27
5. INSTALLATION
•
Read and follow the Safety Information set out in
chapter
of this document. Failure to adhere to any
of the indications set out in chapter 2 may cause a serious
or very serious accident for those who are in direct contact
with the unit or who are in the vicinity, as well as faults in
the unit and/or in the loads connected to it.
•
In addition to the unit's user manual, other documents are
supplied on the documentation pen drive. Consult them and
strictly follow the indicated procedure.
•
The cross-sections of the cables used for the installation
will be in line with the currents indicated on the name
plate, in compliance with local Low Voltage Electrotech-
nical Regulations.
•
This chapter details the relevant requirements for locating
and wiring the
SLC CUBE4
UPS series. As each site has its
own location and installation particularities, the purpose of
this chapter is not to provide precise step-by-step instruc-
tions, rather it should be used as a guide for the general
procedures and practices to be observed by
qualified
staff
(figure recognised and defined in the EK266*08 safety in-
structions).
•
Unless indicated otherwise, all actions, indications, prem-
ises, notes, etc. are applicable to the units, whether or not
they form part of a parallel system.
5.1. RECEPTION
•
All cabinets are supplied on wooden pallets that are me-
chanically attached to them, with cardboard or wooden
packaging according to the model. Although the risk of tip-
ping is minimal, they must be handled with care, especially
the taller cabinets and when there is a slope.
It is dangerous to handle the unit on the pallet in
a careless manner, as it could tip and cause se-
rious or very serious injuries to the operators, resulting
from impact due to it possibly tipping over and/or opera-
tors becoming trapped. Pay attention to section 1.2.1. of
the safety instructions -EK266*08- in all matters relating
to the handling, moving and positioning of the unit.
•
Use the most suitable means for moving the UPS when it is
still packed, with a pallet truck or forklift.
•
Any handling of the unit must be done paying attention to
the weights indicated in
"Annex I. Technical specifications"
according to the model.
5.1.1. Reception, unpacking and contents
•
Reception. Check that:
The information on the label attached to the packaging
corresponds to the information specified in the order.
Once the UPS is unpacked, check the above information
with the information on the unit's name plate.
If there are any discrepancies, deal with the non-con-
formity as soon as possible, citing the unit's manufac-
turing number and the references on the delivery note.
It has not suffered any mishap during transport (pack-
aging and impact indicator in perfect condition).
Otherwise, follow the protocol indicated on the label at-
tached to the impact indicator, located on the packaging.
•
Unpacking
To check the contents, the packaging must be removed.
Complete the unpacking according to the proce-
dure in section
•
Contents
The unit(s), consisting of a number of specific power
modules.
Additional UPS cabinets, if any, for connection in par-
allel, connection bus cables.
Battery cabinets, if any, for their connection with the
UPS cabinets.
•
Once the reception process is complete, the UPS should be
repacked until it is started up in order to protect it against
mechanical shock, dust, dirt, etc.
5.1.2. Storage
•
The unit must be stored in a dry, well-ventilated area,
protected from rain, dust, splashes of water or chemical
agents. It is recommended to keep each unit in its original
packaging, as it has been specifically designed to ensure
maximum protection during transport and storage.
•
Do not store units where the ambient temperature exceeds the
"Annex I. Technical specifications"
.
•
When a battery pack is supplied with the UPS cabinet, ei-
ther in the cabinet, separately to be installed in a cabinet
belonging to the customer, to be installed in a battery rack
or in any other way and it is not installed immediately in
the unit, it will be stored in a cool, dry and well-ventilated
area, at a controlled temperature of between 20 and 25ºC.
In general, and except for specific cases when
batteries are supplied, they are of the sealed
lead calcium type. To prevent degradation during
storage, they should be recharged at the intervals indi-
cated according to the temperature they are exposed to
(see date of last charge noted on the label attached to
the battery unit packaging
Fecha carga /
Fecha recarga /
Charging date :
Recharging date:
DY933B00 - 401AF000001
BACK MA
TERIAL
MUY IMPORTANTE PARA LA VIDA DE LAS BATERÍAS DE Pb-Ca:
Para evitar
su degradación deben ser recargadas en los intervalos indicados. Respetar
el procedimiento referido en el manual de usuario del equipo.
VERY IMPORTANT FOR THE LIFETIME OF Pb-Ca BATTERIES:
In order to avoid
their degradation, they must be recharged according to the stated interval
times. Respect the procedure referred in the equipment user’s manual.
0 - 20
12
21 - 30
9
31 - 40
5
41 - 50
2,5
Meses /
Months
ºC
Factory charging date noted.
Space to note the new charging date.
**-**-****
Data label for the model.
Fig. 21.
Label on the packaging of the battery unit.
SLC CUBE4
- UNINTERRUPTIBLE POWER SUPPLY SYSTEM
-
USER MANUAL