21
•
Information represented in battery mode.
Select SW button
State of the UPS
Level
Value
Input
voltage
backup
time
battery
level
output
voltage
Charge
level
Start
x
v
x
-
v
v
v
v
1st click
x
v
x
-
v
v
v
2nd click
x
v
x
-
v
v
v
v
3rd click (return to Start)
x
v
x
-
v
v
v
v
Press > 3 sec (disable
audible warning)
x
v
x
v
-
-
-
-
-
-
-
Repeat press > 3 sec
(enable audible warning)
x
v
x
x
-
-
-
-
-
-
-
fault and overload alarm
x
v
v+error
code
-
-
-
-
-
-
-
-
other alarms and faults
x
x
v+error
code
-
-
-
-
-
-
-
-
Tab. 9.
Battery operating mode.
7.3. audible alarms.
Description
Alarm modulation or tone
Possibility of
muting
State of the UPS
battery mode
beep every 30 s
yes
Warning
Low battery
beep every 2 s
no
overload
beep every 0.5 s
fault
fault
Continuous.
no
Tab. 10.
Audible alarms.
7.4. warning and error or faulT Codes.
Code
Description of the warning
A56
Low battery voltage warning.
A57
Low battery capacity warning.
A59
disconnected battery warning.
A62
defective battery warning.
A64
overload warning.
A66
ePo activated warning.
A68
overtemperature warning.
A86
Low inverter output voltage warning.
Tab. 11.
Warning code.
Code
Error or failure description
e06
Inverter soft-start fault.
e07
high inverter voltage.
e08
Low inverter voltage.
e09
Short circuit at the output.
e11
high battery voltage.
e12
Low battery voltage.
e14
overload at the output.
e15
Unbalanced loads.
e18
fan fault.
e19
overtemperature.
Tab. 12.
Error or fault code.
SPS ADVANCE R & T
UnInTeRRUPTIbLe PoweR SUPPLy (UPS)
USER MANUAL