- 33 -
Table 8. Particular specifications.
(*)
All the rack mounted equipments with standard back up time, the batteries are provded in an additional rack with identical dimensions.
(**)
The extended back up time on an equipment is achieved with the connection of «n» battery modules with variable capacity depending on the model.
(***)
Some values of depth and width dimensions are between parenthesis.
The first value of the depth means the depth of the metal case itself and the second one is the maximum depth of the parts located in the posterior sides.
With the sum of both values we have the total depth.
About the width in rack-mounted models, the first value means the metal case width only and the second one are the side handles. With the sum of
both values we have the total width of the 19" rack (428+54,6 = 482,6).
25%
50%
75%
100%
SLC-4000 LINK
4000 / 2800
120
140
160
184 ..264
39
(640 + 50) x 260 x 570
86
SLC-4000 LINK-T
4000 / 2800
120
140
160
184 ..264
39
(640 + 50) x 260 x 700
123
SLC-4000 LINK R (*)
4000 / 2800
120
140
160
184 ..264
39
(645 + 100) x (428 + 54,6) x 130
20
SLC-5000 LINK
5000 / 3500
120
140
160
184 ..264
28
(640 + 50) x 260 x 570
86
SLC-5000 LINK-T
5000 / 3500
120
140
160
184 ..264
28
(640 + 50) x 260 x 700
123
SLC-5000 LINK R (*)
5000 / 3500
120
140
160
184 ..264
28
(645 + 100) x (428 + 54,6) x 130
20
SLC-6000 LINK
6000 / 4200
120
140
160
184 ..264
20
(640 + 50) x 260 x 570
86
SLC-6000 LINK -T
6000 / 4200
120
140
160
184 ..264
20
(640 + 50) x 260 x 700
123
SLC-6000 LINK R (*)
6000 / 4200
120
140
160
184 ..264
20
(645 + 100) x (428 + 54,6) x 130
20
Battery mod. 4-6
-
-
-
-
-
(**)
(590 + 100) x 260 x 570
(**)
Battery mod. 4-6 R
-
-
-
-
(**)
(630 + 100) x (428 + 54,6) x 130
(**)
SLC-8000 LINK
8000 / 5600
120
140
160
184 ..264
15
(740 + 50) x 260 x 715
112
SLC-8000 LINK-T
8000 / 5600
120
140
160
184 ..264
15
(740 + 50) x 345 x 715
180
SLC-8000 LINK/3
8000 / 5600
3x208
3x242
3x277
3x319..457
15
(740 + 50) x 260 x 715
112
SLC-8000 LINK/3-T
8000 / 5600
3x208
3x242
3x277
3x319..457
15
(740 + 50) x 345 x 715
180
SLC-10000 LINK
10000 / 7000
120
140
160
184 ..264
15
(740 + 50) x 260 x 715
112
SLC-10000 LINK-T
10000 / 7000
120
140
160
184 ..264
15
(740 + 50) x 345 x 715
180
SLC-10000 LINK/3
10000 / 7000
3x208
3x242
3x277
3x319..457
15
(740 + 50) x 260 x 715
112
SLC-10000 LINK/3-T
10000 / 7000
3x208
3x242
3x277
3x319..457
15
(740 + 50) x 345 x 715
180
SLC-12000 LINK
12000 / 8400
120
140
160
184 ..264
22
(740 + 50) x 345 x 880
182
SLC-12000 LINK-T
12000 / 8400
120
140
160
184 ..264
22
(740 + 50) x 345 x 880
242
SLC-12000 LINK/3
12000 / 8400
3x208
3x242
3x277
3x319..457
22
(740 + 50) x 345 x 880
182
SLC-12000 LINK/3-T
12000 / 8400
3x208
3x242
3x277
3x319..457
22
(740 + 50) x 345 x 880
242
SLC-15000 LINK
15000 / 10500
120
140
160
184 ..264
18
(740 + 123) x 345 x 905
175
Battery mod. 8-10
-
-
-
-
-
(**)
(740 + 50) x 345 x 715
(**)
Battery mod. 12
-
-
-
-
(**)
(740 + 50) x 345 x 880
(**)
Input voltage range (V) with load, for mains:
208/220/230/240V or 3x360/3x380/3x400/3x415V.
Weight
(kg).
Model
Back up time at
half load (min.).
(***) Max. dimensions (mm)
Depth x Width x Height.
Power
(VA / W).
Summary of Contents for SLC Link Series
Page 1: ...EK708A01 SLC LINK Service Manual...
Page 64: ...63...
Page 65: ...08460 Palautordera Tel 34 93 848 24 00 sat salicru com salicru com...
Page 99: ...34...
Page 138: ...73...
Page 139: ...74...
Page 140: ...75...
Page 141: ...08460 Palautordera Tel 34 93 848 24 00 sat salicru com salicru com...