

Page 8: ...e from a source other than the UPS input line B Unit with separate bypass line L Single phase input single phase output configuration L Single phase input three phase output configuration N Three phas...

Page 9: ...a circuit breakers Depending on the panel model the enclosure may vary plastic ormetalbox ormetalcabinet sotheadjacencybetweenthem could be affected although the order would be maintained Depending on...

Page 10: ...n process is complete the panel should be repacked until it is started up in order to protect it against mechanical shock dust dirt etc 5 2 2 Storage The unit must be stored in a dry well ventilated a...

Page 11: ...identified with the label ensuring that this is done before supplying input voltage to the bypass panel Connect the loads to the set of terminals identified as LOADS OUTPUT on the bypass panel respect...

Page 12: ...nt Aux cont available on manual bypass panels for these UPSs SLC ADAPT SLC ADAPT X SLC ADAPT2 SLC CUBE 3 SLC CUBE 4 SLC X PERT SLC X TRA 1 YES YES YES YES YES YES YES 2 YES YES YES 1 YES YES 1 The IDI...

Page 13: ...ese UPSs SLC CUBE 3 SLC CUBE 4 SLC TWIN PRO 2 1 YES YES 2 YES YES Fig 5 Manualbypasspanelfor n standardparallelorredundantUPSs forUPSseriesCUBE3 CUBE4andTWINPRO2 5 3 7 3 Connection between the auxilia...

Page 14: ...t circuit breaker Fig 6 Manual bypass panel for n standard parallel or redundant UPSs for the ADAPT ADAPT X ADAPT2 TWIN PRO2 X PERT and X TRA series INPUT LINE LOADS OUTPUT MANUAL BYPASS Aux cont Manu...

Page 15: ...programmed as an auxiliary contact for the NC output circuit breaker Fig 8 Manual bypass panel for n standard parallel or redundant UPSs with a separate bypass line for the ADAPT ADAPT X ADAPT2 TWIN...

Page 16: ...ut Auxiliary Contact Input Battery Circuit Breaker Auxiliary Contact Input External Digital Input External Digital Input External Digital Input External Digital Input SREG_LOGIC_POS_NEG__DIG_ALMS_BOOL...

Page 17: ...PSNSTATICBYPASS Off UPS NOUTPUT Off Fig 10 Position of the manual bypass switches Out of service with several UPS s Make sure that all the loads are shutdown start up switches turned Off Proceed in th...

Page 18: ...er Off according to the procedure stated in the User s installation and start up manual of the UPS It is essential to shutdown the inverter of the UPS before proceeding otherwise a short circuit at it...

Page 19: ...to the factory for its fixing This option is valid when the power of the equipments which are still installed is enough to supply the loads Evenitisunlikelybutnotimpossible anynewfaultinany of the rem...

Page 20: ...according to the procedure stated in the User s installation and start up manual of the equipment Turn the UPS INPUT and UPS OUTPUT switches of the bypass panel to Off In case of including the separat...

Page 21: ...21 USER S MANUAL...

Page 22: ...any salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Reviews: