Alarms activated in the I/O module while a page
of one of the sections of the power modules is
displayed.
The audible alarm, if enabled, will be activated to indicate
that a failure has occurred. The audible alarm can be muted by
pressing the alarm icon.
7.2.3. Display of the alarms history.
In the Alarms section, you can access the page corresponding
to the alarm history. The following image shows the content
that can be displayed.
Fig. 60.
Device alarms history page.
•
The first event shown is the most recent (LiFo). For each
new event, all of the previous events automatically move
one position, deleting the oldest one.
•
Each line shows the event number (position in the list),
the alarm code and date and time. An asterisk indicates
automatic resetting of the alarm.
•
Up to a maximum of 250 events can be displayed. The event
log can be moved by sliding a finger across the screen.
•
By pressing the SAVE HISTORY TO FILE key, a page will
be opened to enable selection of one of the three different
ways to save the history: SD card, USB, internal memory.
The touch screen recognises when an external memory
medium is inserted, and the corresponding icon changes
from grey to blue (enabled). The text file saved contains the
same information as the history, as well as a description of
each event.
Fig. 61.
Save the history to a file.
7.2.4. Alarms and operating states.
For the SLC X-PERT UPS, any of the following alarms can occur.
Code
Description
A1
MAINS FAILURE
A2
IN. PHASE ROT. ERR
A3
BOOSTER STOPPED
A4
BOOSTER FAILURE
A5
DC VOLTAGE FAILURE
A6
BATTERY TEST
A7
BCB OPEN
A8
BATTERY DISCHARGED
A9
END BATT. BACKUP
A10
BATTERY FAILURE
A11
SHORT-CIRCUIT
A12
SHUTDOWN DUE TO SHORT-CIRCUIT
A13
INV. OUT OF TOL.
A14
BYP. PHASE ROT. ERROR
A15
BYPASS FAILURE
A16
BYP -> LOAD TRANSFER
A17
RETRANSFER DISABLED
A18
MBCB CLOSED
A19
OCB OPEN
A20
OVERLOAD
A21
THERMAL IMAGE
A22
BYPASS SWITCH
A23
EPO PRESSED
A24
HIGH TEMPERATURE
A25
INVERTER OFF
A26
COMMUNICATION ERROR
A27
EEPROM ERROR
A28
CRITICAL FAILURE
A29
MAINT. REQUIRED
A30
COMMON ALARM
A31
MBCB BUS CLOSED
A32
EPO BUS CLOSED
A33
ASYMMETRIC LOAD
A34
SERVICE REQUIRED
A35
DIESEL MODE
A36
RAPID DC SHUTDOWN
A37
OCBD OPEN
A38
INVERTER --> LOAD
A39
INVERT. LOOP ERR.
A40
SSI FAILURE
A41
RECT. LOOP VOLT. ERR.
A42
LOSS OF RECTIFIER REDUNDANCY
A43
RECTIFIER THERMAL IMAGE
A44
INVERTER DESAT
A45
HIGH TEMPERATURE IN SSW
A46
REDUNDANCY LOST
A47
PARAMETER SEND ERR.
A48
E2P PARAMETER RECEP. FAIL.
Summary of Contents for SLC X-PERT 100
Page 1: ...SLC X PERT 80 400 kVA UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...
Page 8: ...8 SALICRU Fig 3 Front view of the 400 kVA model...
Page 34: ...34 SALICRU Fig 42 Connection of three UPSs through the CAN bus for 400 kVA devices...
Page 60: ...60 SALICRU...
Page 61: ...61 X PERT UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...