SALICRU
Operating mode / state
UPS startup
Description. When the UPS is started, the display screen of this mode is displayed for a few seconds to initialise the CPU and system.
LCD.
No output
mode
Description.
If the bypass voltage / frequency is out of range or the bypass is disabled (or prohibited), the UPS will enter no output mode with the
inverter running or shut down. The UPS does not supply output voltage. The audible alarm modulated every two minutes is audible.
AC mode
Description.
If the input voltage is within the range of the device, the UPS will supply stable AC sine-wave voltage to the load or loads, and charge
the batteries.
ECO mode
Description.
If the input voltage is within the regulation ranges and ECO mode is activated, the UPS supplies the output voltage from the bypass
in ECO mode (energy saving).
CF mode
Description.
When the output frequency is selected as CF in parameter 3 of the settings menu code 02, the inverter supplies a constant output
frequency (50 or 60 Hz). In this way, the UPS will not supply bypass output voltage, but will charge the batteries.
Battery mode
Description.
When the input / frequency voltage is not within the predefined range of the device or there is an AC mains failure, the UPS powers
the loads from the batteries for a limited time due to their own capacity and activates the audible alarm modulated every 4 seconds.