4.  INSTALLATION.

4.1. 

IMPORTANT SAfETY INSTRUCTIONS..

Read  the  following  safety  instructions  before  installing 
and starting up the equipment.

4.1.1.  Transport.

 Transport the UPS in the original packing (as protection from 

• 

jolts and impacts).

4.1.2.  Localiton.

 Condensation  problems  could  happen  when  moving  the  UPS 

• 

from cold area to heat one. The UPS has to be perfectly dry be-
fore installing. Two hours of acclimatization should be allowed 
as minimum.
 Do  not  install  the  UPS  close  to  water,  wet  or  dust  environ-

• 

ments.
 Do not install the UPS in places exposed to direct sunlight or 

• 

close to heat sources.
 Do not block the cooling wholes of the UPS enclosure.

• 

4.1.3.  Take care of your safety.

Equipment definition.

• 

Movable installation, class I, fed by an outlet type A and distri-
bution system TT (neutral regime is referred to earth).
Equipment with terminals: Fix installation, class I, permanent 
connected  and  TT  distribution  (neutral  regime  is  referred  to 
earth)

• 

The  UPS  can  be  connected  and  handled  by  staff 
without  any  specific  training,  less  those  hardwired 
models that will be installed by qualified staff and in 

accordance with the regulations in force.

• 

Do not forget that the UPS is a generator of electric 
energy,  therefore  the  user  has  to  take  the  needed 
cautions against direct and indirect contacts.

Do not connect devices or loads at its outlets that can overload 

• 

the UPS, like laser printers.
Put the cables in order to avoid tripping or stepping with them.

• 

Do not overload the equipment with domestic loads like hair-

• 

dryers, irons, etc...
 The earth connection must be wired to the protection earth la-

• 

belled as (

), making sure that it is done before turning on 

the  input  voltage.  For  small  devices  (connected  with  power 
cord with plug), the user has to make sure that the outlet cor-
responds with the supplied type, with earth connection com-
pletely isolated and connected to the local protective earth.
 The UPS plug connected to the mains outlet, will have easy ac-

• 

cess and close to the equipment.

 In those models with terminals a disconnection device has to be 

• 

installed, with easy access and close to the equipment.
 To connect the UPS to the mains and loads, use standardized 

• 

cables and tested by an official organization only.
 When installing the equipment, make sure that the sum of the 

• 

earth leakage currents at the UPS output plus the connected 
load/s do not overcome 3,5 mA.

4.1.4.  Operating.

 Do not disconnect the power cord plug of the UPS meanwhile 

• 

the loads are turned on, because the earth connections of the 
equipment and loads will be disconnected.
 The UPS is characterized for having an internal current power 

• 

supply  (batteries).  The  UPS  outlets  can  be  alive  electrically 
although the UPS is disconnected from the installation of the 
building physically.
 Pay  special  attention  to  the  labelling  of  the  equipment  that 

• 

warns on «Electrical discharge danger» and stated as (

).

Inside the equipment there are dangerous voltages, do not open 

• 

the case, the access has to be done by authorised and compe-
tent staff. In case of maintenance or fault, consult the closest 
STS (Service and Technical Support).
 To disconnect the UPS completely, first press the OFF button, 

• 

then disconnect the power cord cable in those models with plug 
or turn Off the disconnection device close to the equipment (to 
be  installed  and  property  by  the  customer),  in  those  models 
with terminals.
 Make sure that objects or fluids cannot enter inside the UPS.

• 

4.1.5.  Maintenance, service and faults.

 The UPS works with dangerous voltages. The repair has to be 

• 

done by qualified staff only.

Electrical  shock  risk.  Although  the  unit  is  discon-
nected from the electrical mains, there are internal 
parts in the UPS that are still connected to the bat-

teries, therefore they are both under voltage and dangerous.
Before doing any service and/or maintenance, disconnect the 

• 

batteries and check that there is not any voltage in the termi-
nals capacitor bus (BUS-capacitors).
 Only properly staff familiarized with the batteries and with the 

• 

additional  caution  measures  can  replace  them  and  supervise 
the operations. Not authorized people should be kept away.

Electrocution risk. The battery circuit is not isolated 
from the input voltage. Dangerous voltages can exist 
between  the  battery  and  earth  terminals.  Before 

touching, check that there is not any voltage present.
The  batteries  can  cause  electrocution  and  to  produce  a  high 

• 

shot-circuit current. Take the caution measures stated below 
when working with batteries:

 Take watches, rings and any metallic object off.

 

ˆ

Use tools with insulated handles only and gloves.

 

ˆ

During battery replacement, install the same number and type.

• 

 Do not catch fire to the batteries. Explosion danger.

• 

 Do not open or destroy the batteries. Electrolyte spillage can 

• 

hurt eyes and skin. It can be toxic.

Summary of Contents for SLC TWIN series

Page 1: ...S L CT WI N I N D E X U S E R S MA N U A L F R O M0 7 k V AT O3 k V A P a g e 2 U S E R S MA N U A L F R O M4 k V AT O2 0 k V A P a g e 3 4...

Page 2: ...UPS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS SWITCH MODE POWER SUPPLY INDUSTRIAL POWER SUPPLY LIGHTING FLOW DIMMER STABILIZERS STATIC INVERTERS SLC TWIN series from 0 7 to 3 kVA USER S MANUAL...

Page 3: ......

Page 4: ...ng 4 4 2 Installation 4 4 3 Procedure to connect the models with external batteries extended autonomies 4 5 Communication ports 4 5 1 RS 232 interface C7 4 5 2 AS400 interface C16 Option 4 6 Overvolta...

Page 5: ...series This manual has to be read carefully before installing and operating it Keep this manual for future consults 1 2 1 Used symbols and conventions Warning symbol Carefully read the indicated para...

Page 6: ...InthenextPROCESSMAPisrepresentedtheinteractionamongallthe processes of the Quality and Environmental System of SALICRU 2 2 Standard The UPS product SLC TWIN series is designed manufactured and commer...

Page 7: ...ons of voltage frequencies electrical noises black outs and mains faults which are present in the energy distribu tion mains This is the essential target of the UPSs of SLC TWIN series This manual is...

Page 8: ...1 Input breaker protection Fan RJ 45 C7 RS232 communication port Rear view SLC 700 and 1000 TWIN TWIN B1 to 110 Fig 2 115 120 127 VAC C2 Extended autonomy connector C16 AS400 SNMP USB communication po...

Page 9: ...00 SNMP USB communication port optional C11 and C12 Transient protection Fax m dem C4 Outlet C0 Inlet M1 Input breaker protection Fan C7 RS232 communication port Rear view SLC 3000 TWIN to 208 220 230...

Page 10: ...m C4 Outlet C0 Inlet Fan Rear view SLC 700 and 1000 TWIN R TWIN R B1 Fig 8 C2 Extended autonomy connector C16 AS400 SNMP USB communication port optional C7 Communication port RS232 M1 Input breaker pr...

Page 11: ...some other usefull one are in the rear panel C2 Extended au tonomy connector C16 AS400 SNMP USB communication port optional C7 Communication port RS232 M1 Input breaker protection C11 and C12 Transie...

Page 12: ...Transient protection Fax modem C4 Outlets C0 Inlet Fans Rear view SLC 1500 TWIN R B1 Fig 14 C2 Extended au tonomy connector C16 AS400 SNMP USB communication port optional C7 Commu nication port RS232...

Page 13: ...owed from 0 to 999 Vac Hz It displays the frequency value of the output voltage which will be showed from 0 to 99 Hz Load information It displays the of the load in W or VA the maximum value will be s...

Page 14: ...MOD BAT TWIN 2x3AB003 40A R W C0 EE29503 Battery module special EE CO Silk screen printing Made in Spain in the equipment and packing customs topics W White label team R Rack format Protection caliber...

Page 15: ...IN series is card type in order to be inserted into the slot that UPS has in its rear side Thanks to this format it is avoided to have small devices around the UPS The connection from the UPS with the...

Page 16: ...e earth leakage currents at the UPS output plus the connected load s do not overcome 3 5 mA 4 1 4 Operating Do not disconnect the power cord plug of the UPS meanwhile the loads are turned on because t...

Page 17: ...2 6 hours before its use Once the input circuit breaker is turned On the UPS will charge the batteries automatically The UPS can be used immediately without charging the batteries previously but the...

Page 18: ...ifference of potential will provoke a short circuit which will cause dam ages to the UPS and or to the battery modules Any connection between the UPS and battery module s will 3 be done taking care on...

Page 19: ...e new UPS monitoring software which facilitates a friendly monitoring and control interface In case of mains failure this software gives an automatic Shutdown for a system made by several PCs With thi...

Page 20: ...epending if the initial setting has been modi fied or not On bypass mode code 01 the equipment will still be supplying output voltage through the bypass so the input circuit breaker of the switchgear...

Page 21: ...charges the batteries too The acoustic alarm of the UPS will beep once every 2 minutes The UPS doesn t have available the autonomy function when it runs on Bypass mode so if the mains faults the load...

Page 22: ...Operating mode screen Battery mode code 03 Fig 28 220Vac equipments 5 2 5 Fault mode Anyone of the fault or warning codes showed in the table 8 are considered as fault mode Besides some warning word c...

Page 23: ...ect of the LCD panel Step 2 The blinking black point is displayed beside 230 V after pressing twice the button Select Step 3 When pressing the button Enter for more than 1 second the new selected valu...

Page 24: ...or mainte nance job turn off the battery circuit breaker or remove the connection between battery blocks The batteries have dangerous voltages The maintenance 8 or replacement of the batteries has to...

Page 25: ...s guaranteed the perfect operating and the pos sible coming faults are avoided These supervisions are usually done without shutdown the equipment In those cases that a shutdown were needed a date and...

Page 26: ...3 THDv with non linear load 6 in accordance with EN 62040 3 Dynamic response time 150 ms Overload on line mode 150 for 30 s 150 for 0 3 s Overload on battery mode 150 for 30 s 150 for 0 3 s Permissib...

Page 27: ...ble 11 Output power derate according to the operating altitude 7 2 GlosSarY AC It is nominated as alternating current CA in Spanish abbreviation and AC in English to the electrical current in which th...

Page 28: ...d it is crossed by an electric current The colour wave longitude depends on the semiconductor ma terial used in its manufacturing being able to vary from the ultraviolet one going through the visible...

Page 29: ...28 NOTES USER MANUAL...

Page 30: ...29 SALICRU NOTES...

Page 31: ...30 NOTES USER MANUAL...

Page 32: ......

Page 33: ...RLANDA NORUEGA REP BLICA CHECA SUECIA SUIZA UCRANIA ARGENTINA BRASIL CHILE COLOMBIA ECUADOR PER ARABIA SAUD ARGELIA EGIPTO JORDANIA KUWAIT MARRUECOS T NEZ KAZAJST N PAKIST N FILIPINAS INDONESIA MALASI...

Page 34: ...UPS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS SWITCH MODE POWER SUPPLY INDUSTRIAL POWER SUPPLY LIGHTING FLOW DIMMER STABILIZERS STATIC INVERTERS UPS SLC TWIN series from 4 to 20kVA USER S MANUAL...

Page 35: ......

Page 36: ...4 Operating 4 1 5 Maintenance service and faults 4 2 To keep in mind 4 3 Unpacking and content checking 4 4 Connection of the input output and protective earth wiring 4 4 1 Notes for the installation...

Page 37: ...tion measures Danger of electrical discharge symbol Pay special attention to it both in the indication on the equipment and in the paragraph referred to this instruction s manual i Main protective ear...

Page 38: ...represented the interaction among all the processes of the Quality and Environmental System of SALICRU 2 2 Standard The UPS product SLC TWIN series is designed manufactured and commercialized in acco...

Page 39: ...ectrical noises blackouts and mains faults which are present in the energy distribution mains This is the essential target of the UPSs of SLC TWIN series Furthermore the 4 5 and 6kVA equipments can al...

Page 40: ...on port Intelligent slot Fans Input breaker Terminal strip cover Parallel port Maintenance bypass switch Rear view of the 12 15 and 20 kVA equipment bat Fig 3 tery cabinet 40 x 9Ah Communication port...

Page 41: ...m 0 to 999 Vac It displays the frequency value of the output voltage which will be showed from 0 to 99 Hz Load information It displays the of the load in W or VA the maximum value will be showed from...

Page 42: ...single phase UPS Power in VA KIT Equipments with two or more cabinets in a single code MOD BAT TWIN 2x3AB003 40A R W C0 EE29503 Battery module special EE CO Silkscreen Made in Spain in the equipment...

Page 43: ...r equipments with standard autonomy and adapts it to the optimal levels of the battery bank to charge This double conversion structure is complemented with two addi tional functional blocks the bypass...

Page 44: ...accepted by the main software and hardware manufacturers The available SNMP optional for TWIN series is card type in order to be inserted into the slot that UPS has in its rear side Thanks to this fo...

Page 45: ...ctrical shock risk Although the unit is disconnected from the electrical mains there are internal parts in the UPS that are still connected to the batteries therefore they are under dangerous voltage...

Page 46: ...e input and output cables to their corresponding 5 UPS terminals and according to the model circuit diagram i Tighten the connections The protective earth is the connection cable between the 6 equipme...

Page 47: ...eans the number of faulty UPSs that the system can allow simultaneously The higher is X the higher will be the reliability of the system For those occasions where the reliability is the essential N X...

Page 48: ...AINS FAULT REMOTE SHUTDOWN GENERAL ALARM UPS FAULT GND DB 9 interface of AS400 communication protocol Fig 13 4 8 Software Free software WinPower WinPower is the brand of the new UPS monitoring softwar...

Page 49: ...rocedure to add a new UPS 2 Before installing it prepare the input and output wiring a switches and parallel cable Turn OFF the input and output breakers of the new unit b Connect its input output and...

Page 50: ...ed OFF Do not touch the maintenance switch meanwhile the c system runs on inverter mode 5 3 CONTROL Panel All the codes will be displayed in the LCD panel corresponding to their operating modes as fol...

Page 51: ...one those loads that are not critical in order to decrease the load percentage under 90 of the UPS nominal power rate Note To connect a generator or genset proceed as follows Turn on the generator an...

Page 52: ...ternated between the Pn symbol and the code of the mode The P symbol means that the UPS runs on Parallel mode and n number means the parallel quantity Warning mode 6 The LCD panel on Warning mode is s...

Page 53: ...cy or By pass status will be modified by the selected one In case the ENTER or Select buttons are not pressed in 10 seconds period the black point will disappear without applying any changes Only one...

Page 54: ...ing should start when the UPS would have shutdown due to a deep battery discharge The charge time for a standard UPS should 12 hours as minimum 6 2 Notes for installing and replacing the battery Befor...

Page 55: ...e load and reduce the number of loads connected to the UPS Check that they are not damaged The Warning mode is 23 the buzzer beeps every second The UPS charger is faulty Contact with the technical ser...

Page 56: ...s are avoided These supervisions are usually done without shutdown the equipment In those cases that a shutdown were needed a date and time would agree with the customer to do the task This maintenanc...

Page 57: ...the output is broken Internal charger Technology DC DC Flyback Charge type P U Constant power constant voltage Floating voltage accuracy 1 V Maximum charging current 2 A single phase input 4 A three p...

Page 58: ...romag netic interference considerably EMi is the perturbation that occurs in a radio transmis sion or any other electrical circuit caused by an electromagnetic perturbation coming from an external sou...

Page 59: ...nt This isdoneby rectifier diodes which can be solid state semiconduc tors vacuum or gassy valves like the mercury vapour Depending on the features of the alternating current power supply used it is c...

Page 60: ......

Page 61: ...NAMARCA GRECIA HOLANDA IRLANDA NORUEGA REP BLICA CHECA SUECIA SUIZA UCRANIA ARGENTINA BRASIL CHILE COLOMBIA ECUADOR PER ARABIA SAUD ARGELIA EGIPTO JORDANIA KUWAIT MARRUECOS T NEZ KAZAJST N PAKIST N FI...

Reviews: