57
Model
SLC X-PERT
Power (kVA)
80
100
125
160
200
250
300
400
Active power (kW)
80
100
125
160
200
250
300
400
Input frequency (selectable) (Hz)
Tolerance (%)
50 - 60
±
10
Input power factor
>0.99
Input current harmonic distortion (at rated
voltage and THDv <0.5%) (%)
25% load
50% load
75% load
100% load
<5
<4
<3
<3
Output voltage static stability (%)
±
1
Output voltage ripple (%)
<1 (rms)
Battery recharging characteristics
Intermittent load with prevailing state of complete standby and control of the state of the IU batteries
(DIN 41773)
Maximum battery recharging current (A)
- With rated output load
- Maximum current with DCM function
15
50
15
50
20
50
20
50
30
100
40
100
40
100
50
100
Rectifier bridge type
IGBT – PFC
Input protections
Fuses
Rated input current (A)
(with rated load and charged batt.)
122
152
190
243
302
378
453
603
Maximum input current with minimum voltage (A)
(with rated load and maximum recharging current)
175
212
267
334
423
518
611
829
Startup ramp time (walk-in) (s)
5... 30 (programmable)
Sequential startup (hold off) (s)
1... 300 (programmable)
BATTERIES
Battery type (standard)
Sealed lead acid (VRLA - maintenance free)
Number of cells
360... 372
Float voltage at 25 °C (Vdc)
360 el.
372 el.
812
840
Minimum discharge voltage (Vdc)
360 el.
372 el.
620
632
Power consumed by the inverter (kW)
(with rated load cos
φ
=1)
82.5
103.1
128.9
164.9
204.1
255.1
306.1
407.7
Power consumed by the inverter
(with rated load and minimum discharge voltage) (A)
133
166
208
266
329
411
494
658
Protection
Fuses
Test
Included as standard
INVERTER
Inverter bridge
IGBT (high frequency PWM)
Rated apparent power cos
φ
=1 (kVA)
80
100
125
160
200
250
300
400
Rated active power cos
φ
=1 (kW)
80
100
125
160
200
250
300
400
Efficiency (%) DC/AC
25% load
50% load
75% load
100% load
96.0
97.0
97.0
98.1
Output
3 phases/4 wires
Three-phase rated output voltage (Vac)
3x380 / 3x400 / 3x415
Output voltage stability
±
1
±
2
±
5
<20
VFI-SS-111
- Static (balanced load) (%)
- Static (unbalanced load) (%)
Dynamic (load: 20%-100%-20%) (%)
- Voltage recovery after load change (ms)
- Classification according to EN-IEC 62040-3
X-PERT
UNINTERRUPTIBLE POWER SUPPLIES (UPS)
USER MANUAL
Summary of Contents for SLC X-PERT 100
Page 1: ...SLC X PERT 80 400 kVA UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...
Page 8: ...8 SALICRU Fig 3 Front view of the 400 kVA model...
Page 34: ...34 SALICRU Fig 42 Connection of three UPSs through the CAN bus for 400 kVA devices...
Page 60: ...60 SALICRU...
Page 61: ...61 X PERT UNINTERRUPTIBLE POWER SUPPLIES UPS USER MANUAL...