background image

- 7 -

1.- GENERAL INFORMATION.

1.1.- General description of the UPS.

This UPS is built in a metallic structure, where the electronic power is located in and we have access to it through the frontal door.

The external covers of the equipment can be removed completely in order to guarantee an easy start up from any point in front of

any event.

In the right frontal door, it is located the user interface panel, for controlling and managing the UPS.

Due to the high power rate of the UPS, it doesn’t have any battery string inside; they are located in one or several cabinets.

The cooling system of the equipment is based on a hydraulic system (made of water and glycol) and forced cooling, the air is taken

from the baseboard of the UPS and exhausted through the frontal cooling grids placed in the exchanger stage, and located on the

frontal left side of the equipment.

1.1.1.- UPS applications.

This new UPS has been designed to supply stabilized and filtered voltage to sophisticated electronic devices (particularly to data

centres), which must have a power supply free of voltage and frequency fluctuations. Among them there are: hospitals, police

stations, highway tunnels, broadcasting stations, banks, technical offices, etc.

1.1.2.-  Power  and  back  up  time.

Thanks to its modular configuration, the power rates of this series are between 160 KVA and 300 KVA.

It is not foreseen any internal battery string, so to achieve the wanted back up time is needed the use of additional cabinets them.

1.1.3.- Safety and easy use.

All the controls are properly insulated and disconnected from hazardous voltages.

The control for overloads and overtemperatures guarantee an immediate intervention, in case one of them occurs during its

operation.

Through the frontal panel, the end-user can visualize the status of the UPS and make transference and shutdowns manoeuvres in

an easy way . See chapter 3.

There is the possibility to connect one or more external E.P.O. buttons (not supplied). Thanks to them, in case of fire, it is possible

to control the complete UPS shutdown. See chapter 2.7.4.

The UPS monitoring can be remotely managed in an easy way either through a personal computer with a specific communication

software(optional), or  through a remote panel, optional too, they are essential in case of unattended places. See chapters

1.2.5–1.2.6.

1.2.- Configuration and optional devices.

1.2.1.- Standard configuration.

The standard configuration is to assemble the UPS in only one cabinet, which will have the same dimensions in all the possible

configurations and sizes:

- Six pulses: 160 – 300 kVA

- Twelve pulses: 160 – 300 KVA

- Twelve THD filter: 160 – 300 KVA

Summary of Contents for SLC ELITE MAX Series

Page 1: ...User s and installation manual UNINTERRUPTIBLE POWER SUPPLY SLC ELITE MAX Series from 160 to 300kVA EK449A01...

Page 2: ...2...

Page 3: ...3 SAFETY WARNINGS 6 User s manual installation and start up 4 39...

Page 4: ...3 Operating principle 1 3 1 UPS block diagram 1 3 2 Input power module and output 1 3 3 Control and auxiliary circuits 1 3 4 Batteries 1 3 5 Manual bypass 1 3 6 Frontal panel 2 INSTALLATION STANDARDS...

Page 5: ...ete UPS shutdown 4 8 Emergency Power Off E P O 4 9 Instructions to start up the UPS in ECONOMY mode 4 10 Instructions for transferring to manual bypass in ECONOMY mode 4 12 Instructions for complete U...

Page 6: ...e conformity with the CEE Directives by means of the following harmonised standards EN IEC 62040 1 2 Uninterruptible Power Suppply UPS Part 1 1 General safety requirements for UPS used in accessible a...

Page 7: ...1 1 2 Power and back up time Thanks to its modular configuration the power rates of this series are between 160 KVA and 300 KVA It is not foreseen any internal battery string so to achievethe wanted b...

Page 8: ...e terminal strip M1 The system already has a remote communication card and a slot to place an optional one if it is requested for more information see chapter 2 7 Auxiliary connections of the UPS 1 2...

Page 9: ...ICADOR CONVERTIDOR STEP UP RECTIFIER STEP UP CONVERTER INVERSOR INVERTER INTERRUPTOR EST TICO STATIC SWITCH SALIDA CARGA OUTPUT LOAD CARGADOR DE BATER AS BATTERY CHARGER ARMARIO DE BATER AS BATTERY CA...

Page 10: ...S immediately respectively The communication interface can control a part from the standard relay card an additional one which is optional The auxiliary power supply feds all the PCB s and electronic...

Page 11: ...from high humidity and heat sources from 5 to 40 C non condensing humidity lower than 95 When the battery cabinet isalsosupplied it is amust to assure that the period timebetweenthe last recharge oft...

Page 12: ...SIONS D x W x K 160 720 200 720 250 870 300 870 DIMENSIONS D x W x K 160 780 200 780 250 990 300 990 SIX PHASE VERSION 800 x 1240 x 1800 POWER kVA WEIGHT Kg THREE PHASE VERSION 800 x 1240 x 1800 SIX P...

Page 13: ...l the cables enter through the bottom window as it is showed in the figure 2 4 side view 2 5 Location features The UPS installation site must be clean and with a contamination degree of 2 IEC also it...

Page 14: ...urrent higher than 500mA delayed and ready to support loads with DC component RCD type B Diagram 2 6a Bypassestandar Standard bypass Carga Load Red principal Standardmains BYPASSDE MANTENIMIENTO MAINT...

Page 15: ...RNALLY TO THE UPS AT THE MAINS INPUT A CONTACTOR A PART FROM THE PROTECTION CIRCUIT BREAKER IN ORDER TO PROTECT AGAINST BACKFEED VOLTAGES IN ACCORD ANCE WITH THE TABLE 2 6 AND THE FOLLOWING CIRCUIT DI...

Page 16: ...ed in the internal side of the UPS door KVA Their features must inaccordancewith the IEC standards or with the local regulations forcircuit breakers withcharacteristic C Theconnections must done in ac...

Page 17: ...d This card allows the connection of the UPS with several external devices The card has a terminal strip with dry contacts M1 where it can connected the following a remote panel chapter 2 7 2 acoustic...

Page 18: ...through the key 5 LED description 1 UPS ON green led Turned ON means the correct operation of the UPS turned OFF means that thereis oneormore alarms intheinverterstage acousticalarmon 2 ON BATTERY yel...

Page 19: ...n and using see its corresponding manual 2 7 4 Remote E P O button Pay special attention to the connection of the buttons for the E P O function emergency power off That connection is based on several...

Page 20: ...ection Theinput earthcablemust be connected tothe earth stud of the UPS That cablemust be thefirstone to be connected It isbetter to place an anti rust between the earth stud and the contact board to...

Page 21: ...er each one The screens are organised in 7 multilevel menus which can be selected by using the keys placed under the LCD panel In the left side of the LCD there are two LEDs one is green labelled as N...

Page 22: ...ed In this moment the user can decide to continue with the guided procedure by following the proposed visual indications till the system is completed started up or to execute different operations thro...

Page 23: ...ING CORRECT MAINS OUT OF RANGE The input mains is present but the voltage is out of the specified range CORRECT BYPASS LINE OUT OF RANGE The bypass line mains is present but the voltage is out of the...

Page 24: ...are still supplied STA TIC SW ITCH BLOCKED A fter 3 frustrated autom atic attem pts from bypass to inverter the U PS blocks the static sw itch in the bypass line position BA TTERY FAU LT BA TTERY TES...

Page 25: ...F 3 3 LOAD TRANSFERRED TO INVERTER With this message when the key ENTER is pressed the load is transferred from bypass to inverter 3 4 LOAD TRANSFERRED TO BYPASS With this message when the key ENTER i...

Page 26: ...e log list by pressing MENU the LCD panel will come back to the MAIN MENU To delete all the events and alarms the submenu DELETE DATA LOGGER must be selected and after that press ENTER After 3 minutes...

Page 27: ...unning and uses the batteries to fed the loads because there is a mains failure This operating mode guarantees the non interrupted power supply of the loads till the end of autonomy 4 2 Power switches...

Page 28: ...res If this menu is selected the following operations can be done UPS start up UPS shutdown Manual bypass activation I1 INPUT MAINS SWITCH I4 OUTPUT UPS SWITCH I2 INPUT BYPASS SWITCH I3 MANUAL BYPASS...

Page 29: ...are checked we will proceed to start up the system as follows 1 Turn on the BYPASS MAINS SWITCH RESERVE I2 The LCD panel and the control of the UPS starts to run to disable the guided procedures which...

Page 30: ...lect Inverter OFF and press ENTER By doing it the inverter is shutdown and the non interrupted power supply to the loads is not guaranteed 3 Turn on the MANUAL BYPASS I3 Remove the padlock or any othe...

Page 31: ...nverter By means of the menu 3 UPS COMMANDS select the Inverter ON and press ENTER 6 Check the transfer from bypass line to inverter Wait for 30 seconds after that the static switch will do the automa...

Page 32: ...d BE SURE THAT THE PHASE ROTATION OF THE INPUT AND BYPASS MAINS ARE CORRECT See fig 4 3 to know the meaning of each switch Once the above steps are checked the system can be started up in Economy mode...

Page 33: ...perpart of theUPS 4 10 Instructions for transferring to manual bypass in ECONOMY mode If for any maintenance or other reasons the power supply of the critical loads must be done from the mains directl...

Page 34: ...seconds after that the rectifier will start up with a walk in time in order to pre charge the internal capacitors avoiding any overcurrent at the input mains The LCD will show the message INVERTER SH...

Page 35: ...educe the DC output voltage of the converter till the threshold when the battery discharge starts if it is correct at 2 V cell it will start to supply current Otherwise there will be displayed an alar...

Page 36: ...allows checking all the operations during the installation and maintenance periods of each equipment Thegeneral manual bypassallowsisolating the complete systemwithno interruption inthefeeding of thel...

Page 37: ...ON INVERTER SHUTDOWN Initial start up Start up the inverter Permanent overload Check the output OVERLOAD Continuous overload at the UPS output Check the load at the UPS output and the start up the inv...

Page 38: ...ust be done by the UPS dealer company or by a specialised company recommended by the dealer company 7 1 Yearly maintenance or half yearly in some critical cases The yearly maintenance has the followin...

Page 39: ...39...

Page 40: ...40 08460Palautordera Tel 3493 8482400 sat salicru com salicru com...

Reviews: