background image

16

SALICRU

5.2.3.  Connection to B1 external batteries (backup extension).

 

Failure to comply with the instructions in this sec-

tion and the EK266*08 safety instructions carries a 

high risk of electric shock and even death.

 

All standard UPSs incorporate the batteries in the same box as 

the device, except the B1 models. Battery protection is by means 

of internal fuses and is not accessible to the user.

The accumulator modules also have internal battery protections 

by means of fuses that are not accessible to the user.

 

NECESSARY ADJUSTMENTS WHEN ADDING BAT-

TERY MODULES TO B1 MODELS.

B1 models have factory default settings for connection to a 

single battery module.

Whether battery modules are added to an already available de-

vice or if the acquired device has more than one module, it is 

necessary to change the parameter "12" to the corresponding 

value. 

Section 7.4.2.1 of this document indicates the steps to follow to 

adjust this setting and that of the load current.

 

IMPORTANT FOR SAFETY: If you install batteries on your 

own, you must provide the battery pack with bipolar 

magnetothermal protection or sectional fuses of the caliber 

indicated in Tab. 2.

Models

Batteries

(U 

element

 x No.) = 

rated

 / U 

float

Protection features 

Voltage

DC (V)

Current

(A)

SLC-1000- TWIN PRO2 A B1

(12 V x 3 ) =

36 V / 40.95 V

125

40

SLC-2000- TWIN PRO2 A B1

(12 V x 4 ) = 

48 V / 54.6 V

63

SLC-3000- TWIN PRO2 A B1

(12 V x 6 ) = 

72 V / 81.9 V

Tab. 2. 

Protection features between UPS and battery module.

 

Before starting the connection process between 

battery module or modules and device, check that 

the device and loads are set to ‘Off.’

 

The connection of external batteries to the device is carried out 

by means of a polarised connector on B1 models. 

 

To connect the device to the battery module, use the hose sup-

plied with the latter and connect it between both units using the 

connectors.

When more than one battery module is supplied for the same 

device, the connection between modules should be made 

through the hose supplied with the second battery module.

Fig. 11 shows an example of the connection of an SLC-TWIN 

PRO2 A B1 with ‘N’ battery modules. Except for the rear view of 

the model, it is applicable to the entire range indicated in this 

manual. Connect the available modules according to each case.

 

If for any reason the user manufactures the battery connection 

hose, the following cable colour conventions must be observed: 

red for positive, black for negative, as well as the connection 

correlation (+ with + and – with –).

 

Each battery module is independent for each device. 

It is 

strictly forbidden to connect two devices to the 

same battery module

.

5.2.4.  Terminals for EPO (Emergency Power Off).

 

All of the UPSs have two terminals for the installation of an 

external emergency power off [EPO] output button.

 

The device is dispatched from the factory with its EPO circuit set 

to closed [NC] by default. This means that the UPS will cut the 

output power supply, emergency power off, when the circuit is 

opened: 

 

ˆ

Either by removing the female connector from the socket 

where it is inserted. This connector has a cable connected 

as a jumper that closes the circuit [Fig. A],

 

Fig. A 

Fig. B

 

ˆ

or by pressing the button installed external to the device 

belonging to the user. The connection on the button must 

be in the normally closed contact in order to open the circuit 

when activated.

UPS

Module 1

Module ‘n’

OUTPUT

USB

RS232

INTELLIGENT SLOT

USB

RS232

INTELLIGENT SLOT

INPUT

20A max.

PROGRAMMABLE

    OUTLETS(P1)

        10A max.

OUTPUT

INPUT

2K

3K

EPO

IN

OUT

NETWORK/FAX/MODEM

EPO

T

U

O

N

I

NETWORK/FAX/MODEM

R20160615-001A

Rear panel view for Galleon One 

1-3K LV and HV

IN

TE

LL

IG

E

N

S

LO

T

EPO

RS232

T

U

O

N

I

USB

INPUT

NETWORK/FAX/MODEM

1K/1.5K

PROGRAMMABLE

    OUTLETS(P1)

LV

PROGRAMMABLE OUTLETS(P1)

                      10A  max.

O

U

TP

U

T

TOWER 12BATTERY

TOWER 18BATTERY

Rack 12BATTERY

TOWER 4BATTERY

TOWER 8BATTERY

TOWER 6BATTERY

TOWER 16BATTERY

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

TOWER 12BATTERY

TOWER 18BATTERY

Rack 12BATTERY

TOWER 4BATTERY

TOWER 8BATTERY

TOWER 6BATTERY

TOWER 16BATTERY

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

BATTERY BREAKER

         Max, 50A

Fig. 5. 

Connection between device and ‘n’ battery modules.

Summary of Contents for SLC TWIN PRO2 A Series

Page 1: ...USER MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS SLC TWIN PRO2 A 1 2 and 3 kVA...

Page 2: ...Communicationport 5 2 5 1 RS232portandUSBinterface 5 2 5 2 Smartslot 5 2 6 Protectionagainstvoltagespikesforthemodem ADSL Fax line 5 2 7 Software 5 2 8 Considerationsbeforestartup 6 OPERATION 6 1 UPSS...

Page 3: ...3 8 3 2 Exclusions 8 4 TECHNICALSERVICESNETWORK 9 ANNEXES 9 1 GENERALTECHNICALSPECIFICATIONS 9 2 GLOSSARY SLC TWIN PRO2 UNINTERRUPTIBLE POWER SUPPLY UPS USER MANUAL...

Page 4: ...personnel Although no effort has been spared to ensure that the informa tion in this user manual is complete and accurate we accept no liability for any errors or omissions that may exist The images...

Page 5: ...belled for correct identification of each of its parts which together with the instructions described in this user manual allows installation and startup operations to be performed in a simple and org...

Page 6: ...B digital device pur suant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates u...

Page 7: ...accordance with ISO 14001 Recycling of the device at the end of its useful life Our company undertakes to use the services of authorised and regu latory companies to treat the set of products recover...

Page 8: ...ight contradic tions may arise If in any doubt the labelling on the device itself will always prevail The nameplate of the device shows all of the values relating to its main properties and characteri...

Page 9: ...OUTPUT 2kVA model USB RS232 INTELLIGENT SLOT OUTPUT INPUT 3K EPO IN OUT NETWORK FAX MODEM PROGRAMMABLE OUTLETS P1 3kVA model Fig 2 Rear views 1 2 and 3kVA models USB port with HID RS 232 serial port S...

Page 10: ...KER Max 50A BATTERY BREAKER Max 50A BATTERY BREAKER Max 50A TOWER 12BATTERY Rack 12BATTERY TOWER 4BATTERY TOWER 6BATTERY BATTERY BREAKER Max 50A BATTERY BREAKER Max 50A BATTERY BREAKER Max 50A BATTERY...

Page 11: ...c TWIN PRO2 Device series 2000 Power in VA SLC Brand acronym for UPSs CF Frequency converter devices without batteries EE Special EE battery module CO MadeinSpain markingonthedeviceandpackaging for cu...

Page 12: ...ectorsforconnection to the device and or other identical modules Charger current setting up to 8 A to decrease battery recharge time High performance selectable mode 0 97 ECO MODE Energy saving which...

Page 13: ...ation port makes possible a dialogue between the equipment with other machines or devices through the relays supplied in the terminal strip arranged on the same card with a single common terminal for...

Page 14: ...corners polyethylene cover and strapping all of which are recyclable materials consequently if it requires disposal it must be car ried out in accordance with current laws We recommend keeping the pac...

Page 15: ...pt the B1s In the first battery protection is by means of internal fuses and is not accessible to the user Similarly the battery modules also have internal protections by means of fuses and as in the...

Page 16: ...lied for the same device the connection between modules should be made through the hose supplied with the second battery module Fig 11 shows an example of the connection of an SLC TWIN PRO2 A B1 with...

Page 17: ...the user can configure the action to be taken in the event of a low battery alarm such as stopping the computer automatically This feature is ideal for powering network attached storage NAS systems wi...

Page 18: ...h the device can operate correctly without charging the batteries for the indicated time the risk of a prolonged power cut during the first hours of operation and the UPS s available backup time shoul...

Page 19: ...will supply output voltage through its static bypass To carry out a complete shutdown it is necessary to set the dis tribution board protection to OFF 6 1 5 Turn off the UPS without mains voltage in...

Page 20: ...e level connected to the output as a by displaying four equivalent segments respectively in the following proportion 0 25 26 50 51 75 and 76 100 Information about programmable outputs P1 Indicates tha...

Page 21: ...o the point where it is located accessing the previous variable with each press Activating the battery test Press this button for 3 seconds while in normal or frequency converter CF mode At the end of...

Page 22: ...own and provided that it has connected batteries whether internal or external If a complete shutdown is not carried out the setting will not be saved to the memory 7 2 4 Settings Tab 8 shows a summary...

Page 23: ...f frequent mains failures b Entering the value in Ah is vital for the control to be able to calculate and show the backup available on the LCD display without further alterations The settings values a...

Page 24: ...with output frequency of 60 Hz 1 With parameter 02 ENA the CF 50 or CF 60 variables are displayed instead of BAT 50 or BAT 60 DIS ECO mode disabled ENA ECO mode enabled ENA Bypass enabled with the in...

Page 25: ...mode energy saving LCD display 128 128 CF mode Description When the input frequency is between 46 and 64 Hz the UPS can be set to a constant output frequency of 50 or 60 Hz The device will still charg...

Page 26: ...ery voltage too high 28 Battery voltage too low 2A Battery charger short circuited at its output 41 Overtemperature 43 Output overload 45 Charger fault 49 Input overcurrent Tab 13 Error or fault code...

Page 27: ...del and serial number Date on which the issue occurred Full description of the issue including any information provided by the LCD and state of the alarm Power supply conditions type of load and level...

Page 28: ...n on the LCD diplay The audible alarm sounds continuously Charger shorted at its output Check if the connection of the external battery pack connected to the UPS is shorted Fault code 45 is shown on t...

Page 29: ...ctor 1 Transfer time inverter to battery 0 ms Transfer time inverter to bypass 4 ms Transfer time inverter to ECO 4 ms Transfer time ECO to battery 10 ms Performance at full load in line mode with bat...

Page 30: ...tic this is the physical connection between the input of an electrical device and its output DC Direct current is the continuous flow of electrons through a conductor between two points with different...

Page 31: ...when it exceeds certain maximum values On line mode A device is said to be on line when it is con nected to a system is operative and normally has its power supply connected Inverter An inverter is a...

Page 32: ...ce Support T S S network Commercial network and warranty information are available in website www salicru com www linkedin com company salicru salicru_SA Product Range Uninterruptible Power Supplies U...

Reviews: