22
SALICRU
Information about each device’s cables and the input’s protection
fuses is presented below.
Power (kVA)
80
100
125
160
200
250
300
400
INPUT FUSES (A)
Rectifier
160
200
225
315
355
425
500
800
Bypass
125
160
200
250
300
400
500
630
PHASE CONDUCTOR CROSS SECTION (mm
2
)
Rectifier
4x (1x70)
4x (1x95)
4x (1x95)
4x (1x150)
4x (1x185)
4x (1x240)
4x (2x185)
4x (2x240)
Bypass
4x (1x50)
4x (1x70)
4x (1x95)
4x (1x120)
4x (1x150)
4x (1x240)
4x (2x150)
4x (2x185)
Output
4x (1x50)
4x (1x70)
4x (1x95)
4x (1x120)
4x (1x150)
4x (1x240)
4x (2x150)
4x (2x185)
Batteries
3x (1x70)
3x (1x95)
3x (1x95)
3x (1x150)
3x (1x185)
3x (2x150)
3x (2x185)
3x (2x240)
Earth conductor cross section (mm
2
)
35
50
50
95
95
150
185
240
CONNECTION TO THE MAINS
Type
Screw terminals
Aluminium bars
Max. conductor cross section (mm
2
)
95
150
185
240
No. of conductors
1 (2)
2
Fixing screws
-
M12
Tightening torque (Nm)
8... 15
69... 85
Tabla 11.
Cable cross section and input fuses.
The cross sections indicated in the table above are only indicative.
For their dimensioning, standard UNE 20460-5-523 has been
taken into account.
Terminals.
The SLC X-PERT UPS is equipped with terminals for the
connection of power cables and auxiliary connections.
Battery
terminals
Bypass input
Auxiliary terminals
Rectifier
input
UPS
output
Fig. 19.
Terminals for 80 kVA devices.
Summary of Contents for SLC X-PERT 100
Page 1: ...SLC X PERT 80 400 kVA UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...
Page 8: ...8 SALICRU Fig 3 Front view of the 400 kVA model...
Page 34: ...34 SALICRU Fig 42 Connection of three UPSs through the CAN bus for 400 kVA devices...
Page 60: ...60 SALICRU...
Page 61: ...61 X PERT UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...