69
SALICRU
Nominal power (kVA)
5
7,5
10
15
20
30
40
50
60
80
100
Nominal power (kW)
Depending on the input/output setting and power supply voltage (See chart 9)
Capacity (Ah)
7
12
18
26
Standard charging current (Cx0,2) (A)
1.4
2.4
3.6
5.2
Battery terminal torque
According to battery manufacturer
Fitted in the same UPS cabinet
YES
NO
DIMENSIONS AND WEIGHTS FOR UPS CONFIGURATIONS WITH STANDARD BACK UP TIME
Quantity of cabinets
1 (UPS + batteries)
1 (UPS) / 1 (batteries)
Maximum
dimensions(mm)
(Depth x Width x
Height)
CUBE3+ / CUBE3+ B1
770x450x1100
875x590x1320
850x900x1900
CUBE3+ B / CUBE3+ B B1
875x590x1320
875x870x1320
850x1225x1900
Batteries
-
770x450x1100
1050x650x1320
850x1300x1900
Casters without brake. Equipment / batteries
YES / -
YES / YES
YES / NO
NO / NO
Cabinet weight (kg)
CUBE3+ B1
100
102
105
150
175
-
-
-
-
-
-
CUBE3+ B B1
102
104
107
153
178
-
-
-
-
-
-
CUBE3+
210
212
215
310
400
185
265
290
290
540
550
CUBE3+ B
212
214
217
313
403
190
275
310
310
570
580
External batteries
-
-
-
-
-
510
1020
1020
1020
1655
1690
Tabla 7.
Technical specifications for equipments with (LV) voltages.
9.2.
TECHNICAL SPECIFICATIONS, EQUIPMENTS (HV).
Nominal power (kVA)
7,5
10
15
20
30
40
50
60
80
100
120
160
200
Nominal power (kW)
Depending on the input/output setting and power supply voltage (See chart 9)
INPUT
Nominal voltage
Single phase 220V, 230V or 240V
-
Three phase 3x380V, 3x400V or 3x415V (4 wires: 3 N)
Input voltage range
+ 15% / –20%
Frequency
50 or 60 Hz ±5 %
Total input current distortion
(depending on the quality of input mains)
100 % load: THD-i < 1.5 %
50 % load: THD-i < 2.5 %
10 % load: THD-i < 6.0 %
100 % load: THD-i < 1.0 %
50 % load: THD-i < 2.0 %
10 % load: THD-i < 5.0 %
100 % load: THD-i < 1.5 %
50 % load: THD-i < 2.0 %
10 % load: THD-i < 6.0 %
Current limit
High overload: PFC limit (discharging batteries)
Power factor
0.99 from 10% load
INVERTER
Output nominal voltage
Single phase 220V, 230V or 240V
-
Three phase 3x380V, 3x400V or 3x415V (4 wires: 3 N)
(*) Output power factor
0.9 for three phase/three phase setting. 0.8 for L, M and N settings
0.8
Accuracy
Static: ±1 %. Dynamic: ±2 % (step loads 100-0-100 %)
Output frequency
50 or 60 Hz synchronised ±5 Hz. Free running ±0.05 %
Maximum slew rate
±1 Hz/s
Output wave shape
Sinewave
Total output voltage harmonic distortion
Linear load: THD-v < 0.5 %. Ref. non-linear load (EN-62040-3): THD-v < 1.5 %
Phase shifting
120 ±1 % (balanced load). 120 ±2 % (unbalanced load of 50 % )
Dynamic response time
10 ms. at 98 % of the static value
(**) Permissible overload
125 % for 10 min., >125.. 135 % for 5 min., >135.. 150 % for 1 min., > 150 % for 20 ms.
Permissible crest factor
3.4 to 1
3.2 to 1
2.8 to 1
3.2 to 1
3 to 1
Permissible power factor
0.7 leading to 0.7 lagging
Unbalanced output voltage (100 % unbalanced load)
< 1 %
Current limit
High overload, short-circuit: RMS voltage limit. High current crest factor: Peak voltage limit
Efficiency on battery mode (100% linear load) (%)
94.3
94.5
95.0
95.3
95.9
96.2
96.3
96.4
96.9
96.5
96.4
96.8
96.9
STATIC BYPASS
Type
Solid state
Bypass line
Common. Separate as an option (B)
Nominal voltage
Single phase 220V, 230V or 240V
-
Three phase 3x380V, 3x400V or 3x415V (4 wires: 3 N)
Voltage range
12 % (adjustable b20... +5%) / –15% (adjustable between –25... –5%
Voltage hysteresis
±2 % as regards to bypass voltage range. In a standard equipment is of +10 /–13%
Frequency
50 or 60 Hz
Frequency range
±5 Hz (selectable among 0.5 - 1.0 - 2 and 5.0 Hz)
Frequency hysteresis
1 Hz as regards the frequency range (selectable among 0.2 - 0.5 - 1.0 and 2.0 Hz)
Activation criteria
Controlled by microprocessor
Transference time
Nil, less in Smart Eco-mode < 3ms