- 21 -
7.9.4.4.- Software installation.
• Installation on Windows platforms.
Insert the CD-Rom into the corresponding unit of the PC.
The software installation will boot automatically, but if this property is not activated, just access the unit where the CD is
inserted and execute the file «Setup.exe».
Follow the steps indicated by the software itself, answering the questions that will appear on the screen.
It is better to perform the installations as administrator user of the system or with equivalent permits.
7.10.- Optional communication cards or electronic units and integrated in the UPS case (C16).
• As options the
UPS
has two communication cards or electronic units (5-dry contact AS/400 and management and supervi-
sion SNMP/WEB card) that can be implemented at the factory or later on the equipment.
You can place any of them indistinctly, but not both simultaneously.
7.10.1.- Fitting a communication card or electronic unit in the equipment (C16).
• Indistinctly that it is the 5-dry contact AS/400 card or the management and supervision SNMP/WEB card, remove the screws,
which are fixing the cover
(Ti)
, take out and keep it in sure place.
• Introduce the requested card in the guides that are visible once the cover
(Ti)
has been removed. Enter it until the bottom and
place back the screws that will fix the cover
(Ti)
integrated with the own card. It can be proceeded to the connection.
7.10.1.1.- SUB-D9 connector of the communication card or electronic unit, 5-dry contact AS/400.
•
The communication lines (interface) constitute a safety circuit of very low voltage. To preserve this quality, they should
be installed separated from other lines with dangerous voltages (like distribution lines of energy).
• This card is enabling the communications between the UPS and the environment, the same as the optocoupler interface and
simultaneously with this card, considering that the given alarms are through dry contacts and some of them are different from
the standard optocoupler interface. These alarms are given through SUB-D9 male connector like the figure 4.
The same connector has a «Shutdown» input (between pins 3 and 4) that allows the UPS to be able to be turned off when
there is a voltage of 12 V DC for more than 5 sec., as long as there is no mains.
In the table 3 is showed the pin-out of the port and their functions. Do not apply higher values than 120V AC 1A or 24V DC1A to these pins.
Table 3. Pin-out of the SUB-D9 connector, 5-Dry contact AS/400.
Pin Nr.
Functions.
Jumper Nr. Jumper position.
1
UPS failure.
JP2
NC
2
General alarm.
JP5
NC
3
Shutdown ground.
-
-
4
+ Shutdown (12V DC> 5 sec.).
-
-
5
Common.
-
-
6
Bypass.
JP3
NC
7
Low battery (End of back up time).
JP1
NC
8
x
x
x
9
Mains failure.
JP4
NC
Summary of Contents for SLC Link Series
Page 1: ...EK708A01 SLC LINK Service Manual...
Page 64: ...63...
Page 65: ...08460 Palautordera Tel 34 93 848 24 00 sat salicru com salicru com...
Page 99: ...34...
Page 138: ...73...
Page 139: ...74...
Page 140: ...75...
Page 141: ...08460 Palautordera Tel 34 93 848 24 00 sat salicru com salicru com...