8. MAINTENANCE, WARRANTY AND SERVICE
8.1. BATTERY MAINTENANCE
•
Pay attention to all of the safety instructions relating to the
batteries and indicated in chapter 1.2.3 of the EK266*08
manual.
•
The useful life of the batteries depends directly on the am-
bient temperature and other factors, such as the number
of charges and discharges, as well as the depth of these.
Their design lifetime is between 3 and 5 years if the am-
bient temperature to which they are subjected is between
10 and 20ºC. On request, batteries of a different type and/
or design lifetime can be supplied.
•
The
SLC CUBE4
series UPS requires a minimum level of
maintenance. The batteries used in standard models are
sealed lead-acid, valve-regulated and maintenance-free.
The only requirement is to charge the batteries regularly to
extend their life expectancy.
As long as the UPS is connected to the supply network,
whether or not it is in operation, it will keep the batteries
charged and will also provide protection against over-
charging and deep battery discharge.
8.1.1. Notes for installing and replacing the batteries
•
If a connection cable must be replaced, purchase original
materials through our
T.S.S.
or authorised distributors. The
use of unsuitable cables can lead to overheating in the con-
nections that could pose a fire risk.
•
There are permanent dangerous voltages inside the
unit, even without mains supply present, due to its
connection with the batteries, and especially in UPS units
where the electronics and batteries share the same box.
Also take into consideration that the battery circuit is not
isolated from the input voltage, so there is a risk of dis-
charge with dangerous voltages between the battery ter-
minals and the earth terminal, which in turn is connected to
the earth (any metal part of the unit).
Repair and/or maintenance work must be carried out by the
T.S.S.
, except for the replacement of batteries, which can
also be carried out by qualified staff who are familiar with
them. No other person should handle them.
•
Depending on the UPS configuration, certain actions will be
carried out before handling the batteries:
Units with batteries and electronics in the same box.
–
To stop the loads and the unit completely.
–
Disconnect the
SLC CUBE4
from the mains.
–
Open the unit in order to access the inside.
–
Remove the internal battery fuse or fuses.
–
Proceed to replace the batteries, after releasing
their holders.
–
Proceed in the reverse order to leave the unit as it
was at the beginning, including start-up.
UPS with batteries and electronics in separate boxes.
–
To stop the loads and the unit completely.
–
Disconnect the
SLC CUBE4
from the mains.
–
Disconnect the UPS battery module.
–
Open the battery module to access the inside.
–
Remove the internal battery fuse or fuses.
–
Proceed to replace the batteries, after releasing
their holders.
–
Proceed in the reverse order to leave the unit as it
was at the beginning, including start-up.
8.2. WARRANTY CONDITIONS
8.2.1. Warranty terms
On our website, you will find the warranty conditions for the
product you have purchased and you can register it there. It is
recommended to do so as soon as possible in order to include
it in the database of our Technical Service and Support (
T.S.S.
).
Among other advantages, it will streamline any regulatory pro-
cedures for the intervention of the
T.S.S.
in the event of a fault.
8.2.2. Exclusions
Our company will not be bound by the warranty if it notices
that the defect in the product does not exist or was caused by
improper use, negligence, improper installation and/or verifi-
cation, attempts at unauthorised repair or modification, or any
other cause beyond the intended use, or by accident, fire, light-
ning or other hazards. Nor shall it cover any compensation for
damages.
8.3. TECHNICAL SERVICES NETWORK
Information about our national and international Technical Ser-
vice and Support (
T.S.S.
) centres can be found on our website.
Summary of Contents for SLC CUBE4
Page 1: ...30 80 kVA USER MANUAL...
Page 66: ...66 SALICRU...
Page 67: ...67 SLC CUBE4 UNINTERRUPTIBLE POWER SUPPLY SYSTEM USER MANUAL...
Page 68: ...68 SALICRU...
Page 69: ...69 SLC CUBE4 UNINTERRUPTIBLE POWER SUPPLY SYSTEM USER MANUAL...