background image

13

SALICRU

5.  Installation.

•  Check the Safety instructions (see chapter 2).
•  Check that the data in the nameplate are the required by the 

installation.

•  A wrong connection or manoeuvring, can make faults in the 

UPS and/or loads connected to itself. Read carefully the in-

structions of this manual and follow the stated steps in the 

established order.

• 

This UPS has to be installed by qualified staff and it 

can be used by personnel with no specific training, 

just with the help of this «Manual» only.

• 

All connections of the equipment including the control 

(interface, remote panel, ...), will be done with the 

switches at rest and no voltage present (UPS power supply 

switch to «Off»).

• 

Never forget that the UPS is an electrical energy gener-

ator, so the user has to take the needed cautions against 

direct and indirect contacts.

•  When there is only one equipment, omit all the instructions 

and their implicit connections as regards to parallel systems.

•  Parallel system installation needs a switchgear panel with 

input, output and static bypass single protections (the last 

one for TWIN/3 PRO models higher than 10 kVA only), and a 

manual bypass too.
This switchgear panel allows isolating only one equipment 

from the system, when facing any malfunctioning and sup-

plying the loads with the rest of equipments during the pre-

ventive maintenance or during the reparation of itself.
Under request a manual bypass panel can be supplied for a 

single equipment or a particular system.

• 

In parallel systems, the length and cross section of the 

cables that go from the switchgear panel till one of the 

UPSs and vice versa, will be the same for all of them without 

any exception.

• 

Battery circuit is not isolated from input voltage. Haz-

ardous voltages can be found out between the battery 

terminals and earth. Check that there is not input voltage be-

fore doing any intervention on them.

5.1.  To be considered in the 

installation.

•  All the equipments and battery sets have terminals as con-

nection parts for power and connectors for communications.

•  Terminals for separate bypass line are only available in TWIN/3 

PRO models higher than 10 kVA.

•  Cross cable section of the input and output lines, will be cal-

culated from the currents stated in the nameplate of each 

equipment, and respecting the Local and/or National Low 

Voltage Electrotechnical Regulations.
For the bypass current stated in the nameplate, has to be 

considered two groups of equipments:

 

ˆ

Equipments up to 10 kVA TWIN/3 PRO. Current on 

phase R is higher to the other two, because the input of 

the UPS is common with the bypass line. 

 

ˆ

Equipments > 10 kVA TWIN/3 PRO. These equipments 
have separate terminals for UPS input and bypass line.

•  Protections of the switchgear panel, will have the following 

features:

 

ˆ

For input and bypass lines, type B for RCD devices and 

C characteristic for circuit breakers.

 

ˆ

For the output (load feeding), C characteristic for circuit 

breaker.

Regarding the size, they will be as minimum to the currents 

stated in the nameplate of each UPS. Pay attention to the 

UPSs up to 10 kVA and three phase input, because a four 

pole switch has to be fitted in as input protection and a 

second one of two poles between this one and the own UPS, 

in order to protect the phase R and neutral.

•  In the nameplate of the equipment there are only printed the 

nominal currents as it is stated in the safety standard EN-IEC 

62040-1. To calculate the input current, the power factor and 

the efficiency of the equipment have been considered.
Overload conditions are considered as nonpermanent and 

exceptional operating mode.

•   If it is added peripherals to the input, output or bypass like trans-

formers or autotransformers to the UPS, the currents stated in 

the own nameplates of those elements has to be considered 

in order to use the suitable cross sections, by respecting the 

Local and/or National Low Voltage Regulation 

• 

When an equipment incorporates a galvanic isolation 

transformer, as standard, as an option or either in-

stalled by yourself, either at the UPS input, bypass line, 

output or at all of them, protections against indirect contact 

has to be fitted in (residual current device) at the output of 

each transformer, because due to its specification of isolation 

it will prevent the triggering of the protections fitted in the pri-

mary of the transformer in case of electrical shock in the sec-

ondary (output of the isolation transformer) 

•   Remind you that all external isolation transformers already 

installed or supplied from factory, has the neutral of the sec-

ondary connected to earth by means of a cable bridge be-

tween both terminals. If it were required an isolated output 

neutral, remove this cable bridge, keeping the precautions 

stated in the respective local and/or national low voltage reg-

ulations.

•  All standard UPSs have batteries in the same enclosure of 

the equipment , less those ones as B0 and B1. In the first 

ones, the battery protection is by internal fuses and there is 

no access to the end-user.
Accumulator cabinet or modules have battery protection 

too, and in this case, they are duplicated. An internal ones 

through fuses with no access for the end-user and an addi-

tional ones by means of a two pole circuit breaker.

• 

IMPORTANT FOR SAFETY: In case of installing the 

batteries by yourself, the accumulators have to be pro-

vided with a two pole circuit breaker protection sized to the 
features stated in table 2.

5.2.  Reception of the equipment.

5.2.1.  Unpacking, content checking and 

inspection.

•   To unpacking, see section 5.2.3.
•  On receiving the device, make sure that it has not suffered 

any damage in transport (impact, drop, ...) and its features 

correspond with the ones in the order, so it is recommended 

to unpack the UPS and make a first visual inspection.

Summary of Contents for UPS SLC TWIN PRO series

Page 1: ...UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL UPS SLC TWIN PRO series 4 20 kVA...

Page 2: ......

Page 3: ...on 5 3 9 Software 5 3 10 Considerations before starting up the connected loads 6 Operating 6 1 Commissioning 6 1 1 Controls before commissioning 6 2 Start up and shutdown of the UPS 6 2 1 Start up of...

Page 4: ...l exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The images in...

Page 5: ...installation and commissioning in an easy and ordered way without doubt Finally once the equipment is installed and operative for future requests or doubts that could arise it is recommended to keep...

Page 6: ...IEC 62040 2 Uninterruptible power supply UPS Part 2 EMC requirements The manufacturers responsibility is excluded in the event of any modification or intervention in the product by the customer s sid...

Page 7: ...due to the constant evolution of the product some discrepancies or small contradictions can arise In front of any doubt the labelling of the equipment will always prevail Figures regarding its main f...

Page 8: ...slot EPO RS 232 USB Protection cover for external batteries IEC output connectors Protection cover for manual bypass switch maintenance and output Protection cover for power blocks USB RS 232 EPO Pro...

Page 9: ...9 SALICRU Battery switch Protection cover for power blocks Batteries module for models 10 kVA Batteries module for models up to 10 kVA Battery switch Power blocks Fig 3 Rear view batteries module...

Page 10: ...ith no accessories screws and electrical cables Batteries owned by the client will be installed out from the case or cabinet of the UPS Under request it is possible to supply the acces sories screws a...

Page 11: ...low input current distortion so mains pollution is decreased Great adaptability to the worst conditions of the input mains Wide margins of the input voltage frequency range and wave shape so it is av...

Page 12: ...adaptor The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of controlling and management at the manager system dis posal This f...

Page 13: ...es type B for RCD devices and C characteristic for circuit breakers For the output load feeding C characteristic for circuit breaker Regarding the size they will be as minimum to the currents stated i...

Page 14: ...o the instructions described in this manual and charge them for 12 hours In parallel systems it is not needed to make the connection among the equipments to charge the batteries It can be treated as s...

Page 15: ...correct torque in the screws of the power blocks In installations with only one UPS the Jumper cable as bridge mode connected from factory between the terminals JP1 and JP2 has to be kept as it is Fo...

Page 16: ...the power contactor 2 with 400V AC coil and NO contact of 5A 1A at least 4 Cable installed from factory as a bridge mode in any TWIN 3 PRO 10 kVA equipment Remove this cable fitted in as a bridge mode...

Page 17: ...connection JP2 Output neutral N Output phase U L Output earth bonding UPS connection power block TWIN PRO UPS connection power block TWIN 3 PRO 10 kVA UPS connection power block TWIN 3 PRO up to 10 k...

Page 18: ...the first bat tery module and from this last negative to the second module and so on Proceed in the same way to connect the red posi tive cable and the green yellow earth cable In parallel systems th...

Page 19: ...and it can t be extended under any other concept due to the risk of interfer ences and communication failures that it could cause In those installations with only one UPS the Jumper cable as bridge mo...

Page 20: ...ion software 5 3 8 2 Smart slot UPS s have a unique slot for TWIN PRO and two slots for TWIN 3 PRO hidden rear the covers stated in the views of the equipment One of them allows inserting the SNMP car...

Page 21: ...h makes a user friendly interface of monitoring and management This software supplies an auto Shutdown for a system based on several PCs in case of an electrical blackout With this soft ware the end u...

Page 22: ...will be done gradually to avoid any problem as minimum in the first commissioning If inductive loads with big inrush current apart from sensi tive ones are required to be connected like laser printers...

Page 23: ...ck that the battery switch is in position On models B0 and B1 Turn the input M1 and bypass M2 circuit breakers to On Switch M2 is only available in models TWIN 3 PRO 10 kVA In equipments with single p...

Page 24: ...sfer to Bypass mode Put all the equipments on manual bypass To do it re move the cover from manual bypass switch which is located at the back of each equipment and turn all the switches to position BY...

Page 25: ...S T S Press over the shutdown key in any UPS for more than 3 seconds and each one will be shutdown supplying output voltage through the bypass Turn On the output circuit breaker switch of the distrib...

Page 26: ...UPS and put the mechanical lock To avoid wrong manoeuvring the mechanical lock has to be fit otherwise the equipment and loads are exposed to serious damages even the de struction of both or fire Turn...

Page 27: ...r 1 sec as minimum to validate the modified option and change the settings Table 6 Functionality of the buttons or keypad of the control panel The UPS has a control panel with the following parts Four...

Page 28: ...s UPS only 8 20 kVA TWIN 3 Blue 81 Fault Heatsink over temperature Red Code Condition Description Color LCD 82 Alarm Ambient over temperature UPS only 4 10 kVA TWIN Blue 83 Alarm Ambient NTC abnormal...

Page 29: ...UPS power supply information single phase input Fig 17 Main screen of the equipment with single phase input Information of load level connected to the UPS UPS power supply information three phase inpu...

Page 30: ...ls due to fault or wrong the equipment will transfer to Battery mode to feed the load s properly Fig 24 Frequency converter mode screen This function can be activated through the settings of the contr...

Page 31: ...beadaptedto the own needs and optimise the function of the equipment 7 3 1 Main screen From main screen when pressing the key or for less than 1 sec it is shown detailed information about the alarm pa...

Page 32: ...UPS status menu Structure of main menu Press 1 sec Fig 31 UPS status screen Press 1 sec Press o 1 sec Structure of Data logger submenu Structure of main menu Press 1 sec Fig 32 Event logger submenu Pr...

Page 33: ...T S password only Fig 34 Control submenu screens 7 3 5 Control submenu When pressing the key the key for less than 1 sec from this Control submenu it is accessed to the control structure see figure 34...

Page 34: ...ation from factory 7 4 1 Operating on ECO mode 7 4 1 1 Short description of the ECO mode ECO mode function allows supplying the load s from mains directly through the internal filters only meanwhile t...

Page 35: ...rs or service cen tres in order to avoid overheating and sparks with fire risk because the size is not enough Do not short the and poles of the batteries there is risk of fire or electrocution Be sure...

Page 36: ...ooling and the ambient temperature of the room NTC abnormal UPS internal fault Consult with the S T S Communication cable male disconnected Para cable Male Loss Alarm code E3 Parallel bus cable is dis...

Page 37: ...er Under Voltage Inv Under Voltage Alarm code 33 UPS internal fault Consult with the S T S Inverter Softstart Failed Inv Softstart Fail Alarm code E34 UPS internal fault Consult with the S T S Negativ...

Page 38: ...ypothetical fault 8 3 2 Out of scope of supply Our company is not forced by the warranty if it appreciates that the defect in the product doesn t exist or it was caused by a wrong use negligence insta...

Page 39: ...oad 2 Voltage THD with non linear load 5 Output voltage recovering time 100 ms IEC 62040 3 70 ms IEC 62040 3 60 ms IEC 62040 3 Transient response of the output voltage with load fluctuation of 0 100 0...

Page 40: ...ending on model 273 V DC 13 65 V DC block 4 A 345 6 V DC 14 4 V DC block Floating voltage block set 13 65 V DC 273 V DC 13 65 V DC 327 6 V DC Maximum charging current 1 A 1 4 A 4 A Recharging time 5 h...

Page 41: ...mitting Diode Circuit breaker A circuit breaker or switch is a device ready to break the electrical current of a circuit when it over comes the maximum set values On Line mode Regarding to an equipmen...

Page 42: ...42 USER MANUAL...

Page 43: ...43 SALICRU...

Page 44: ...mpany salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Se...

Reviews: