29
Fig. 32.
Top view of a row of batteries (12 V, 12 -14 Ah).
Battery fuse
negative
Interconnection
link
Interconnection
link
Battery fuse
negative
Interconnection
link
Interconnection
link
Battery fuse
positive
Battery neutral
Interconnection
link
Interconnection
link
Battery fuse
positive
Interconnection
link
Battery neutral
Interconnection
link
+B
N
N
+B
-B
-B
Tray 1
Tray 2
Tray 3
Tray 4
Tray 5
Tray 6
Fig. 33.
Top view of the battery connection tray
(12 V, 12-14 Ah).
After connection, insert the trays back into the UPS.
Replace and fix the left/right cover with the screws.
5.2.3. Connection of the auxiliary cables.
SLC X-PERT UPS units can be connected to controls/external
components specifically designed to improve the safety and
reliability of the device. The following auxiliary connections
can be made in the UPS:
•
External manual bypass (MBCB).
•
External Normal/Bypass selector.
•
External output switch (OCB).
•
Emergency power off button (EPO).
•
Auxiliary batteries contact (BCB).
•
Diesel generator.
Auxiliary cables must be connected to specific terminals.
Cables up to 4 mm
2
can be connected.
X-PERT
UNINTERRUPTIBLE POWER SUPPLIES (UPS)
USER MANUAL
Summary of Contents for SLC X-PERT 100
Page 1: ...SLC X PERT 80 400 kVA UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...
Page 8: ...8 SALICRU Fig 3 Front view of the 400 kVA model...
Page 34: ...34 SALICRU Fig 42 Connection of three UPSs through the CAN bus for 400 kVA devices...
Page 60: ...60 SALICRU...
Page 61: ...61 X PERT UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...