background image

17

6.  START UP AND SHUTDOWN.

 

These instructions are generic for any manual bypass panel 

of this series, parallel and redundant equipments included. 

Omit those manoeuvring of the switches that your unit 

doesn’t have.

 

The references 

in bold between brackets, 

which are shown 

in the different points of this section, correspond to the UPS 

elements identified in their own user’s manual. For more infor-

mation consult that document.

 

The shown illustrations in this section are mere examples and  

they are with four poles switches of DIN rail type, but in practice 

they can differ in one or more aspects like: type of panel configu-

ration, format, size or protection type. Nevertheless, in any case 

the order will not be different from the stated in them.

Also, in the manual bypass panels in parallel or redundant 

equipments, the illustrations do not match with any preset 

system, so they are generic for any panel regardless of the 

quantity of equipments in parallel or redundant that belong 

to. 

6.1.  CONTROLS BEFORE THE START UP.

 

Check that all connections have done properly, by re-

specting the labelling of the equipment and the instructions 

in section «INSTALLATION». If phase or phases and neu-

tral rotation is not respected, important damages can be 

caused to the panel, UPS or UPS’s and/or connected loads.

 

In order to avoid bad electrical contacts, check the connec-

tions screws are firmly tighten.

 

Check all switches coming from the power supply which 

feeds the bypass panel, the own ones in the panel (see Fig. 

9 or 10 depending on the case) and the ones in the UPS or 

UPS’s are turned «Off».

UPS INPUT

STATIC BYPASS

MANUAL BYPASS

UPS OUTPUT

Off

Off

Off +

 

Off

Fig. 9. 

Position of the manual bypass switches «Out of 

service» (with one UPS only).

UPS 1 INPUT

UPS 1 STATIC BYPASS

MANUAL BYPASS

UPS 1 OUTPUT

Off

Off

Off +

 

Off

•••

UPS N INPUT

Off

•••

UPS N STATIC BYPASS

Off

UPS N OUTPUT

Off

•••

Fig. 10. 

Position of the manual bypass switches «Out of 

service» (with several UPS’s).

 

Make sure that all the loads are shutdown (start up 

switches turned «Off»).

 

Proceed in the established order of this document. Any 

wrong manoeuvring over the stated switches of the by-

pass panel, or the ones in the UPS or UPS’s, can cause a break or 

short-circuits in the power supply to the loads, with the unin-

tended  and unexpected consequences for any part of the set.

 

In the installation section, for single and parallel equipments, 

it is stated the need of connecting the auxiliary contact of 

the manual bypass with the one in the manual bypass panel. 

Thanks to this auxiliary safety contact, in case of wrong or 

different manoeuvring than the stated in this section, it is 

avoided to overlap the inverter output with the UPS input 

power supply.

For any change in the operating mode, respect the steps 

stated in the instructions of this section strictly, and in par-

ticular, for the TWIN PRO 33 series, which do not have this 

auxiliary contact, but they have the needed protections, in 

order to make the steps in the established order.

Before starting the equipment up, check that the 

manual bypass switch of the equipment or equip-

ments and the one in the manual bypass panel are in the 

same position (UPS and Off or BYPASS and On).

6.2.  OPERATION TO SHIFT FROM 

«

OUT OF SERVICE

»

 (UPS 

OR UPS’S TO 

«

OFF

»

) TO 

«

NORMAL OPERATING

» 

(LOADS 

SUPPLIED BY THE UPS OR UPS’S).

 

Turn the external protections of the bypass panel «On» (RCD and/

or circuit breaker switches), they will supply energy to the termi-

nals labelled as «INPUT LINE».

 

In panels with separate bypass line (-B), turn the external 

protections of the bypass panel «On» (RCD and/or circuit breaker 

switches) «On», they will supply energy to the terminals labelled 

as «STATIC BYPASS INPUT LINE».

6.2.1.  Manual bypass panel with one UPS only.

 

Turn the «UPS INPUT» and «UPS OUTPUT» switches of the 

bypass panel to «On». In case of including the separate by-

pass line (-B), turn the «STATIC BYPASS» switch of the bypass 

USER'S MANUAL        

Summary of Contents for SLC ADAPT

Page 1: ...SLC ADAPT SLC ADAPT X SLC ADAPT 2 SLC CUBE 3 SLC CUBE 4 7 5 80 kVA SLC X PERT SLC X TRA SLC TWIN PRO2 MAKE BEFORE BREAK MANUAL BYPASS PANEL FOR UPS BM USER S MANUAL...

Page 2: ...2 SALICRU...

Page 3: ...Systemswith n equipmentsinparallelorredundant 5 3 7 1 Powerconnections 5 3 7 2 Connection of the auxiliary contact of the manual bypass switch of each UPS with the one in the bypass panel not availab...

Page 4: ...onnel exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The image...

Page 5: ...SING THIS MANUAL The generic documentation for the unit is provided in digital format on a pen drive and includes among other documents the system user manual itself and document EK266 08 relating to...

Page 6: ...d in accordance with the EN ISO 9001 standard on Quality Assurance and is certified by SGS The mark indi cates conformity with the EEC Directives 2014 35 EU Low voltage directive 2014 30 EU Electromag...

Page 7: ...lbypasspanelto theUPS With a separate static bypass line Fig 2 These panels have separate terminal blocks for the input and static bypass networks which allows both networks to be supplied from differ...

Page 8: ...e from a source other than the UPS input line B Unit with separate bypass line L Single phase input single phase output configuration L Single phase input three phase output configuration N Three phas...

Page 9: ...a circuit breakers Depending on the panel model the enclosure may vary plastic ormetalbox ormetalcabinet sotheadjacencybetweenthem could be affected although the order would be maintained Depending on...

Page 10: ...n process is complete the panel should be repacked until it is started up in order to protect it against mechanical shock dust dirt etc 5 2 2 Storage The unit must be stored in a dry well ventilated a...

Page 11: ...identified with the label ensuring that this is done before supplying input voltage to the bypass panel Connect the loads to the set of terminals identified as LOADS OUTPUT on the bypass panel respect...

Page 12: ...nt Aux cont available on manual bypass panels for these UPSs SLC ADAPT SLC ADAPT X SLC ADAPT2 SLC CUBE 3 SLC CUBE 4 SLC X PERT SLC X TRA 1 YES YES YES YES YES YES YES 2 YES YES YES 1 YES YES 1 The IDI...

Page 13: ...ese UPSs SLC CUBE 3 SLC CUBE 4 SLC TWIN PRO 2 1 YES YES 2 YES YES Fig 5 Manualbypasspanelfor n standardparallelorredundantUPSs forUPSseriesCUBE3 CUBE4andTWINPRO2 5 3 7 3 Connection between the auxilia...

Page 14: ...t circuit breaker Fig 6 Manual bypass panel for n standard parallel or redundant UPSs for the ADAPT ADAPT X ADAPT2 TWIN PRO2 X PERT and X TRA series INPUT LINE LOADS OUTPUT MANUAL BYPASS Aux cont Manu...

Page 15: ...programmed as an auxiliary contact for the NC output circuit breaker Fig 8 Manual bypass panel for n standard parallel or redundant UPSs with a separate bypass line for the ADAPT ADAPT X ADAPT2 TWIN...

Page 16: ...ut Auxiliary Contact Input Battery Circuit Breaker Auxiliary Contact Input External Digital Input External Digital Input External Digital Input External Digital Input SREG_LOGIC_POS_NEG__DIG_ALMS_BOOL...

Page 17: ...PSNSTATICBYPASS Off UPS NOUTPUT Off Fig 10 Position of the manual bypass switches Out of service with several UPS s Make sure that all the loads are shutdown start up switches turned Off Proceed in th...

Page 18: ...er Off according to the procedure stated in the User s installation and start up manual of the UPS It is essential to shutdown the inverter of the UPS before proceeding otherwise a short circuit at it...

Page 19: ...to the factory for its fixing This option is valid when the power of the equipments which are still installed is enough to supply the loads Evenitisunlikelybutnotimpossible anynewfaultinany of the rem...

Page 20: ...according to the procedure stated in the User s installation and start up manual of the equipment Turn the UPS INPUT and UPS OUTPUT switches of the bypass panel to Off In case of including the separat...

Page 21: ...21 USER S MANUAL...

Page 22: ...any salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Reviews: