67
Wiring Specification
30 kVA
40 kVA
50 kVA
60 kVA
80 kVA
Rectifier input general line section (mm
2
)
16
25
35
50
Bypass general line section (mm
2
)
10
16
25
35
General output line (mm
2
)
Manual bypass general line (mm
2
)
Auxiliary contacts (mm
2
)
1,5
Terminal type
Rounds
M6 Input/Output
Rounds
M8 In/M6 Out.
Rounds M8 Input/Output
Maximum number of conductors in a single terminal
2
Wiring insulation temperature (º C)
90
Torque (Nm)
5 Input/Output
6 Input/5 Output
6 Input/Output
Tabla 15.
Wiring specification and torque.
9.4. ELECTRICAL CHARACTERISTICS
9.4.1. Electrical characteristics (rectifier input)
Rectifier specifications
30 kVA
40 kVA
50 kVA
60 kVA
80 kVA
Active power (kW)
30
40
50
60
80
Technology
Double boosters per phase, 3 switching levels
Three-phase nominal voltage (3P + N + E)
3 x 380 V / 3 x 400 V / 3 x 415 V
Input voltage range (for 3 x 400 V)
+15 %
~
-15 %: 100% load / -15%
~
-50%: load degradation up to 65%
Frequency
50 Hz / 60 Hz ± 5 Hz (45 to 65 Hz)
Nominal input current (3 x 380 V / 3 x 400 V / 3 x 415 V) (A)
48 / 46 / 44
64 / 61 / 58
80 / 76 / 73
95 / 91 / 87
127 / 121 / 117
Maximum input current (A) at minimum voltage and maximum
battery charge (3 x 380 V / 3 x 400 V / 3 x 415 V)
64 / 61 / 59
83 / 79 / 76
102 / 97 / 93
120 / 114 / 110
158 / 150 / 145
Icc (kA)
6
10
Input power factor (load ≥ 10%)
1.0
Input THDi
@100% load: THDi < 3.0%
@50% load: THDi < 5.0%
@25% load: THDi < 8.0%
Tab. 16.
Rectifier input characteristics
9.4.2. Electrical characteristics (bypass input)
Static bypass specifications
30 kVA
40 kVA
50 kVA
60 kVA
80 kVA
Nominal voltage (3P + N + E)
3 x 380 V / 3 x 400 V / 3 x 415 V
Maximum allowed voltage (Phase-neutral / Phase-Phase)
265 V / 460 V
Technology
Solid state + relays
Activation criterion
Digital Control
Transfer time
Zero
Voltage range
-15 % ~ +12 %
Overload
100% ~ 110% (permanently)
110% ~ 125% (for 60 min.)
125% ~ 150% (for 10 min.)
150% ~ 200% (for 10 s.)
> 200% (immediate)
Transfer time
0
Manual bypass type
Without interruption
Neutral line nominal current
1.7 × In
Frequency
50 / 60 Hz ± 5 Hz (programmable between 0.5 Hz and 5 Hz)
Nominal bypass current (3 x 380 V / 3 x 400 V / 3 x 415 V) (A)
46 / 43 / 42
61 / 58 / 56
76 / 73 / 70
91 / 87 / 83
122 / 115 / 111
Maximum permanent bypass current (3 x 380 V / 3 x 400 V / 3 x
415 V) (A)
50 / 48 / 46
67 / 64 / 61
84 / 79 / 77
100 / 95 / 92
134 / 127 / 122
Tab. 17.
Static bypass characteristics
SLC CUBE4
- UNINTERRUPTIBLE POWER SUPPLY SYSTEM
-
USER MANUAL