36
SALICRU
7.7. ERROR OR FAULT CODES.
Code
Error or failure description
01
DC bus startup fault.
02
DC bus overvoltage.
03
DC bus undervoltage.
04
DC bus imbalance.
11
Inverter soft start fault.
12
High voltage in the inverter.
13
Low voltage in the inverter.
14
Inverter output short-circuited.
1A
Negative power fault at the output.
21
Battery thyristor short-circuited.
24
Inverter relay short-circuited.
2A
Battery charger short-circuited
31
CAN communication fault.
36
Output current in parallel system unbalanced
41
Overtemperature.
42
CPU communication fault.
43
Output overloaded.
60
Inverter overcurrent
63
Inverter waveform incorrect
6A
Battery startup fault.
6B
PFC current fault in battery mode.
6C
DC Bus voltage change too fast.
6D
Current sensor failure
6E
Power supply fault
77
Overtemperature in output transformer
Tab. 13.
Error or fault code.
7.8. WARNING OR ALERT INDICATORS.
Code
Icon (flashing)
Audible alarm
Low battery voltage.
Modulated every second.
Overload.
Modulated twice per
second
Battery disconnected.
BATT FAULT
Modulated every second.
Battery overcharge.
Modulated every second.
EPO activated.
Modulated every second.
Fan fault /
Overtemperature.
TEMP
Modulated every second.
Charger fault.
CHARGING
BATTERY
Modulated every second.
Tab. 14.
Warning or alert indicators.