7.2.2. Audible alarms.
Description
Alarm modulation or tone
Possibility of
muting
State of the UPS
Bypass mode
Beep every 10 seconds.
No
Battery mode
Beep every 5 seconds.
Yes
Fault
Continuous.
No
Warning
Overload
Beep every second.
Yes
End of backup
Beep every 2 seconds.
No
Faults
All
Continuous.
No
Tab. 7.
Audible alarms.
7.2.3. Location of the adjustment parameters on the display.
Parameter 1
Parameter 2
Parameter 3
Fig. 10.
Arrangement of the parameters on the LCD display.
•
Parameter 1:
Code of the settings menu. For more information, consult Tab. 8.
•
Parameters 2 and 3 are the configuration or value options for
each settings menu.
Select with buttons
‘ ’
or
‘ ’
to modify the menus or
parameters.
All of the parameter settings are saved when the UPS is
completely shut down and provided that it has connected
batteries, whether internal or external.
If a complete shutdown is not carried out, the setting will not be
saved to the memory.
7.2.4. Settings.
Tab. 8 shows a summary of parameter 1’s adjustable codes for each
operating mode and 0 shows the structure of the menu tree with the
operating mode for the settings.
Code
Description
Bypass mode
/ No output
mode
Mode
AC
Mode
ECO
Mode
CF
Battery mode
Battery
batteries
01
Output voltage.
YES
-
-
-
-
-
02
Frequency converter state.
YES
-
-
-
-
-
03
Output frequency.
YES
-
-
-
-
-
04
ECO enable/disable mode.
YES
-
-
-
-
-
06
Bypass state (UPS ‘Off’).
YES
YES
-
-
-
-
09
Programmable output state.
YES
YES
YES
YES
YES
YES
10
Programmable output configuration.
YES
YES
YES
YES
YES
YES
11
Backup limitation configuration.
YES
YES
YES
YES
YES
YES
12
Total battery pack Ah configuration.
YES
YES
YES
YES
YES
YES
15
EPO logical configuration.
YES
YES
-
YES
YES
-
17
Viewable backup time configuration.
YES
Tab. 8.
Parameter 1 codes list. Description and settings