6.3.2. Manual bypass panel with two or more UPS’s.
•
Put all the UPS’s
on bypass (inverters «Off»)
, according
to the procedure stated in the «User’s, installation and start
up manual» of the UPS.
It is essential
to shutdown the inverters
of the
UPS’s before proceeding, otherwise a short-circuit at
its output will be made with unexpected and unintended out-
comes for any part of the set (UPS’s, panel and loads).
•
Remove the mechanical lock from the switch labelled as
«MANUAL BYPASS» in the bypass panel and turn it «On».
Keep the mechanical lock in a safe place, because it will
have to put it back, once the maintenance or fixing tasks
have been finished.
•
Manual bypass panels with isolation transformer, the loads
will be supplied with a clean and/or attenuated voltage
from electrical noises.
•
Turn the «UPS 1 INPUT» to «UPS N INPUT» and «UPS
1 OUTPUT» to «UPS N OUTPUT» switches of the bypass
panel to «Off». In case of including the separate bypass line
(-B), turn the «UPS 1 STATIC BYPASS» to «UPS N STATIC
BYPASS» switches of the bypass panel «Off» too. In the
illustration of Fig. 14, it is shown the position of switches
once the manoeuvring has been done.
UPS 1 INPUT
UPS 1 STATIC BYPASS
MANUAL BYPASS
UPS 1 OUTPUT
Off
Off
On +
Off
•••
UPS N INPUT
Off
•••
UPS N STATIC BYPASS
Off
UPS N OUTPUT
Off
•••
Fig. 14.
Position of the bypass panel switches in «Mainte-
nance operating» (with several UPS’s).
•
Loads are supplied by mains directly through the manual
bypass panel and UPS’s are completely shutdown, so they
are ready to be serviced for a preventive maintenance,
fixing or replacement for another equipment with the same
specifications.
•
In case of faulty UPS, it can also be removed and sent to the
factory for its fixing. This option is valid when the power of the
equipments, which are still installed is enough to supply the
loads. Even it is unlikely but not impossible, any new fault in any
of the remaining equipments and the possible consequences
that could happen will be assumed.
Even, if this alternative is going to be done, it is man-
datory to remove any cable bundle connected to the
panel, which has at its opposite end the cables bare from
isolation, resulting in a risk of electrocution or short-circuit in
case of turning on any of the panel switches.
6.4. SHIFTING FROM «MAINTENANCE OPERATING» (LOADS
SUPPLIED THROUGH THE MANUAL BYPASS) TO
«NORMAL OPERATING» (LOADS SUPPLIED BY THE UPS
OR UPS’S).
6.4.1. Manual bypass panels with one UPS only.
•
Once the preventive maintenance, fixing or UPS replacing
tasks have been finished, loads must be shifted to UPS, but
checking the following points previously:
UPS switches are turned «Off».
Bypass panel switches, less the «MANUAL BYPASS»
switch are turned «Off».
•
Turn the «UPS INPUT» and «UPS OUTPUT» switches of the
bypass panel to «On». In case of including the separate
bypass line (-B), turn the «STATIC BYPASS» switch of the
bypass panel «On» too.
•
Turn the «MANUAL BYPASS» switch of panel bypass to
«Off» and put the mechanical lock back.
For safety it is mandatory to put back the mechanical
lock before proceeding with the operating.
•
In the illustration of Fig. 15 it is shown the position of the
panel switches after doing the manoeuvring of this point.
•
Start the UPS up according to the procedure stated in the
«User’s, installation and start up manual» of the equipment.
The bypass panel supplies voltage to the terminals labelled
as «LOADS OUTPUT» to the loads from UPS.
UPS INPUT
STATIC BYPASS
MANUAL BYPASS
UPS OUTPUT
On
On
Off +
On
Fig. 15.
Position of the bypass panel switches in «Normal
operating» (with one UPS only).