- 29 -
10.5.- Measures, parameters and options lists.
LCD message.
Message description.
O/P VOLT= ***.* V
AC output voltage.
O/P FREQ= **.* HZ
Output frequency.
I/P VOLT= ***.* V
AC input voltage.
I/P FREQ= **.* HZ
Input frequency.
BAT VOLT= **.* V
Battery voltage.
O/P LOAD= ** %
Connected Load in % of the nominal load.
O/P WATT= ***** W
Active output power.
O/P VA= ***** VA
Apparent output power.
O/P CUR= ***.* A
Output current.
TEMPERATURE= ** C
Ambient temperature.
Rating = ***** VA
Nominal apparent power of the equipment.
CPU VER **.*
CPU version.
LCD m essage
Parameter options
Factory selection
Description
I/P FREQ SET
FREQ TOL.= +/- 2%
FREQ TOL.= +/- 5%
FREQ TOL.= +/- 7%
FREQ TOL.=+/-5%
Input frequency range where the
UPS
is
synchronised.
I/P BYPAS S S ET
I/P TOL=+/- 10%
I/P TOL=+10/-15%
I/P TOL=+15/-20%
I/P TOL=+10/-15%
Input voltage range where the bypass line
voltage is acceptable.
FREE RUN S ET
FREE R UN ON
FREE R UN OFF
FREE RUN ON
UPS
on free running operation
(no synchronisation).
S ubm enu FR EE RUN SET
with the option ON
(*)
.
BYPAS S ENABLE
BYPAS S DISABLE
BYPASS DISABLE
Allows to transfer the load to bypass although
the input and output are not synchronised.
HE MODE S ET
HE MODE ON
HE MODE OFF
HE M ODE OFF
UPS
on high efficiency operating (OFF-LINE).
MANUAL BYPAS S
BYPAS S ENABLE
BYPAS S DISABLE
BYPASS DISABLE
With the selection «BYPASS ENABLE» the
UPS
is forced to m anual bypass perm anently
(*)
.
BATTERY TES T
TES T ?
Force according to
defined criterion (**).
Force the
UPS
to do a m anual battery test.
It requires confirm ation with key ENTER.
S ILENCE SET
S ILENCE ON
S ILENCE OFF
SILENCE OFF
Activate o deactivate the silence function.
S ITE FAULT S ET
DETECT ENABLE DETEC T
DISABLE
DETECT ENABLE
S elect «DETECT DIS ABLE» in installation
without neutral.
LANGUAGE
English
Portuguese
Français-French
Español-S panish
C atalà-Catalán
Español-Spanish
LCD panel language.
GENER ATOR
ENABLE
DISABLE
ENABLE
To be selected when the
UPS
is supplied by a
generator
(***)
.
R S232 CONTROL
ENABLE
DISABLE
ENABLE
The RS -232 com m unications are activated or
deactivated.
BAT C ABINET SET
EXTERN PAC K= 0
(a)
EXTERN PACK= 1 to 2
(b)
EXTERN PACK= 1 to 5
EXTERN PACK: 0
Num ber of external battery packs. «0» m eans
internal batteries.
Table 4. Measures list.
Table 5. Parameter, options and factory selections list.
Summary of Contents for SLC Link Series
Page 1: ...EK708A01 SLC LINK Service Manual...
Page 64: ...63...
Page 65: ...08460 Palautordera Tel 34 93 848 24 00 sat salicru com salicru com...
Page 99: ...34...
Page 138: ...73...
Page 139: ...74...
Page 140: ...75...
Page 141: ...08460 Palautordera Tel 34 93 848 24 00 sat salicru com salicru com...