5

SALICRU

• 

If 

the instructions are not in total or partial and in 

special referred to the safety, do not carry on with 

the installation or commissioning tasks

, because there 

could be a 

risk on your safety or on the other/s persons,

 

being able to make 

serious injuries even the death

, also it 

can 

cause damages to the equipment and/or to the loads 

and installation

.

• 

The local electrical regulations and the different re-

strictions of the client's site, they can invalidate some 

recommendations included in the manuals. When discrepan-

cies exist, the user has to comply the local regulations.

• 

The equipments provided with power cord with plug 

and outlets, can be connected and used by personnel 

without any kind of experience.
The equipments with power blocks have 

to be installed by 

qualified personnel

 and it can be used by personnel with 

not specific training, just with only help of this manual.
A person is defined as 

qualified

, if it has experience of as-

sembling, commissioning and perfect control operating of 

the equipment, if he has the requirements to do the job and 

if has read and understand all the things described in this 

manual, in particular the safety indications. Such preparation 

is considered only valid if it is certified by our 

S.T.S.

.

• 

Place the equipment the closest to the power supply and 

loads to be supplied, leaving an easy access if it were needed 

an urgent disconnection.
In the hardwired equipments and due to the impossibility of 

fast disconnection, a diconnection device (switch) with easy 

access and close to the equipment will be installed.

• 

Warning labels should be placed on all primary power 

switches installed in places away from the equipment to alert 

the electrical maintenance personnel of the presence of a 

UPS in the circuit 
The label will bear the following text or an equivalent one:

Before working in this circuit.

• 

Isolate the Uninterruptible Power System (UPS).

• 

Check the voltage between all terminals including the 

protective earth.

Risk of voltage feedback from UPS.

1.2.3.1.  General safety warnings.

• 

All connections and disconnections of the cables from the 

equipment, including the control ones, will be done with no 

power supply and the switches on rest, position «O» or «Off».

• 

Shutdown the equipment completely by switching «Off» the 

button of the control panel first. Next disconnect the cable 

from the wall outlet for equipments up to standard 3 kVA or by 

switching «Off» the input circuit breaker of the installation and 

disconnect the power supply cables in models of the 3 kVA B1 

or higher power rate.

 The indiscriminate manoeuvring of the switches may 

involve production losses and/or equipment dam-

ages. Consult the documentation before doing any action 

• 

Pay special attention to the labelling of the equipment 

that warns about the «Electrical shock hazard». Inside 

the equipment there are dangerous voltages, never open the 

enclosure, the access has to be done by qualified staff. In 

case of maintenance or fault, consult to the closest (

S.T.S.

).

• 

Cross cable sections used to supply the equipment and loads, 

will be according to the nominal current stated in the nameplate 

label of the equipment, and respecting the Low Voltage Electro-

technical Regulations or standards of the country.
Use approved cables only

• 

Protection Earth cable of the UPS drives the leakage 

current of the load devices. An isolated earth cable has 

to be installed as part of the circuit that supplies the equip-

ment. Cross cable section and its features will be same as 

the power supply cables, but with green colour with or without 

the yellow strip.
All outlets of the UPS has an earth bonding, duly connected 

and those equipments with power blocks there is an exclusive 

terminal for the load earth connection. When an outgoing dis-

tribution is done, i.e power strips, it is essential that they have 

an earth terminal connected to each one of them.
It is essential that the cables that supplies the loads have the 

earth connection cable. 

The protection earth must be connected to the frame 

or metallic chassis of any electrical equipment (in our 

case to the UPS, battery cabinet or case and loads), assuring 

that it is done before connecting the input voltage.
Check the quality and availability of the earth, it has to be 

between the defined parameters by the local or national 

regulations.

• 

For the smallest devices (the ones connected with the fore-

seen power cord with plug), the user has to check the wall 

outlet corresponds with the type of supplied plug, with earth 

duly installed and connected to the local protection earth.

• 

During the normal UPS operation, in equipments up to 

3kVA the power cord cable can't be disconnected 

from wall outlet, because the protection earth of the own UPS 

would be disconnected and also the earth from the loads 

connected to the output.
For this reason, the general protection earth cable of the 

building or switchgear panel that supplies the UPS will not 

be disconnected.

• 

In small equipments (the ones connected with the foreseen 

power cord with plug), check that the sum of the leakage currents 

of the UPS and connected load/s do not exceed over 3,5mA.

• 

The installation will have input protections sized to the cur-

rents of the equipment and stated in the nameplate label 

(RCD devices type B and circuit breakers with C character-

istic or any other equivalent one).
For equipments with three phase input, and connected to 

an IT distribution system, the protection will be four poles in 

order to break the three phases and neutral in the same ma-

noeuvring.
Overload conditions are considered as a nonpermanent an 

exceptional operating mode, so these currents will not be 

kept in mind when sizing the protections.

• 

Do not overload the UPS by connecting loads with inrush 
consumptions at its output, like laser printers.

• 

For those installations with redundant equipments or sepa-

rate Bypass line, there will only be a common RCD of 300 to 

500 mA at the head of the installation for both lines.

• 

Output protection will be done with a circuit breaker of C char-

acteristic or an equivalent one.
It is recommended to distribute the output power, into four 

lines as minimum. Each one of them will have a protection 

circuit breaker sized to the quarter of the nominal power. 

This kind of outgoing distributions will allow that any fault in 

any device connected to the equipment, that makes a short-

circuit, will affect to the line with the faulty device only. An 

uninterruptible power supply will be guaranteed to the rest of 

connected loads, due to the protection tripping of the affected 

line by the short-circuit only.

Summary of Contents for SLC TWIN PRO Series

Page 1: ...PS LIGHTING FLOW DIMMER STABILIZERS ILUEST SWITCH MODE POWER SUPPLY STATIC INVERTERS PHOTOVOLTAIC INVERTERS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS UPSSLCTWINPROseries 4 to 20 kVA UNINTERRUPTI...

Page 2: ......

Page 3: ...ing 5 1 Commissioning 5 1 1 Controls before commissioning 5 2 Start up and shutdown of the UPS 5 2 1 Start up of the UPS with mains present 5 2 2 Start up of the UPS without mains 5 2 3 UPS shutdown w...

Page 4: ...structions for safety of the things To not respect such instructions can damage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instru...

Page 5: ...chnical Regulations or standards of the country Use approved cables only Protection Earth cable of the UPS drives the leakage current of the load devices An isolated earth cable has to be installed as...

Page 6: ...r cause can make an electrical discharge of high voltage and it is restricted to qualified staff only Do not open the equipment A part from the implicit stated risks any action that make the modificat...

Page 7: ...hem Do not modify its length In those equipments requested without batteries their ac quisition installation and connection of themselves will be done by the end user and under his responsibility Data...

Page 8: ...ive EMC In accordance with the specifications of the harmonized stand ards Standards as reference EN IEC 62040 1 Uninterruptible power supply UPS Part 1 1 General and safety requirements for UPS s use...

Page 9: ...due to the constant evolution of the product some discrepancies or small contradictions can arise In front of any doubt the labelling of the equipment will always prevail i Figures regarding its main...

Page 10: ...USB Protection cover for external batteries IEC output connectors Protection cover for manual bypass switch maintenance and output Protection cover for power blocks USB RS 232 EPO Protection cover for...

Page 11: ...11 SALICRU Battery switch Protection cover for power blocks Batteries module for models 10 kVA Batteries module for models up to 10 kVA Battery switch Power blocks Fig 3 Rear view batteries module...

Page 12: ...ews and electrical cables Batteries owned by the client will be installed out from the case or cabinet of the UPS Under request it is possible to supply the acces sories screws and electrical cables n...

Page 13: ...user s installation wiring is achieved as well as low input current distortion so mains pollution is decreased Great adaptability to the worst conditions of the input mains Wide margins of the input v...

Page 14: ...tor The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of controlling and management at the manager system dis posal This facili...

Page 15: ...es type B for RCD devices and C characteristic for circuit breakers For the output load feeding C characteristic for circuit breaker Regarding the size they will be as minimum to the cur rents stated...

Page 16: ...any start it up according to the instructions described in this manual and charge them for 2 hours from floating level In parallel systems it is not needed to make the connection among the equipments...

Page 17: ...all ends of the cables connected to the power blocks input output and by pass Check the correct torque in the screws of the power blocks In installations with only one UPS the Jumper cable as bridge...

Page 18: ...is done through the terminals of the own UPS MC coil out and MC coil in R N R S T N R N U N 1 3 2 SAI Backfeed protection connection in TWIN 3 PRO 10 kVA Backfeed protection signal Backfeed protectio...

Page 19: ...wn in any of the machines connected to the device causing a short circuit it will affect to no more than the line that is faulty The rest of the connected loads will have their continuity as sured due...

Page 20: ...of each equipment with its external battery cabinet s has to be done like if they were single units completely separate from the rest ones Each battery module is independent for each equip ment It is...

Page 21: ...tput static bypass this last one for TWIN 3 PRO 10 kVA models only also a manual bypass with mechanical lock see figures 12 and 13 This switchgear panel allows isolating only one equipment from the sy...

Page 22: ...oltage circuit of safety To preserve the quality it has to be installed separate from other lines that have dangerous voltages energy distribution line UPS has a dry contact card for the relays interf...

Page 23: ...imum before using the UPS for first time For models with single phase input TWIN PRO or three phase TWIN 3 PRO up to 10 kVA It will be necessary to supply power supply voltage to the equipment and tur...

Page 24: ...attery switch is in position On models B0 and B1 Turn the input M1 and bypass M2 circuit breakers to On Switch M2 is only available in models TWIN 3 PRO 10 kVA In equipments with single phase input TW...

Page 25: ...will transfer to Bypass mode Put all the equipments on manual bypass To do it re move the cover from manual bypass switch which is located at the back of each equipment and turn all the switches to p...

Page 26: ...he UPSs have to be set contact with the S T S Press over the shutdown key in any UPS for more than 3 seconds and each one will be shutdown supplying output voltage through the bypass Turn On the outpu...

Page 27: ...ot be fed Turn the manual bypass switch of the panel to Off UPS and put the mechanical lock To avoid wrong manoeuvring the mechanical lock has to be fit otherwise the equipment and loads are exposed t...

Page 28: ...g Press the key for 1 sec as minimum to validate the modified option and change the settings Table 6 Functionality of the buttons or keypad of the control panel The UPS has a control panel with the fo...

Page 29: ...TWIN Blue 72 Warning On maintain Bypass UPS only 8 20 kVA TWIN 3 Blue Code Condition Description Color LCD 81 Fault Heatsink over temperature Red 82 Alarm Ambient over temperature UPS only 4 10 kVA TW...

Page 30: ...ad level connected to the UPS UPS power supply information three phase input UPS output information Equipment Battery information Fig 18 Main screen of the equipment with three phase input All the scr...

Page 31: ...supply fails due to fault or wrong the equipment will transfer to Battery mode to feed the load s properly Fig 24 Frequency converter mode screen This function can be activated through the settings of...

Page 32: ...ucture of the main menu includes six submenus UPS status Event log Measurement Control Identification Setting With password only and by the S T S 6 3 2 UPS status submenu When pressing the key for les...

Page 33: ...ucture of UPS status menu Structure of main menu Press 1 sec Fig 31 UPS status screen Press 1 sec Press o 1 sec Structure of Data logger submenu Structure of main menu Press 1 sec Fig 32 Event logger...

Page 34: ...rd only Fig 34 Control submenu screens 6 3 5 Control submenu When pressing the key the key for less than 1 sec from this Control submenu it is accessed to the control structure see figure 34 Shutdown...

Page 35: ...ndard configuration from factory 6 4 1 Operating on ECO mode 6 4 1 1 Short description of the ECO mode ECO mode function allows supplying the load s from mains directly through the internal filters on...

Page 36: ...en used for long time In hot areas battery has to be charged every 2 months The charging time has to be 12 hours as minimum Under normal conditions the battery lifetime is from 3 to 5 years 25 C In ca...

Page 37: ...the UPS cooling and the ambient temperature of the room NTC abnormal UPS internal fault Consult with the S T S Communication cable male disconnected Para cable Male Loss Alarm code E3 Parallel bus ca...

Page 38: ...oltage Inv Under Voltage Alarm code 33 UPS internal fault Consult with the S T S Inverter Softstart Failed Inv Softstart Fail Alarm code E34 UPS internal fault Consult with the S T S Negative Power Fa...

Page 39: ...7 3 1 Covered product UPS SLC TWIN PRO series 7 3 2 Warranty terms This product is guaranteed against any parts and or labour defect for 12 months period from its commissioning by our company staff o...

Page 40: ...age THD with non linear load 5 Output voltage recovering time 100 ms IEC 62040 3 70 ms IEC 62040 3 60 ms IEC 62040 3 Transient response of the output voltage with load fluctuation of 0 100 0 9 7 7 Tra...

Page 41: ...elation to the working height 8 2 Glossary AC It is nominated as alternating current abbreviation in Spanish CA and in English AC to the electrical current in which the magnitude and direction varies...

Page 42: ...rcuit when it over comes the maximum set values On Line mode Regarding to an equipment it is on line when it is connected to the system and it is in operation and usually has its power supply turned o...

Page 43: ...43 SALICRU...

Page 44: ...NCIA VALLADOLID ZARAGOZA BRANCHES AND SERVICES AND TECHNICAL SUPPORT S T S CHINA FRANCIA HUNGR A MARRUECOS M XICO PORTUGAL REINO UNIDO SINGAPUR SUBSIDIARIES ALEMANIA ARABIA SAUD ARGELIA ARGENTINA B LG...

Reviews: