The external connection ports shown in the previous figures are
described below:
•
RS-232/USB
: for connection to proprietary programming
and control software.
•
SRC-2 (optional)
: relay card used for remote signalling of
states and alarms.
•
Parallel (optional)
: used for parallel UPS communication.
•
MODBUS (optional)
: used for the transmission of data to
the outside through the MODBUS RTU protocol (RS-485).
•
Thermal probe (optional)
: used to measure the
temperature of the cabinet/battery room and adjust the
charging voltage automatically.
•
SNMP (optional)
: used for the external transmission of
data through a LAN.
•
Normal/Bypass selector
.
5.2.5. Relay interface connection.
The SLC X-PERT UPS, in its complete configuration, is equipped
with a 5-relay interface in order to transmit alarms and operating
states remotely. The electrical connection is made directly to
the terminals located on the front of the SRC-2 interface slot.
SRC-2 slot
Common alarm
Mains failure
End of battery backup
Inverter out of tolerance
The bypass powers the load
Fig. 38.
Relay interface terminals.
Relay output specifications: 250 V AC (1 A); 30 V DC (1 A).
RELAY
ALARM/STATES
STATES
M1
LED
PINS
STATE IN NORMAL
OPERATION
NAME
STATE IN NORMAL
OPERATION
RL1
A30: Common alarm
No voltage if there is an
alarm
2-3
Closed
DL1
ON
1-2
Open
RL2
A1: Input failure
No voltage if there is an
alarm
5-6
Closed
DL2
ON
4-5
Open
RL3
A9: End of battery backup
No voltage if there is an
alarm
8-9
Closed
DL3
ON
7-8
Open
RL4
A13: Inverter out of tolerance
No voltage if there is an
alarm
11-12
Closed
DL4
ON
10-11
Open
RL5
Normal mode
A16: Bypass
→
load
No voltage if there is an
alarm
13-14
14-15
Closed
Open
DL5
ON
ECO mode
S7 state: Bypass
→
load
With voltage if there is
state
14-15
13-14
Closed
Open
Tabla 12.
Relays available in the relay interface.
Summary of Contents for SLC X-PERT 100
Page 1: ...SLC X PERT 80 400 kVA UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...
Page 8: ...8 SALICRU Fig 3 Front view of the 400 kVA model...
Page 34: ...34 SALICRU Fig 42 Connection of three UPSs through the CAN bus for 400 kVA devices...
Page 60: ...60 SALICRU...
Page 61: ...61 X PERT UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...