- 19 -
8.- EQUIPMENT START UP AND SHUTDOWN.
8.1.- Controls before starting up the unit.
• Carefully check that all the connections have been done correctly by respecting the labelling of the equipment and the
instructions of the chapter 7.
• When the input plug
(C1)
is connected to an electric AC mains outlet, the
(LCD)
panel lights and the fans and battery charger start.
•
Follow the established order for start up and shutdown the
UPS
.
8.2.- UPS start up.
•
Before using the
UPS
for the first time or after a longer shutdown of more than 6 months, it is necessary to charge the
batteries during as minimum 4 hours. Do not continue with the start up procedure until having lapsed this time.
• Press during at least 3 seconds the
(ON/OFF)
key of the control panel, the led
( )
will light. The system will carry out an
internal test and once it is concluded, the inverter of the
UPS
will start up and supply output voltage.
Any anomaly in the mains will be absorbed by the equipment.
During the start up procedure the
(LCD)
panel shows the message «READY ON» and when the equipment is supplying output
voltage the led
(
)
lights and the
(LCD)
panel shows the message «LINE MODE».
• Start the critical loads to be supplied.
8.3.- Daily UPS shutdown, «inverter» shutdown.
• Shutdown the loads and press on the
(ON/OFF)
key during as minimum 3 seconds, the inverter will be shutdown.
• The
(LCD)
panel will show «SHUTDOWN » during some seconds, after that the
(LCD)
panel will only be lighted and with the
fans and battery charger will still be ON.
8.4.- Cold start, without commercial mains.
• The cold start up procedure (without commercial mains), is the same as the normal one less for the mains absence, the
optical indications of the control panel, the acoustic ones and the indications of the
(LCD)
panel «BATTERY MODE» .
•
Due to the equipment is blocked by software against an accidental start up during transport, it is not possible to use the
cold start function to the reception of this.
Connect it to the mains and start it up for the first time according to the section 8.2.
Summary of Contents for SLC Link Series
Page 1: ...EK708A01 SLC LINK Service Manual...
Page 64: ...63...
Page 65: ...08460 Palautordera Tel 34 93 848 24 00 sat salicru com salicru com...
Page 99: ...34...
Page 138: ...73...
Page 139: ...74...
Page 140: ...75...
Page 141: ...08460 Palautordera Tel 34 93 848 24 00 sat salicru com salicru com...