background image

13

7.  GENERAL TECHNICAL  

SPECIFICATIONS

MODEL

500

700

900

1100

1500

2000

Power (VA)

500

700

900

1100

1500

2000

Power (W)

240

360

480

600

900

1200

Technology

Line-interactive

INPUT
Voltage

220 / 230 / 240 VAC.

Margins

162-290 VAC.

Nominal 

frequency

50 / 60 Hz.

Frequency auto-

detect

Yes.

Stabilisation

AVR buck/boost.

OUTPUT
Voltage (VAC)

220 / 230 / 240 VAC.

Voltage accuracy

(1)

± 10 %.

Frequency

(1)

50 / 60 ± 1 Hz.

Waveform

(1)

Pseudo-sine (simulated sine).

Available socket 

types

Schuko (DIN), British (UK), IEC.

MODEL

500

700

900

1100

1500

2000

Transfer time

standard 2-6 ms, maximum 10 ms.

PROTECTION

Input

Thermal self-resetting or fuse (according to the 

model).

Complete 

protection

Overload, battery discharged and overcurrent in the 

charging device.

BATTERY
Type

Sealed Pb-Ca, maintenance free, useful life of 3-5 years.

Charge time

4 -6 hours to charge 90% of its capacity.

Battery 

replacement 

warning

Yes.

Can be replaced by 

the user

Yes.

Capacity (Ah)

4.5

7

9

7

9

Number

1

2

FUNCTIONS

Cold start

Yes.

Auto-test

At start-up.

Automatic restart

Yes, once the operating time has ended and after 

reconnected to the mains.

MODEL

500

700

900

1100

1500

2000

OPTICAL LED INDICATIONS AND ACOUSTIC ALARMS
Normal operation, 

connected to the 

mains

Green LED On

Alarm Off

Mains error and 

UPS in the battery 

mode

Yellow LED flashing

Beeping sound every 10 sec.

Low battery

Yellow LED flashing. Red LED On

Beeping sound every sec.

UPS stopped

Green LED Off

Alarm Off

UPS fault

Red LED On

Constant beeping

COMMUNICATION
Port

USB HID

Software

Supports Windows, Linux, Unix and Mac operating 

systems.

Download from

support.salicru.com

GENERAL
Maximum altitude

2400 m a.s.l.

Relative humidity

Up to 90%, non-condensing.

Temperature

0.. 40ºC.

Acoustic noise at 

1 m.

< 40 dBA.

STANDARDS
Safety

EN-IEC 62040-1, EN-IEC 60950-1.

Electromagnetic 

compatibility. (EMC)

EN-IEC 62040-2.

Quality and 

Environmental 

Management

ISO 9001 and ISO 14001.

DIMENSIONS AND WEIGHT
Depth (mm)

300

320

Width (mm)

101

130 

Height (mm)

142

 182 

Net weight (kg)

3.50

4.45

4.90

8.20

10.40 11.00

(1)

Battery mode.

Tabla 2. 

General technical specifications.

USER MANUAL        

SPS.ONE

 UNINTERRUPTIBLE POWER SUPPLY (UPS) SYSTEMS

Summary of Contents for SPS.ONE Series

Page 1: ...SPS ONE UNINTERRUPTIBLE POWER SUPPLY UPS SYSTEMS USER MANUAL...

Page 2: ...2 SALICRU...

Page 3: ...RATING PRINCIPLE 4 3 1 Features 5 INSTALLATION 5 1 STORAGE LOCATION AND CONDITIONS 5 2 CONNECTING THE UNIT TO THE MAINS FOR THE FIRST TIME OR AFTER IT HAS BEEN OUT OF USE FOR TWO MONTHS 5 3 CONNECTING...

Page 4: ...effort has been made to guarantee that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may be present The images included in this d...

Page 5: ...to understand information Finally once the unit is installed and in operation we recom mend that you keep the documentation in a safe place that is easy to access in case of any future queries that ma...

Page 6: ...g to the specifications of harmonised standards Ref erence standards EN IEC 62040 1 Uninterruptible power systems UPS Part 1 1 General and safety requirements for UPS used in user access areas EN IEC...

Page 7: ...ll always take precedence All of the values for the main specifications or features can be checked on the unit s name plate Act accord ingly for your installation SPS 500 ONE SPS 700 ONE and SPS 900 O...

Page 8: ...E SPS 500 ONE SPS 700 ONE and SPS 900 ONE 1 5 4 3 1 5 4 3 1 5 6 3 4 Fig 3 Rear views with British UK sockets SPS 1100 ONE SPS 1500 ONE and SPS 2000 ONE SPS 500 ONE SPS 700 ONE and SPS 900 ONE 5 2 4 3...

Page 9: ...best protec tion solution for the units and the information that make up both domestic and professional IT environments small businesses offices shops etc The use of AVR Boost Buck technology permanen...

Page 10: ...control mode interface Always bear in mind that the UPS is an electrical gen erator which is why the user must take the necessary precautions to prevent direct or indirect contact 5 1 STORAGE LOCATIO...

Page 11: ...ted Once you have registered you can download the software for each model from the site support salicru com software Use with your installation as with any other type of soft ware When you reboot your...

Page 12: ...e of a problem in the mains the operating time is very short The UPS is overloaded Disconnect critical loads Battery voltage is too low Charge the UPS for at least 6 hours Defective battery It may be...

Page 13: ...start Yes Auto test At start up Automatic restart Yes once the operating time has ended and after reconnected to the mains MODEL 500 700 900 1100 1500 2000 OPTICAL LED INDICATIONS AND ACOUSTIC ALARMS...

Page 14: ...14 SALICRU...

Page 15: ...15 USER MANUAL SPS ONE UNINTERRUPTIBLE POWER SUPPLY UPS SYSTEMS...

Page 16: ...alicru com SALICRU COM Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Reviews: