8. MAINTENANCE, WARRANTY AND SERVICE.
8.1. BATTERY
MAINTENANCE.
t
Pay attention to all of the safety instructions concerning
batteries indicated in section 1.2.3 of manual EK266*08.
t
The service life of the batteries greatly depends on the
ambient temperature and other factors such as the number
of charges and discharges, as well as their depth.
The service life is designed to be between 3 and 5 years if
the ambient temperature is between 10 and 20ºC. Different
types of battery with different service lives are available
upon request.
t
SPS.ADAVANCE RT2 series UPSs require minimum upkeep.
The batteries used in the standard models are lead acid,
sealed, valve regulated and maintenance free. The only
requirement is to charge the batteries regularly to extend
their life expectancy.
While it is connected to the mains supply, whether or not it
is running, it will keep the batteries charged and also offer
protection from overcharging and deep discharge.
8.1.1. Notes for the installation and replacement of the battery.
t
If it is necessary to replace any connection cables, original
materials can be purchased through our
T.S.S.
or authorised
distributors. Using inappropriate cables can lead to over-
heating in connections, which is a fire hazard.
t
Inside the device, there are permanent dangerous
voltages even without mains supply present through
its connection with the batteries and especially in UPSs
where the electronics and batteries share a box.
Also take into consideration that the battery circuit is
not isolated from the input voltage, so there is a risk of
discharge with dangerous voltages between the battery
terminals and the earth terminal, which is in turn connected
to earth (any metal part of the device).
t
Repair and/or maintenance work must be carried out by our
T.S.S.
, except for the replacement of batteries, which can
be performed by qualified personnel familiar with them. No
other person should handle them.
Depending on the configuration of the UPS, certain actions
need to be carried out before handling the batteries:
Devices with batteries and electronics sharing the
same box.
–
Shut down the loads and device completely.
–
Disconnect the SPS.ADVANCE RT2 from the mains.
–
Open the device to access the interior.
–
Remove the fuse or internal battery fuses.
–
Release the battery holders and replace the
batteries.
–
Perform the above steps in reverse to return the
device to how it was at the start, including start-up.
UPS with batteries and electronics in separate boxes.
–
Shut down the loads and device completely.
–
Disconnect the SPS.ADVANCE RT2 from the mains.
–
Disconnect the battery module from the UPS.
–
Open the battery module to access the interior.
–
Remove the fuse or internal battery fuses.
–
Release the battery holders and replace the batteries.
–
Perform the above steps in reverse to return the
device to how it was at the start, including start-up.
8.2. UPS TROUBLESHOOTING GUIDE.
If the UPS does not work properly, check the information shown
on the LCD screen of the control panel and act accordingly
depending on the device model.
Using the Tab. 14 troubleshooting guide, try to resolve the issue
and, if it persists, consult our Technical Service and Support
T.S.S.
If it is necessary to contact our Technical Service and Support
T.S.S.
, provide the following information:
t
UPS model and serial number.
t
Date on which the issue occurred.
t
Full description of the issue, including information provided
by the LCD display or LEDs and state of the alarm.
t
Power supply conditions, type of load and level of load
applied to the UPS, ambient temperature, ventilation
conditions.
t
Battery information (capacity and number of batteries),
whether the device is a (B0) or (B1).
t
Any other information considered relevant.
t
Troubleshooting guide.
YOUR CONNECTION TO SAFETY
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
Thiele KG
• V
orderer W
einberg 26 • D-71522 Backnang • T
el.: +49 (0)7191 3560-0
• Fax.: +49 (0)7191 3560-19
• info@thiele-kg.de
• www
.thiele-kg.de
YOUR CONNECTION TO SAFETY
klick to
www
u-s-v
YOUR CONNECTION TO SAFETY
klick to
www
ACDC-DCDC
YOUR CONNECTION TO SAFETY
klick to
www
SYSTEME
YOUR CONNECTION TO SAFETY
klick to
www
CONTACT
YOUR CONNECTION TO SAFETY
klick to
www
CALLBACK