6.  Maintenance, warranty and 

service.

6.1. 

Basic maintenance guide.

The main guidelines for a correct maintenance are similar to the 
ones that are applying our Service and Technical Support in the 
Preventive maintenance modality (see section 6.5).

6.2.  Battery maintenance.

• 

Pay attention to the safety instructions regarding battery and 
the stated in section 1.2.3.3.

• 

The SPS from SOHO+ series only requires a minimum main-
tenance. The used battery in the standard models is lead 
acid, sealed, VRLA and maintenance free. These models 
require a minimum of reparations. The only requirement 
is to charge the SPS regularly, in order to prolong the bat-
tery lifetime. Meanwhile, it is connected to the power supply, 
never mind if the SPS is ON or OFF, it will keep the batteries 
charged and will give protection against overcharging and 
undercharging.

• 

The SPS has to be charged once, every 4 or 6 months if it 
has not been used for long time.

• 

In hot areas, battery has to be charged every 2 months. The 
charging time has to be 12 hours as minimum.

• 

Under normal conditions, the battery lifetime is from 3 to 5 
years 25º C. In case that the battery was not in good condi-
tions, it has to be replaced before. This replacement has to 
be done by qualified staff.

• 

Always replace them with the same quantity and type.

• 

Do not replace one battery only. All batteries have to be re-
placed at the same time and following the instructions of the 
manufacturer.

• 

Usually, the batteries should be charged and discharged 
every 4 or 6 months. The charging would be started after shut-
down the SPS due to a low battery (discharging). Charging 
time for standard SPS should be 12 hours as minimum.

6.2.1.  Notes for installing and replacing the 

batteries. 

• 

If it is needed to replace the connection of any wire, purchase 
original parts through authorised distributors or service cen-
tres in order to avoid overheating and sparks with fire risk 
because the size is not enough.

• 

Do not short the + and - poles of the batteries, there is risk of 
fire or electrocution.

• 

Be sure that there is no voltage before touching the batteries. 
Battery circuit is not isolated from the input. Hazardous volt-
ages can be found between the battery and earth terminals

• 

Although the input circuit breaker the switchgear panel is 
turned off, the internal parts of the SPS are still connected to 
the batteries, so there are hazardous voltages inside.

Therefore, before doing any reparation or maintenance task, 
the internal battery fuses have to be removed and/or the in-
terlink connections between them and the SPS.

• 

Batteries have hazardous voltages. The battery maintenance 
and replacement have to be done by qualified personnel and 
familiarised with them. Nobody else can manipulate them.

6.3.  SPS troubleshooting guide.

If the SPS doesn’t work properly, check the information given by 
the LCD of the control panel. Try to solve the problem by means 
of the established steps in the table 3. In case the problem per-
sists, consult with our Service and Technical Support S.T.S..

When it is needed to contact with our Service and Technical Sup-
port S.T.S. , provide the following information:

• 

SPS model and serial number.

• 

Date when the problem occurred.

• 

Complete description of the problem, including the informa-
tion given by the LCD panel and the status of the alarms.

• 

Power supply condition, type of load and the level connected 
to the SPS, ambient temperature, cooling conditions.

• 

Other informations that you may think that they are important.

Symptom

Possible Cause

Remedy

LCD display is not 
illuminated

1. Unloaded battery.

1. Charge battery up to 
8 hours.

2. Battery defect.

2. Replace with the 
same type of battery.

3.When the Input cord 
isn’t electrified and 
Power switch is not 
pressed.

3. Press the power 
switch again or test the 
Input cord.

Alarm buzzer beeps 
continuously when AC 
supply is normal.

Overload of the UPS.

Verify that the load 
matches the UPS 
capability specified in 
the specs.

When power failure, 
back-up time is 
shorten.

1. Overload of the UPS.

1. Remove some 
noncritical load.

2. Battery voltage is 
too low.

2. Charge battery 8 
hours or more.

3. Battery defect due 
to high temperature 
operation environment, 
or improper operation to 
battery.

3. Replace with the 
same type of battery.

Communication lost 
between UPS and 
computer.

1. Software is not 
installed well.

1. Check the setting of 
the software .

2. Cable is not properly 
connected.

2. Check the USB cable 
is firmly connected 
to the computer and 
confirm the setting 
again.

Mains normal but LCD 
display Battery mode.

1. Circuit breaker 
tripped.

1. Reset the circuit 
breaker.

2. Power cord is loose.

2. Reconnect the power 
cord properly.

Table 3. 

SPS troubleshooting guide.

6.4.  Warranty conditions.

The limited warranty only applies to those products that you ac-
quire for commercial or industrial use in the normal development 
of your business.

Summary of Contents for SPS SOHO+ series

Page 1: ...SUPPLY UPS LIGHTING FLOW DIMMER STABILIZERS ILUEST SWITCH MODE POWER SUPPLY STATIC INVERTERS PHOTOVOLTAIC INVERTERS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS SPS SOHO series USER S MANUAL UNINTE...

Page 2: ......

Page 3: ...considered in the installation 4 2 Equipment reception 4 2 1 Unpacking and contents checking 4 2 2 Storing 4 2 3 Location 4 2 4 Battery charging 4 3 Communication ports 4 3 1 Description and features...

Page 4: ...respect such instructions can damage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instructions and features for the equipment safety...

Page 5: ...or the smallest devices the ones connected with the fore seen power cord with plug the user has to check the wall outlet corresponds with the type of supplied plug with earth duly installed and connec...

Page 6: ...d sprinkling or spillage that could enter through the slots or cooling grids which may cause fire or electric shock Do not clean the equipments with products that could have alcohol benzene solvent or...

Page 7: ...he working day proceed to the load shutdown and then to the equipment too by following the op erating described in this User s manual When the equipment and or battery module has a protec tion through...

Page 8: ...ve EMC In accordance with the specifications of the harmonized stand ards Standards as reference EN IEC 62040 1 Uninterruptible power supply SPS Part 1 1 General and safety requirements for SPS used i...

Page 9: ...in features or specifications can be checked in the nameplate of the equipment Keep them in mind for its installation 1 LCD Back Light 2 Power ON OFF Switch Fig 1 Front view from SOHO 400 600 800 VA 1...

Page 10: ...charging the batteries In the event of mains absent or incorrect off margins the inverter supplies pseudo sinusoidal wave energy from the batteries for a limited time When the mains returns or finds i...

Page 11: ...afety standard EN IEC 62040 1 To calculate the input current the power factor and the efficiency of the equipment have been considered Overload conditions are considered as nonpermanent and exceptiona...

Page 12: ...the software When downloading the needed files from Internet enter the following licence to install the software 511C1 01220 0100 478DF2A When the computer is rebooted WinPower software will be shown...

Page 13: ...LCD display The LED will always turns on when SPS works including in off charging mode and fault mode When LCD start to work it will display all information for 3s INPUT Unit V AC LINE MODE AVR OUTPU...

Page 14: ...attery voltage 11 V 11 V Battery voltage 11 5 V 11 5 V Battery voltage 12 5 V Battery voltagea 12 5 V Battery level Table 2 Battery level When over load the mark will flicker every 1 second When batte...

Page 15: ...ill connected to the batteries so there are hazardous voltages inside Therefore before doing any reparation or maintenance task the internal battery fuses have to be removed and or the in terlink conn...

Page 16: ...aused by a wrong use negligence installation and or inadequate testing tentative of repairing or not authorized modification or any other cause beyond the foreseen use or by accident fire lightnings o...

Page 17: ...cond Overload Sounding every 0 5 seconds Battery replace Sounding every 2 seconds Fault Continuously sounding Buck Boost with 70 SPS load Sounding every 0 5 seconds after 25 min and fault after 30 min...

Page 18: ...the magnetic and thermal Joule effect So the de vice has two parts an electromagnetic and a b i metal plate connected in series and the current is circulating through them to the load LAN LAN is the a...

Page 19: ...19 SALICRU...

Page 20: ...NCIA VALLADOLID ZARAGOZA BRANCHES AND SERVICES AND TECHNICAL SUPPORT S T S CHINA FRANCIA HUNGR A MARRUECOS M XICO PORTUGAL REINO UNIDO SINGAPUR SUBSIDIARIES ALEMANIA ARABIA SAUD ARGELIA ARGENTINA B LG...

Reviews: