- 20 -
8.5.- Complete UPS shutdown.
• Shutdown the loads and press the
(ON/OFF)
key during as minimum 3 seconds, the inverter will be shutdown.
• The
(LCD)
panel will show «SHUTDOWN» during some seconds, after them the
(LCD)
panel will only be lighted and with the
fans and battery charger will still be ON.
• Disconnect the input plug
(C1)
from electric AC mains outlet. The equipment will be totally shutdown.
8.6.- UPS blocked by the keypad, advisable for reshipments to factory.
• Connect the
UPS
to the mains.
• Without starting it up through the
(ON/OFF)
key of the control panel, keep pressed the key
(FUNC)
and then pulse at the
same time 3 times the key
(ENT/STATUS)
in 5 seconds until a beep of the acoustic alarm is listened.
• Leave all the keys.
• Disconnect the input plug
(C1)
from the electric mains outlet.
• Wait until the
(LCD)
panel is switched off.
• Press the
(ON/OFF)
key during as minimum 3 seconds and check that it is not supplying output voltage. The screen lights but
the equipment neither starts up, nor supplies output voltage.
• If the equipment doesn’t start up, end of the process. Otherwise repeat the complete sequence from the beginning.
• To unblock the equipment, connect it to the mains and do the first start up procedure. The cold start up is unblocked.
8.7.- Bypass types definition (Automatic and Manual).
• Automatic Bypass. It is referred to the automatic switch of the internal Bypass line of the
UPS
.
If the parameter option «HE MODE ON» is activated, the
UPS
is like an «OFF-LINE».It means that is supplying permanently
output voltage through the Automatic Bypass «BYPASS MODE» and it transfers the load to the inverter when the mains is
incorrect.
The
UPS
transfers to Automatic Bypass for overload or internal faults.
• Manual Bypass. It is referred to the option of the selectable parameter. By choosing «BYPASS ENABLE», it is forced the
transference of the loads to the own Automatic Bypass of the
UPS
, not being able to return automatically back meanwhile
this option is selected.
Summary of Contents for SLC Link Series
Page 1: ...EK708A01 SLC LINK Service Manual...
Page 64: ...63...
Page 65: ...08460 Palautordera Tel 34 93 848 24 00 sat salicru com salicru com...
Page 99: ...34...
Page 138: ...73...
Page 139: ...74...
Page 140: ...75...
Page 141: ...08460 Palautordera Tel 34 93 848 24 00 sat salicru com salicru com...