32
SALICRU
Parameter 2 setting.
–
OPN. Bypass permitted. When selecting this op-
tion, the UPS will operate in bypass mode, provided
that selection in bypass settings (parameter 3) has
been enabled/disabled.
–
FBD. When selecting this option, operation in by-
pass mode is forbidden in any condition.
Parameter 3 setting:
–
ENA. Bypass enabled. When selected, bypass
mode is enabled.
–
DIS. Bypass disabled. If selected, automatic bypass
is permitted but not manual switch to bypass.
At this point, manual switch to bypass is under-
stood as being that which users perform on the
UPS. For example, pressing the OFF button on the
front of the device when it is in AC mode transfers
the load to the static bypass.
•
Code 09
Maximum battery discharge time setting.
Fig. 34.
Parameter 3 setting:
–
DIS, default value. Disables the battery discharge
time protection and the backup time will depend on
the capacity of the batteries.
–
000 ~ 999. Sets maximum backup time. The UPS
will turn off automatically once it has elapsed to
protect the batteries. In some III/II models and de-
pending on the firmware version, it can be set to
990 minutes [16.5 h] instead of DIS.
•
Code 10
Reserved.
Fig. 35.
Reserved for future options.
•
Code 11
Reserved.
Fig. 36.
Reserved for future options.
•
Code 12
Enabling/disabling the hot standby function.
Fig. 37.
Parameter 2 setting. HS.H
–
Enabling or disabling the Hot standby function.
Parameter 3 setting:
–
YES: The Hot standby function is enabled after
the mains are restored even without the batteries
being connected to the UPS.
–
NO: The Hot standby function is disabled. The UPS
operates in normal mode. It will not restart if the
batteries are not connected to the UPS.
•
Code 13
Reserved.
Fig. 38.
Reserved for future options.