11
•
When there are discrepancies between the labels
and the instructions in this manual, the labels on the
unit will always take precedence.
•
References
in bold in brackets
that appear in the different
sections of this chapter, correspond to elements of the UPSs
identified in their respective user manual. For more informa-
tion, consult this document.
5.3.1. Connection of the bypass panel power. UPS input line
(rectifier)
•
The earth connection must be connected to the ter-
minal identified with the
( )
label, ensuring that this
is done before supplying input voltage to the bypass panel.
•
Connect the bypass panel input line power cables to the ter-
minals indicated as “INPUT LINE”, respecting the order of the
phase (R) or phases (R-S-T) and neutral (N), indicated on the
unit’s labels and in this manual.
It is essential to have a neutral (N).
5.3.2. Connection of the bypass panel power. Static bypass
line (only on -B panels).
•
The earth connection must be connected to the ter-
minal identified with the
( )
label, ensuring that this
is done before supplying input voltage to the bypass panel.
•
Connect the bypass panel’s static bypass line power ca-
bles to the terminals indicated as “STATIC BYPASS INPUT
LINE”, respecting the order of the phase (R) or phases (R-
S-T) and neutral (N), indicated on the unit’s labels and in
this manual.
It is essential to have a neutral (N).
5.3.3. Connection of the UPS to the bypass panel
•
Connect a cable bundle between the set of terminals identi-
fied as “UPS INPUT” on the bypass panel and the UPS input
terminals identified as “INPUT”, respecting the order of the
phase (R) or phases (R-S-T) and neutral (N), indicated on the
unit’s labels and in this manual.
•
On units with a separate static bypass line, connect a cable
bundle between the set of terminals identified as “STATIC BY-
PASS INPUT” on the bypass panel and the UPS input terminals
identified as “STATIC BYPASS”, respecting the order of the
phases (R-S-T) and neutral (N), indicated on the unit’s labels
and in this manual.
•
Connect a cable bundle between the set of terminals iden-
tified as “UPS OUTPUT” on the bypass panel and the UPS
output terminals identified as “OUTPUT”, respecting the
order of the phase (R) or phases (R-S-T) and neutral (N),
indicated on the unit’s labels and in this manual.
5.3.4. Connection of the loads to the bypass panel
•
The earth connection must be connected to the ter-
minal identified with the
( )
label, ensuring that this
is done before supplying input voltage to the bypass panel.
•
Connect the loads to the set of terminals identified as
“LOADS OUTPUT” on the bypass panel, respecting the
order of the phase (R) or phases (R-S-T) and neutral (N),
indicated on the unit’s labels and in this manual.
5.3.5. Connection of the auxiliary contact of the UPS
manual bypass switch to the bypass panel
•
The terminals identified as “BYPASS AUXILIARY CON-
TACT” on the UPS must be connected to those on the
bypass panel using control cables (minimum 1 mm
2
and max-
imum 2.5 mm
2
). These signal terminals are the extension of the
normally open auxiliary contact of the respective internal
manual bypass switch.
The auxiliary terminals of the UPS are identified as follows,
depending on the product series:
ADAPT, ADAPT-X, pins
1
and
2
of
(JP5)
.
ADAPT2, pins 1 and 2 of
(IDIG3)
.
CUBE3+, 2-terminal strip
(X51)
.
CUBE4, 2-terminal strip
(IDIG3)
.
X-PERT, terminals
(X10-1), (X10-2)
.
X-TRA, terminals
(MBY-1)
and
(MBY-2)
.
TWIN PRO, 2-terminal strip
(EMBS)
.
•
This connection is a safety lock against unwanted or erro-
neous operations, which, without it, would lead to faults on
the UPS and/or in the loads supplied by it, as it transfers the
inverter to “OFF” when switching any of the manual bypass
switches to “ON”.
5.3.6. Connection of the auxiliary contact of the UPS output
switch to the bypass panel (only available on panels
from the SLC CUBE3+ and SLC CUBE4 series).
The output switch on each UPS has a normally open auxiliary
contact with a cable connected as a bridge
(PT)
that closes
its circuit respectively on terminal strip
(X45)
on CUBE3+,
on terminal strip
(IDIG4)
on CUBE4 30-80 kVA, between the
terminals on strip
(XAUX-1)
and
(XAUX-2)
on X-TRA, or be-
tween terminals
(X10-5)
and
(X10-6)
on X-PERT.
On CUBE4 7.5-20 kVA models, the output switch does not
have an auxiliary contact, but it does have the auxiliary con-
tact signal of the external output switch between terminals 5
and 11 or 9 on the INPUT SIGNAL terminal strip.
•
Remove it and, using control cables (minimum 1 mm
2
and
maximum 2.5 mm
2
), connect the terminals identified as
“OUTPUT AUXILIARY CONTACT” on the UPS
(X45)
,
(IDIG4)
and (between terminals
5 and 11 or 9 INPUT SIGNAL
) to
those on the bypass panel. Both terminals are the extension
of the normally open auxiliary contact of the respective
output switch.
The purpose of this connection is none other than to activate
the alarm on the control panel due to accidental tripping or
voluntary/involuntary switching to “OFF” of either of the two
output switches (on the UPS or the panel).
USER'S MANUAL
Summary of Contents for SLC ADAPT
Page 2: ...2 SALICRU...
Page 21: ...21 USER S MANUAL...