3.2. Definition of the product.
3.2.1. Nomenclature.
SLC-8000-TWIN RT (B1) WCO “EE29503”
MOD BAT TWIN RT 2x6AB003 40A WCO “EE29503”
EE*
Special specifications of the client.
CO
“Made in Spain” marking in the UPS and packaging
(custom issues).
W Neutral
brand.
(B0)
No batteries and no space to fit them in.
(B1)
Equipment with extra charger and batteries out from
UPS.
TWIN RT
Series of the equipment.
8000
Power in VA.
SLC Brand
acronym.
EE*
Special specifications of the client.
CO
“Made in Spain” marking in the UPS and packaging
(custom issues)..
W Neutral
brand.
40A Protection
size.
003
Last three characters of battery code.
AB
Initials of the battery family.
6
Battery quantity in one string.
2x
Quantity of strings in parallel. Omitted for one.
0/
Battery module without them, but the needed acces-
sories to install them.
TWIN RT
Series of the battery module.
MOD BAT
Battery module.
i
Note relative to the batteries:
B0 and B1 acronyms stated the nomenclature related to
batteries:
(B0) The equipment is supplied without batteries and
without accessories for them (screws and electrical
cables).
Batteries are property of the client, and they will be
fitted out of the UPS case or cabinet.
Under request, it is possible to supply the acces-
sories (screws and electrical cables), needed to
install and connect the external batteries.
(B1) Equipment with extra battery charger. The equip-
ment is supplied without batteries and without ac-
cessories for them (screws and electrical cables),
corresponding to the stated batteries in the model.
Under request, it is possible to supply the acces-
sories (screws and electrical cables), needed to
install and connect the batteries.
For those equipments requested without batteries, the
acquisition, installation and connection of themselves
will always be done by client and under his responsibility.
Regarding the battery data of quantity, capacity and
voltage stated in the nameplate sticked of the equip-
ment,
respect this data and the polarity of the bat-
tery connection strictly
.
In equipments with separate bypass line, a galvanic iso-
lation transformer has to be installed in any of both UPS
input power supplies (rectifier input or static bypass), in
order to avoid the direct connection of both lines through
the internal wiring of the equipment.
This is only applicable,when both power supply lines
come from different electrical networks, for example:
- Two different electrical companies.
- One from an electrical company and the other from a
generator set, ...