26

SALICRU

8.  MAINTENANCE, WARRANTY AND SERVICE.

8.1. BATTERY 

MAINTENANCE.

 

t

Pay attention to all of the safety instructions concerning 
batteries indicated in section 1.2.3 of manual EK266*08.

 

t

The service life of the batteries greatly depends on the 
ambient temperature and other factors such as the number 
of charges and discharges, as well as their depth.
The service life is designed to be between 3 and 5 years if 
the ambient temperature  is between 10 and 20ºC. Different 
types of battery with different service lives are available 
upon request.

 

t

SPS.ADAVANCE RT2 series UPSs require minimum upkeep. 
The batteries used in the standard models are lead acid, 
sealed, valve regulated and maintenance free. The only 
requirement is to charge the batteries regularly to extend 
their life expectancy.
While it is connected to the mains supply, whether or not it 
is running, it will keep the batteries charged and also offer 
protection from overcharging and deep discharge.

8.1.1.  Notes for the installation and replacement of the battery. 

 

t

If it is necessary to replace any connection cables, original 
materials can be purchased through our 

T.S.S.

 or authorised 

distributors. Using inappropriate cables can lead to over-
heating in connections, which is a fire hazard.

 

t

Inside the device, there are permanent dangerous 
voltages even without mains supply present through 

its connection with the batteries and especially in UPSs 
where the electronics and batteries share a box.
Also take into consideration that the battery circuit is 
not isolated from the input voltage, so there is a risk of 
discharge with dangerous voltages between the battery 
terminals and the earth terminal, which is in turn connected 
to earth (any metal part of the device).

 

t

Repair and/or maintenance work must be carried out by our 

T.S.S.

, except for the replacement of batteries, which can 

be performed by qualified personnel familiar with them. No 
other person should handle them.
Depending on the configuration of the UPS, certain actions 
need to be carried out before handling the batteries:

 

ˆ

Devices with batteries and electronics sharing the 
same box.

 

Shut down the loads and device completely.

 

Disconnect the SPS.ADVANCE RT2 from the mains.

 

Open the device to access the interior.

 

Remove the fuse or internal battery fuses.

 

Release the battery holders and replace the 
batteries.

 

Perform the above steps in reverse to return the 
device to how it was at the start, including start-up.

 

ˆ

UPS with batteries and electronics in separate boxes.

 

Shut down the loads and device completely.

 

Disconnect the SPS.ADVANCE RT2 from the mains.

 

Disconnect the battery module from the UPS.

 

Open the battery module to access the interior.

 

Remove the fuse or internal battery fuses.

 

Release the battery holders and replace the batteries.

 

Perform the above steps in reverse to return the 
device to how it was at the start, including start-up.

8.2.  UPS TROUBLESHOOTING GUIDE.

If the UPS does not work properly, check the information shown 
on the LCD screen of the control panel and act accordingly 
depending on the device model.
Using the Tab. 14 troubleshooting guide, try to resolve the issue 
and, if it persists, consult our Technical Service and Support 

T.S.S.

If it is necessary to contact our Technical Service and Support 

T.S.S.

, provide the following information:

 

t

UPS model and serial number.

 

t

Date on which the issue occurred.

 

t

Full description of the issue, including information provided 
by the LCD display or LEDs and state of the alarm.

 

t

Power supply conditions, type of load and level of load 
applied to the UPS, ambient temperature, ventilation 
conditions.

 

t

Battery information (capacity and number of batteries), 
whether the device is a (B0) or (B1).

 

t

Any other information considered relevant.

 

t

Troubleshooting guide.

YOUR CONNECTION TO SAFETY

Thiele KG 

• V
orderer W

einberg 26 • D-71522 Backnang • T

el.: +49 (0)7191 3560-0 

• Fax.: +49 (0)7191 3560-19 

• info@thiele-kg.de 

• www

.thiele-kg.de

Thiele KG 

• V

orderer W

einberg 26 • D-71522 Backnang • T

el.: +49 (0)7191 3560-0 

• Fax.: +49 (0)7191 3560-19 

• info@thiele-kg.de 

• www

.thiele-kg.de

YOUR CONNECTION TO SAFETY

klick to

www

u-s-v

YOUR CONNECTION TO SAFETY

klick to

www

ACDC-DCDC

YOUR CONNECTION TO SAFETY

klick to

www

SYSTEME

YOUR CONNECTION TO SAFETY

klick to

www

CONTACT

YOUR CONNECTION TO SAFETY

klick to

www

CALLBACK

Summary of Contents for SPS.ADVANCE RT2

Page 1: ...o thiele kg de www thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de YOUR CONNECTION TO SAFETY klick to www u s...

Page 2: ...el Placez le frontal 401AF000320 A YOUR CONNECTION TO SAFETY Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de Thiele KG Vor...

Page 3: ...2 5 Communication port 5 2 5 1 RS232 and USB port 5 2 6 Smartslotfortheintegrationofanelectroniccommunication unit 5 2 7 Protection against voltage spikes for the modem ADSL fax etc line 5 2 8 Softwar...

Page 4: ...ele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0...

Page 5: ...and may not represent exactly the parts of the equipment shown therefore they are not contractual How ever any divergence that may arise will be remedied or solved with the correct labelling on the un...

Page 6: ...ccess place for any future queries or doubts that may arise The following terms are used interchangeably in the document to refer to t SPS ADVANCE RT2 ADVANCE RT2 ADV RT2 RT2 equipment unit or UPS Uni...

Page 7: ...ion on the device by the user WARNING SPS ADVANCE RT2 0 8 3 kVA This is a category C2 UPS In a residential environment this product may cause radio interference in which case the user must take additi...

Page 8: ...Control panel with LCD display Battery module Plastic front trim Fig 1 Front view of the SPS ADVANCE RT2 and battery module for extended backups SPS ADVANCE RT2 UNINTERRUPTIBLE POWER SUPPLY UPS USER...

Page 9: ...cover Battery connector protective cover RS232 COM port Modem ADSL fax etc line output For connection to external EPO AC power protection fuse Standard 3 000 VA models and B1 AC input IEC connector I...

Page 10: ...rack etc For B0 devices ordered the cost of acquisition installation and connection of the batteries shall always be borne by the customer or distributor and under their responsibility Accessories su...

Page 11: ...ion by adding battery modules t Availability of additional battery chargers to reduce battery recharge time B1 t Intelligent battery management technology is very useful for extendingthelifeofaccumula...

Page 12: ...single common terminal for all of them From the factory all contacts are normally open and can be changed one by one as indicated in the information supplied with the optional extra t The most common...

Page 13: ...ver and strapping all of which are recyclable materials When the packaging requires disposal it must be carried out in accordance with current laws We recommend keeping it for at least 1 year 5 1 2 St...

Page 14: ...height ensuring correct tightening of the fixing screws and appropriate fitting in the machining according to each case Place the device onto the guides and insert it all the way to the back Depending...

Page 15: ...hecontrolpanelwithLCDdisplayonthe plastic front trim t The device is initially set up at the factory for installation as a rack To facilitate the reading of messages on the display when the device is...

Page 16: ...circuit breaker at the output of each transformer since due to its own insulation properties it will prevent the tripping of the protections placed on the primary of the isolation transformer in case...

Page 17: ...nductive loads such as for laser printers or CRT monitors the starting up of these peripherals will need to be taken into account to prevent the device from crashing We do not recommend connecting loa...

Page 18: ...onstitutes a very low voltage safety circuit To preserve the quality must be installed separately from other lines carrying dangerous voltages power distribution line t The RS232 and USB interfaces ar...

Page 19: ...connected loads t It is recommended to charge the batteries for at least 12 hours before using the UPS for the first time For this it will be necessary to supply voltage to the device The battery cha...

Page 20: ...r of the device is not exceeded 6 2 2 UPS start up without mains voltage t If it has a distribution board turn the input and output protections to On t Turn the battery switch to On B0 and B1 t Press...

Page 21: ...UCK Indicates that the device is in buck mode BOOST Indicates that the device is in boost mode Information about battery charge level BATT FAULT Indicates that the battery is not connected Tab 4 Descr...

Page 22: ...rcentage of load consumption Settings or configuration mode Press this button for at least 3 seconds to access this mode when the inverter of the UPS is shut down Button to navigate downwards When thi...

Page 23: ...ly according to the value of the total capacity entered up to the maximum of the current that is possible This results in faster charging and therefore greater availability and more immediate backup i...

Page 24: ...e backup time will be 10 seconds Battery pack Ah Do not change for standard models and adjust in B1 or extended backup models see section 7 3 2 1 Although the device will still work without adjusting...

Page 25: ...voltage is not within the predefined range of the device or there is an AC mains failure the UPS powers the loads from the batteries for a limited time due to their own capacity and activates the audi...

Page 26: ...us start up fault 02 DC bus overvoltage 03 DC bus undervoltage 11 Inverter soft start fault 12 High voltage in the inverter 13 Low voltage in the inverter 14 Inverter output short circuited 27 Battery...

Page 27: ...the batteries Devices with batteries and electronics sharing the same box Shut down the loads and device completely Disconnect the SPS ADVANCE RT2 from the mains Open the device to access the interio...

Page 28: ...ault codes 01 02 03 11 12 13 and 41 are shown on the LCD display The audible alarm sounds continuously An internal fault has occurred in the UPS Contact the distributor or seller or failing that our T...

Page 29: ...ry module connected in series x no packs in parallel group voltage 2 x 2 24 V DC 4 x 2 48 V DC 6 x 2 72 V DC Low battery voltage 22 4 V DC 44 8 V DC 67 2 V DC Blocking voltage for group end of backup...

Page 30: ...ue digital converter ADC t Power factor The power factor PF of an AC circuit is defined as the ratio between active power P and apparent power S or as the cosine of the angle formed by the current and...

Page 31: ...mains phase or three phase when they are powered by three phases Depending on the type of rectification they can be half wave when only one of the half cycles of the current is used or full wave when...

Reviews: