52
SALICRU
10. GENERAL TECHNICAL FEATURES.
10.1. INTERNATIONAL STANDARDS.
Information
Standards
Quality and Environmental Management
ISO 9001 & ISO 14001
General and safety requirements for UPS used in user access areas.
IEC/EN62040-1
Electromagnetic compatibility (EMC) requirements for UPS
EN-IEC 62040-2
Railway standards
EN 50121-4 / EN 50121-5
Method of specifying the performance and test requirements of UPS
VFI-IEC-111 (EN-IEC 62040-3)
Table 14.
Standards applied.
10.2. ENVIRONMENTAL CHARACTERISTICS.
Information
Units
Environmental
Acoustic noise at 1 metre distance
dB(A)
56.0
Operating altitude
masl
2400
Relative humidity
%
0.. 95%, non-condensing
Operating temperature
ºC
0.. 40 (battery life is reduced by 50% for every 10ºC increase over 20ºC)
Storage and transport temperature
ºC
-20.. +70 (UPS)
Recommended battery storage temperature
ºC
0.. 25 (20ºC for optimum storage)
Table 15.
Environmental characteristics.
10.3. MECHANICAL CHARACTERISTICS.
Specifications of the cabinets
Units
24 U
33 U
42 U
UPS
Bat.
Dimensions (Depth × Width × Height)
mm
888 × 639 × 1103
888 x 639 x 1613
888 x 639 x 2013
Yes
Yes
Colour
-
RAL 9005
Degree of protection, IEC60529
-
IP20
Sub-rack specifications
Units
20/10 and 30/15
40/10 and 45/15
60/10 and 90/15
Dimensions (Depth × Width × Height)
mm
671 × 485 × 308
671 × 485 × 485
792 × 485 × 1033
Weight
Kg.
58 ÷ 73
66 ÷ 112
100 ÷ 178
Colour
-
RAL 9005
Degree of protection, IEC60529
-
IP20
Power module specifications (PM)
Units
10 kVA
15 kVA
Dimensions (Depth × Width × Height)
mm
590 × 485 × 85
Weight
Kg.
15.3
15.5
Colour
-
RAL 9005
Specifications of Bypass and Monitoring
Module (MBS)
Units
2-slot and 4-slot sub-racks
6-slot sub-rack
Dimensions (Depth × Width × Height)
mm
395 × 485 × 130
380 × 485 × 380
Weight
Kg.
4.5
13.5
Colour
-
RAL 9005
Table 16.
Mechanical characteristics.