16
SALICRU
5.1.4. Transport to the site.
•
It is recommended to transport the UPS by means of a
pallet jack or the most appropriate method considering the
distance between the two points.
•
If the distance is considerable, it is recommended to
transport the device in its packaging to the installation site
and then unpack it.
The device is heavy.
Make sure that the UPS does not topple over during
transportation.
The cabinets should always be kept in the upright
position.
During loading and unloading operations, always
follow the instructions marked on the packaging.
•
Before positioning the device, and to prevent it from toppling
over, it is advisable to move the entire system together with
the wooden pallet on which it is mounted. For removal from
the pallet, remove the lower rear and front parts and insert
the forks of the forklift. The UPS can be moved from its front
according to the spaces available.
5.1.5. Siting.
5.1.5.1. Siting for single devices.
•
For correct ventilation of the device, ensure that the space
around it is free from obstructions. Observe the minimum
distances indicated in Tabla 2 and Tabla 3 of section 5.1.7 of
this document, in which the values for distances A, B, C and
D are indicated according to the power of each device. For
the battery cabinets, maintain the distances recommended
for the UPS itself.
•
For extended backups with more than one cabinet, it is
recommended to place one on each side of the device and,
in the case of a greater number of battery cabinets, repeat
the same sequence alternately.
5.1.5.2. Siting for parallel systems.
•
It is recommended to place them in order according to the
number (No.) indicated on the door of each device. The
number corresponds to the address originally assigned at the
factory.
The arrangement is optimum considering the length of
the wiring of the batteries and the communications bus.
For a greater number of battery cabinets in systems with
extended backup, follow the same criterion, maintaining
the symmetry.
•
If the system consists of models with the batteries and
device mounted in the same cabinet, the battery module
illustrations should be disregarded.
•
For correct ventilation of the device, it is necessary to
leave its surroundings free from obstructions. Observe
the minimum distances indicated in Tabla 2 and Tabla
3 of section 5.1.7 of this document, in which the values
for distances A, B, C and D are indicated according to the
power of each device.
•
For the battery cabinets, maintain the distances recom-
mended for the UPS that makes up the system itself.
5.1.6. Plan view of the base, static load and weights.
118
494
Cable-
routing
plate
26.5
943
516
552
705.5
146
Fig. 12.
Plan view of the base of 80... 160 kVA devices.
Cable-routing
plate
947
300
880
750
700
855
Fig. 13.
Plan view of the base of 200... 300 kVA devices.
Summary of Contents for SLC X-PERT 100
Page 1: ...SLC X PERT 80 400 kVA UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...
Page 8: ...8 SALICRU Fig 3 Front view of the 400 kVA model...
Page 34: ...34 SALICRU Fig 42 Connection of three UPSs through the CAN bus for 400 kVA devices...
Page 60: ...60 SALICRU...
Page 61: ...61 X PERT UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...